TDD-D-1Vertical Highboy, LowboyFront Flue, Lowboy Rear Flue,Downflow/HorizontalOil-Fired FurnaceFREEDOM 80FREEDOM 80with Comfort-RHighboy VerticalAHV1M087A936,V3,SAAAHV1M087A948,V5,SAADownflow/HorizontalFront FlueADF1M087A936,V3,SAAADF1M087A948,V5,SAALowboy Front Flue<strong>ALF</strong>1M087A936,V3,SAA<strong>ALF</strong>1M087A948,V5,SAALowboy Rear FlueALR1M087A936,V3,SAAALR1M087A948,V5,SAAPUB. NO. 12-1205-03


GeneralFeaturesOil Furnace ModelsCentral heating <strong>oil</strong> <strong>furnace</strong> models are designed to meetU.L.standards and are certified by ETL. Limit settingand rating data were established and approved understandard rating conditions using U.L.Safe OperationOil <strong>furnace</strong> models ship with Beckett Burners that utilizecad cells for flame sensing and a safety lockout featureto prevent excess <strong>oil</strong> buildup in the combustionchamber if ignition fails. The burner also includes avalve delay on cycle and clean cut solenoid valve forsmooth ignition.Quick HeatingDurable, cycle tested, hot rolled, 13 gauge steel heatexchanger quickly transfers heat to provide warmconditioned air to the structure.BurnerModel AF Beckett Burner with valve delay on & "cleancut"<strong>oil</strong> pump for safety and efficient combustion.ControlsProven fan limit control for reliable operation isadjustable to avoid cold drafts. The <strong>oil</strong> <strong>furnace</strong> fancenter is rated at 40VA for use with a cooling systemand accessories.Air DeliveryMultispeed, direct drive blower motor, has sufficientairflow for most heating and cooling requirements, willswitch from heating to cooling speeds on demand fromroom thermostat. Variable speed models tailor air flowfor varied cooling capacities.StylingHeavy gauge, steel cabinet construction with two colorpowder paint for attractive appearance and durability.The heat exchanger section of the cabinet is completelylined with f<strong>oil</strong> faced fiberglass insulation and the blowercompartment includes a sound reduction insulation.This results in quiet and efficient operation due to theexcellent acoustical and insulating qualities of fiberglass.A bottom pan is built into the blower compartmentwith alternate back, left side or right side return airconnection provision.© 2006 American Standard Inc. All Rights Reserved2 Pub. No. 12-1205-03


ContentsFeature SummaryFeatures and BenefitsStandard EquipmentOptional EquipmentGeneral DataAHV1M087A936SAAAHV1M087A948SAA<strong>ALF</strong>1M087A936SAA<strong>ALF</strong>1M087A948SAAALR1M087A936SAAALR1M087A9486SAAADF1M087A936SAAADF1M087A948SAAAHV1M087A936SAAAHV1M087A948SAA<strong>ALF</strong>1M087A936SAA<strong>ALF</strong>1M087A948SAAALR1M087A936SAAALR1M087A9486SAAADF1M087A936SAAADF1M087A948SAAPerformance DataElectrical DataField WiringDimensions2469172124Pub. No. 12-1205-033


Featuresand BenefitsFreedom 80 STANDARD EQUIPMENT• Up to 82.4% Annual FuelUtilization Efficiency (AFUE)• 13 gauge hot rolled steel wraparound heat exchanger fordurability• Beckett Flame Retention Burneroperates cleanly and quietly• Burner features include primarycontrol with interrupted ignitionfor reliability, pre-purge andclean cutoff solenoid valve forsmooth ignition• Burner and controls factorywired• Dual clean out ports for quickaccess and easy cleaning• Direct drive, permanentlylubricated, 4 speed blowermotor on Freedom 80 models• Variable speed blower motorson Freedom 80 with Comfort-Rmodels• Insulated blower compartment• Slide out blower assembly forquick cleaning and serviceaccessibility• Filter rack with cleanable filter(Highboy & Lowboy Models)except Downflow/Horizontal• 5 year parts limited warrantyand lifetime heat exchangerwarranty• Preformed ceramic fibercombustion chamber for higherefficiencies and more completecombustion• 40 VA control transformer foradd on cooling• Heavy gauge, painted (twotone), steel cabinet• Recessed door handles for easyremoval of highboy & lowboyFurnace doors• Lowboy models available withfront or rear flue• Highboy models with top or rightside venting• Downflow/Horizontal model fieldconvertible from downflow toright or left horizontal• 6” Left and Right side fresh airknockouts – Highboy andLowboy Models• Barometric draft regulatorincluded• Heat exchanger cabinet sectionlined with f<strong>oil</strong> faced insulation4 Pub. No. 12-1205-03


Featuresand BenefitsOPTIONAL EQUIPMENTDownflow Subbase - TDF1M087A936, 948SAA ....................................................................................... BAYSUB10ABASEAA [ ]Trim Kit - Horizonatal Right Vent - Top Cover and Vent Trim Ring - THV1M087A936, 948SAA ................... BAYTRM10AVENTAA [ ]Thermostat, Prog.,7Day, 1-Stage Htg. / Clg. .................................................................................................... ACONT800AS11A [ ]Thermostat, Prog.,7Day, 3 Htg. / 2 Clg. .........................................................................................................ACONT802AS32DA [ ]Thermostat, Prog.,7Day, 3 Htg. / 2 Clg w/dehumidification. ...........................................................................ACONT803AS32DA [ ]Thermostat, Prog.,5/1/5 Day, 1-Stage Htg. / Clg. ............................................................................................. ACONT600AF11M [ ]Thermostat, Prog.,5/1/5 Day, 2 Htg. / 2 Clg. ..................................................................................................... ACONT602AF22M [ ]Thermostat, Mechanical 1-Stage Htg. / Clg.1 ......................................................................................................... ASYSTAT610[ ]Thermostat, Mechanical 2-Stage Htg. / Clg 1 ........................................................................................................ ASYSTAT611[ ]Subbase Auto Changeover - ASYSTAT610,611 .................................................................................................... ASYSTAT616 [ ]Add-on Heat Pump Kit ........................................................................................................................................ TAYPLUS103A [ ]Bonnet thermostat-( required with TAYPLUS103A) ....................................................................................................... THT1248 [ ]1 Requires subbase with isolated RC & RH terminals.Pub. No. 12-1205-035


GeneralDataOil Fired Furnace SpecificationsModelAHV1MO87A936 & 948SAA<strong>ALF</strong>1MO87A936 & 948SAAALR1MO87A936 & 948SAAADF1MO87A936 & 948SAAType Upflow - Highboy Upflow - Lowboy Downflow - HorizontalHeat input Rate (BTUH): 140,000 119,000 105,000 84,000 140,000 119,000 105,000 84,000 140,000 119,000 105,000 84,000Nominal Thermal Efficiency (%): 83.6 84.2 83.8Heating Capacity (BTUH): 114,000 98,000 87,000 70,000 114,000 98,000 87,000 70,000 114,000 98,000 87,000 70,000Nominal Temperature Rise (deg. F): 85 85 85Minimum AFUE (I.C.S.) Rating (%):Burner Specifications:AHV1MO87A936SAA - 82.4%AHV1MO87A948SAA - 82.6%R.W. Beckett Pressure AtomizingType, Model AF<strong>ALF</strong>1MO87A936SAA - 82.0%<strong>ALF</strong>1MO87A948SAA - 82.7%ALR1MO87A936SAA - 82.0%ALR1MO87A948SAA - 82.4%R.W. Beckett Pressure Atomizing Type,Model AFADF1MO87A936SAA - 81.7%ADF1MO87A948SAA - 82.6%R.W. Beckett Pressure Atomizing Type,Model AFAir Tube Length (in.): 5.875, Effective 5.875, Effective 5.875, EffectiveBurner Head Type: Fixed, Flame Retention Fixed, Flame Retention Fixed, Flame RetentionFuel Type: # 2 Distillate (Domestic Heating Oil) # 2 Distillate (Domestic Heating Oil) # 2 Distillate (Domestic Heating Oil)Nozzle Rating For Beckett AF (GPM): 1.00 0.85 0.75 0.60 1.00 0.85 0.75 0.60 1.00 0.85 0.75 0.60Spray Angle (deg.): 80 80 80Spray Pattern: Hollow Hollow HollowOil Pump Pressure (PSIG): 130 130 130Ignition Control Type: Interrupted, Direct Spark Interrupted, Direct Spark Interrupted, Direct SparkPre / Post Purge Feature(s): Yes / no Yes / no Yes / noAutomatic Oil Solenoid Valve: Yes Yes YesBlower Drive: Direct Direct DirectAHV1MO87A936SAA AHV1MO87A948SAA <strong>ALF</strong>1MO87A936SAAALR1MO87A936SAA<strong>ALF</strong>1MO87A948SAAALR1MO87A948SAAADF1MO87A936SAA ADF1MO87A948SAADiameter x Width (in.): 10 x 9 11 x 11 10 x 9 10 x 9 10 x 9 11 x 9No. Used: 1 1 1 1 1 1Speeds (no.): 4 4 4 4 4 4CFM vs in. w.g.: See Fan Performance Table See Fan Performance Table See Fan Performance TableMotor HP: 1/2 3/4 1/2 3/4 1/2 3/4R.P.M.: 1075 1130 1075 1130 1075 1130Volts / Ph. / Hz.: 120 / 60 / 1 120 / 60 / 1 120 / 60 / 1Filter Furnished?: Yes Yes NoType Recommended: Throwaway Throwaway ThrowawayNo. - Size x Thick: 1 - 16 x 25 x 1 2 - 10 x 20 x 1 Not SuppliedVent - Size (in.): 6 6 6Gross Heat Exchanger Area (sq. ft.): 27.8 27.8 (Front Flue) / 30.0 (Rear Flue) 27.8Suply / Return Size (in. x in.): See Outline Drawing See Outline Drawing See Outline DrawingCombustion Chamber Type:Preformed, Refactory(Ceramic Fiber Matrix Material)Preformed, Refactory(Ceramic Fiber Matrix Material)Preformed, Refactory(Ceramic Fiber Matrix Material)Total Current (amps.): 12.1 19.8 12.1 19.8 12.1 19.8Max. Fuse Size (amps.): 15 30 15 30 15 30Dimensionsuncrated (in.):WeightShipping (lbs.) / Net (lbs.)H X W X D58 X 22.25 X 31H X W X D41.5 X 22.25 X 47H X W X D22.25 X 61.25 X 22.25260 / 250 300 / 290 280 / 2706 Pub. No. 12-1205-03


GeneralDataOil Fired Furnace SpecificationsModelAAHV1MO87A9V3 & 9V5SAA<strong>ALF</strong>1MO87A9V3 & 9V5SAAALR1MO87A9V3 & 9V5SAAADF1MO87A9V3 & 9V5SAAType Upflow - Highboy Upflow - Lowboy Downflow - HorizontalHeat input Rate (BTUH): 140,000 119,000 105,000 84,000 140,000 119,000 105,000 84,000 140,000 119,000 105,000 84,000Nominal Thermal Efficiency (%): 83.6 84.2 83.8Heating Capacity (BTUH): 114,000 98,000 87,000 70,000 114,000 98,000 87,000 70,000 114,000 98,000 87,000 70,000Nominal Temperature Rise (deg. F): 85 85 85Minimum AFUE (I.C.S.) Rating (%):Burner Specifications:AHV1MO87A9V3SAA - 82.4%AHV1MO87A9V5SAA - 82.6%R.W. Beckett Pressure AtomizingType, Model AF<strong>ALF</strong>1MO87A9V3SAA - 82.0%<strong>ALF</strong>1MO87A9V5SAA - 82.7%ALR1MO87A9V3SAA - 82.0%ALR1MO87A9V5SAA - 82.4%R.W. Beckett Pressure Atomizing Type,Model AFADF1MO87A9V3SAA - 81.7%ADF1MO87A9V5SAA - 82.6%R.W. Beckett Pressure Atomizing Type,Model AFAir Tube Length (in.): 5.875, Effective 5.875, Effective 5.875, EffectiveBurner Head Type: Fixed, Flame Retention Fixed, Flame Retention Fixed, Flame RetentionFuel Type: # 2 Distillate (Domestic Heating Oil) # 2 Distillate (Domestic Heating Oil) # 2 Distillate (Domestic Heating Oil)Nozzle Rating For Beckett AF (GPM): 1.00 0.85 0.75 0.60 1.00 0.85 0.75 0.60 1.00 0.85 0.75 0.60Spray Angle (deg.): 80 80 80Spray Pattern: Hollow Hollow HollowOil Pump Pressure (PSIG): 130 130 130Ignition Control Type: Interrupted, Direct Spark Interrupted, Direct Spark Interrupted, Direct SparkDelay valve on / Post Purge Feature: Yes / no Yes / no Yes / noAutomatic Oil Solenoid Valve: Yes Yes YesBlower Drive: Direct Direct DirectAHV1MO87A9V3SAA AHV1MO87A9V5SAA <strong>ALF</strong>1MO87A9V3SAAALR1MO87A9V3SAA<strong>ALF</strong>1MO87A9V5SAAALR1MO87A9V5SAAADF1MO87A9V3SAA ADF1MO87A9V5SAADiameter x Width (in.): 10 x 9 12 x 9 10 x 9 11 x 9 10 x 9 12 x 9No. Used: 1 1 1 1 1 1Speeds (no.): Variable Variable Variable Variable Variable VariableCFM vs in. w.g.: See Fan Performance Table See Fan Performance Table See Fan Performance TableMotor HP: 1/2 1 1/2 1 1/2 1Volts / Ph. / Hz.: 120 / 60 / 1 120 / 60 / 1 120 / 60 / 1Filter Furnished?: Yes Yes NoType Recommended: Hi Velocity Hi Velocity Hi VelocityNo. - Size x Thick: 1 - 16 x 25 x 1 2 - 10 x 20 x 1 Not SuppliedVent - Size (in.): 6 6 6Gross Heat Exchanger Area (sq. ft.): 27.8 27.8 (Front Flue) / 30.0 (Rear Flue) 27.8Suply / Return Size (in. x in.): See Outline Drawing See Outline Drawing See Outline DrawingCombustion Chamber Type:Preformed, Refactory(Ceramic Fiber Matrix Material)Preformed, Refactory(Ceramic Fiber Matrix Material)Preformed, Refactory(Ceramic Fiber Matrix Material)Total Current (amps.): 13.5 18.8 13.5 18.8 13.5 18.8Max. Fuse Size (amps.): 15 30 15 30 15 30Dimensionsuncrated (in.):WeightShipping (lbs.) / Net (lbs.)H X W X D58 X 22.25 X 31H X W X D41.5 X 22.25 X 47H X W X D22.25 X 61.25 X 22.25260 / 250 300 / 290 280 / 270Pub. No. 12-1205-037


GeneralDataFurnace Model:AllBurner Model:R.W. Beckett, AFStandard Nozzle:Delavan, 0.75 GPH / 80 deg. angle /hollow coneOil Pump Pressure (PSIG): 130Burner Head Type:F3Head / Turbulator Setting:“Z” = 1.125 in.Air Band Setting:Fully-closedAir Shutter / Damper Setting: 5Overfire Draft (in. W.G.): 0.02Smoke Spot, Maximum (Bacharach Scale): # 1Carbon Dioxide, CO 2 , Maximum (%): 13Carbon Dioxide, CO 2 , Minimum (%): 12*Carbon Monoxide, CO (PPM) 0Oil Solenoid Valve Equipped:YESDelay valve on Time (sec):Postpurge Time (sec):15 sec.NoneIgnition Type:InterruptedOil Burner Application and Specifications* When operating these <strong>furnace</strong>s at the lowest input rate (84,000 BTUH), the carbon dioxide (CO 2) value may notbe able to be adjusted above 12%. This is normal and does not necessarily indicate a problem.High Limit Thermostat Setting (deg. F.):230 (highboy / lowboy models)190 (horizontal / downflow model)Fan “On” Setting (deg. F.): 130Fan “Off” Setting (deg. F.): 100Standard Fan Speed as shipped Low, Orange Wire to “L” TerminalStandard Furnace Fan / Limit Control and Speed Settings8 Pub. No. 12-1205-03


PerformanceDataFurnace Airflow (CFM) vs. External Static Pressure (in. WC)Model Speed Tap 0.1 0.2 0.3 0.4 0.5 0.6 0.7High 1508 1468 1407 1345 1278 1202 1120HighboyAHV1M087A936SAMed-High 1420 1361 1310 1242 1176 1096 1019Med-Low 1308 1263 1220 1174 1103 1031 953Low 1189 1150 1113 1072 1009 936 870High 1974 1913 1854 1766 1695 1621 1547HighboyAHV1M087A948SAMed-High 1694 1643 1589 1534 1477 1406 1339Med-Low 1413 1384 1348 1315 1280 1235 1184Low 1166 1144 1127 1105 1076 1027 983High 1688 1648 1595 1522 1447 1373 1309LowboyFront Flue<strong>ALF</strong>1M087A936SAMed-High 1372 1331 1290 1246 1200 1146 1079Med-Low 1173 1156 1134 1108 1082 1043 989Low 999 993 975 956 931 888 807High 1920 1822 1730 1649 1564 1483 1397LowboyFront Flue<strong>ALF</strong>1M087A948SAMed-High 1620 1572 1511 1443 1376 1311 1224Med-Low 1358 1339 1309 1264 1216 1167 1098Low 1103 1106 1080 1056 1023 981 858High 1669 1599 1541 1475 1409 1329 1231LowboyRear FlueALR1M087A936SAMed-High 1410 1345 1299 1246 1184 1127 1171Med-Low 1196 1184 1149 1111 1066 1023 938Low 1007 1004 985 963 915 845 749High 1844 1771 1694 1612 1538 1451 1355LowboyRear FlueALR1M087A948SAMed-High 1622 1545 1484 1419 1356 1274 1172Med-Low 1366 1330 1303 1247 1187 1124 1046Low 1110 1107 1091 1068 1031 973 887High 1616 1550 1482 1406 1347 1231 1144Downflow/HorizontalADF1M087A936SAMed-High 1447 1397 1343 1284 1209 1127 1043Med-Low 1320 1274 1228 1176 1111 1043 950Low 1166 1139 1107 1064 1017 955 871High 1901 1837 1790 1714 1648 1584 1496Downflow/HorizontalADF1M087A948SAMed-High 1615 1572 1521 1468 1412 1355 1308Med-Low 1355 1342 1311 1273 1230 1183 1133Low 1116 1105 1084 1058 1038 1001 955Pub. No. 12-1205-039


PerformanceData*LR/F1M087A9V3SAA OIL FURNACE COOLING AND HEATING AIRFLOW AND POWER VS. EXTERNAL STATIC PRESSURE WITH FILTERCOOLINGOUTDOORUNIT SIZE(TONS)3.53**2.52AIRFLOWSETTINGLow(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal**(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)DIP SWITCH SETTINGEXTERNAL STATIC PRESSURESW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9OFFOFFOFFONONONOFFOFFOFFOFFOFFOFFOFFOFFONONOFFOFFONOFFOFFONOFFOFFONOFFOFFONOFFOFFONOFFCFMCFMCFMCFMCFMCFMCFMCFM1093125412599401057121778890411201296130091910601211775880112012961306900104911967618681113128412988811037117971484010911244125086210151151674818WATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTS183262271154213300104145267382375207291387152194340467472254352461197240413552557310409525239290471608609371468582284348CFM 1007 1001 987 978OFF ON ON OFF962WATTS 181 248 302 357 417ONONONONONONOFFOFFONONOFFOFFCFMCFMCFM6345418176076828055858087925429297484931030710WATTSWATTSWATTS678511399127162142173206181218249218260300HEATINGAIRFLOWLOW(920 CFM)HIGH(1500 CFM)SETTINGMEDIUM LOW(1145 CFM)MEDIUM HIGH**(1290 CFM)DIP SWITCH SETTINGEXTERNAL STATIC PRESSURESW 7 SW 8 0.1 0.3 0.5 0.7 0.9ONOFFONOFFONONOFFOFFCFMCFMCFMCFM8049851107129379199111111330792988112713327809871129132476196411221319WATTSWATTSWATTSWATTS100146192291146221272407198283355495256346428582307393498661NOTES:1. *FIRST LETTER MAY BE ""A"" OR ""T""“2. **FACTORY SETTING.3. CONTINUOUS FAN SETTING: HEATING OR COOLING AIRFLOW IS APPROXIMATELY 50% OF SELECTED COOLING VALUE.4. FOR VARIABLE SPEED: LOW SPEED AIRFLOWS ARE APPROXIMATELY 30% OF LISTED VALUES.5. LOW 350 CFM/TON IS RECOMMENDED FOR VARIABLE SPEED APPLICATION FOR COMFORT & HUMID CLIMATE SETTING:NORMAL IS 400 CFM/TON: HIGH 450 CFM/TON IS FOR DRY CLIMATE SETTING.10 Pub. No. 12-1205-03


PerformanceData*LR/F1M087A9V5SAA OIL FURNACE COOLING AND HEATING AIRFLOW AND POWER VS. EXTERNAL STATIC PRESSURE WITH FILTERCOOLINGOUTDOORUNIT SIZE(TONS)5**43.52.5AIRFLOWSETTINGLow(350 CFM/TON)Normal **(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)DIP SWITCH SETTINGEXTERNAL STATIC PRESSURESW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9OFFOFFOFFONONONOFFOFFOFFONONONOFFOFFOFFOFFOFFOFFONONONONONONOFFOFFONOFFOFFONOFFOFFONOFFOFFONONOFFOFFONOFFOFFONOFFOFFONOFFOFFCFMCFMCFMCFMCFMCFMCFMCFMCFMCFMCFMCFM153917561948119813961572105612001363774863962154817591958121614341577105312161407754875971153317661927122314251570104712371405741861969152717401852122314011574104812311388728859951152517221780122114061575104612261381705826935WATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTS43863587023733946717223231795111140573790106332246458825132644913817720867497012154035657083044255521832282707611055124049363181637549462523328432086611801255565741922445575712289334383HEATINGAIRFLOWSETTINGLOW(920 CFM)MEDIUM LOW(1145 CFM)MEDIUM HIGH **(1290 CFM)HIGH(1500 CFM)DIP SWITCH SETTINGEXTERNAL STATIC PRESSURESW 7 SW 8 0.1 0.3 0.5 0.7 0.9ONOFFONOFFONONOFFOFFCFMCFMCFMCFM8049851107129379199111111330792988112713327809871129132476196411221319WATTSWATTSWATTSWATTS100146192291146221272407198283355495256346428582307393498661NOTES:1. *FIRST LETTER MAY BE ""A"" OR ""T""“2. **FACTORY SETTING.3. CONTINUOUS FAN SETTING: HEATING OR COOLING AIRFLOW IS APPROXIMATELY 50% OF SELECTED COOLING VALUE.4. FOR VARIABLE SPEED: LOW SPEED AIRFLOWS ARE APPROXIMATELY 30% OF LISTED VALUES.5. LOW 350 CFM/TON IS RECOMMENDED FOR VARIABLE SPEED APPLICATION FOR COMFORT & HUMID CLIMATE SETTING:NORMAL IS 400 CFM/TON: HIGH 450 CFM/TON IS FOR DRY CLIMATE SETTING.Pub. No. 12-1205-0311


PerformanceData*HV1M087A9V3SAA OIL FURNACE COOLING AND HEATING AIRFLOW AND POWER VS. EXTERNAL STATIC PRESSURE WITH FILTERCOOLINGOUTDOORUNIT SIZE(TONS)3.53**2.52AIRFLOWSETTINGLow(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal **(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)DIP SWITCH SETTINGEXTERNAL STATIC PRESSURESW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9OFFOFFOFFONONONOFFOFFOFFONONONOFFOFFOFFOFFOFFOFFONONONONONONOFFOFFONOFFOFFONOFFOFFONOFFOFFONONOFFOFFONOFFOFFONOFFOFFONOFFOFFCFMCFMCFMCFMCFMCFMCFMCFMCFMCFMCFMCFM1127127813019691132126480291010486697498371147129313209931145125383694210776777818681148129713231004114712708299491083669772862113812931315997113612608029411072663751841111712721287968110612417899181041642731829WATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTS229321336152225308981321856785111295398419213289369150189251107134162356469493272350441199244311146179211413536558329405502238300368184217255470597611377460562280346419220254300HEATINGAIRFLOWSETTINGLOWMEDIUM LOWMEDIUM HIGH **HIGHDIP SWITCH SETTINGEXTERNAL STATIC PRESSURESW 7 SW 8 0.1 0.3 0.5 0.7 0.9ON ONCFM 857 882 883 858 843WATTS 115 167 219 263 307OFF ONCFM 1061 1086 1092 1080 1051WATTS 196 261 321 378 430ON OFFCFM 1198 1205 1197 1193 1172WATTS 272 337 395 458 517OFF OFFCFM 1280 1295 1297 1287 1265WATTS 330 407 476 538 596NOTES:1. *FIRST LETTER MAY BE ""A"" OR ""T""“2. **FACTORY SETTING.3. CONTINUOUS FAN SETTING: HEATING OR COOLING AIRFLOW IS APPROXIMATELY 50% OF SELECTED COOLING VALUE.4. FOR VARIABLE SPEED: LOW SPEED AIRFLOWS ARE APPROXIMATELY 30% OF LISTED VALUES.5. LOW 350 CFM/TON IS RECOMMENDED FOR VARIABLE SPEED APPLICATION FOR COMFORT & HUMID CLIMATE SETTING:NORMAL IS 400 CFM/TON: HIGH 450 CFM/TON IS FOR DRY CLIMATE SETTING.12 Pub. No. 12-1205-03


PerformanceData*HV1M087A9V5SAA OIL FURNACE COOLING AND HEATING AIRFLOW AND POWER VS. EXTERNAL STATIC PRESSURE WITH FILTERCOOLINGOUTDOORUNIT SIZE(TONS)5**43.53AIRFLOWSETTINGLow(350 CFM/TON)Normal **(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)DIP SWITCH SETTINGEXTERNAL STATIC PRESSURESW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9OFFOFFOFFONONONOFFOFFOFFONONONOFFOFFOFFOFFOFFOFFONONONONONONOFFOFFONOFFOFFONOFFOFFONOFFOFFONONOFFOFFONOFFOFFONOFFOFFONOFFOFFCFMCFMCFMCFMCFMCFMCFMCFMCFMCFMCFMCFM1609184120401277149416611094127714778661081121316161835197812961501165911031304147089310961244162018201915130115041657112213051470893110612691623180718641314149216651125131714728861104127516321779181013111493165711241312146187911011266WATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTS543818114228744059519528842811518925364292511613705306892583745041722553407371020117844661578233244958622832242583611101204.0853169089040253267328738750093611811215.44604776979473606745346458573HEATINGAIRFLOWSETTINGLOWMEDIUM LOWMEDIUM HIGH **HIGHDIP SWITCH SETTINGEXTERNAL STATIC PRESSURESW 7 SW 8 0.1 0.3 0.5 0.7 0.9ONOFFONOFFONONOFFOFFCFMCFMCFMCFM864105211621377895106411851397899105912021396899105712051399879106112111401WATTSWATTSWATTSWATTS111174226353169238302445224296378520239359450604334431526688NOTES:1. *FIRST LETTER MAY BE ""A"" OR ""T""“2. **FACTORY SETTING.3. CONTINUOUS FAN SETTING: HEATING OR COOLING AIRFLOW IS APPROXIMATELY 50% OF SELECTED COOLING VALUE.4. FOR VARIABLE SPEED: LOW SPEED AIRFLOWS ARE APPROXIMATELY 30% OF LISTED VALUES.5. LOW 350 CFM/TON IS RECOMMENDED FOR VARIABLE SPEED APPLICATION FOR COMFORT & HUMID CLIMATE SETTING:NORMAL IS 400 CFM/TON: HIGH 450 CFM/TON IS FOR DRY CLIMATE SETTING.Pub. No. 12-1205-0313


PerformanceData*DF1M087A9V3SAA OIL FURNACE COOLING AND HEATING AIRFLOW AND POWER VS. EXTERNAL STATIC PRESSURE WITH FILTERCOOLINGOUTDOORUNIT SIZE(TONS)3.53**2.52AIRFLOWSETTINGLow(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal **(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)DIP SWITCH SETTINGEXTERNAL STATIC PRESSURESW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9OFFOFFOFFONONONOFFOFFOFFONONONOFFOFFOFFOFFOFFOFFONONONONONONOFFOFFONOFFOFFONOFFOFFONOFFOFFONONOFFOFFONOFFOFFONOFFOFFONOFFOFFCFMCFMCFMCFMCFMCFMCFMCFMCFMCFMCFMCFM1215137513759921173135883693810856907828531243138913891048122913618791000113570581392012351414141410651235137587210061145699818911122714171417106812261374863101411486778019011211136413641044120613408399921115649760885WATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTS23229029014118929581114156657988303378378218288353148187234107134163371492492277358452197250312155184216442571571348438548254321386198231278507600600406498607313384433235279327HEATINGAIRFLOWSETTINGLOWMEDIUM LOWMEDIUM HIGH **HIGHDIP SWITCH SETTINGEXTERNAL STATIC PRESSURESW 7 SW 8 0.1 0.3 0.5 0.7 0.9ONOFFONOFFONONOFFOFFCFMCFMCFMCFM864110312671375913114812921389919115912981414910115113011417892111712891364WATTSWATTSWATTSWATTS94175245290161253329378220324417492281404489571337462553600NOTES:1. *FIRST LETTER MAY BE ""A"" OR ""T""“2. **FACTORY SETTING.3. CONTINUOUS FAN SETTING: HEATING OR COOLING AIRFLOW IS APPROXIMATELY 50% OF SELECTED COOLING VALUE.4. FOR VARIABLE SPEED: LOW SPEED AIRFLOWS ARE APPROXIMATELY 30% OF LISTED VALUES.5. LOW 350 CFM/TON IS RECOMMENDED FOR VARIABLE SPEED APPLICATION FOR COMFORT & HUMID CLIMATE SETTING:NORMAL IS 400 CFM/TON: HIGH 450 CFM/TON IS FOR DRY CLIMATE SETTING.14 Pub. No. 12-1205-03


PerformanceData*DF1M087A9V5SAA OIL FURNACE COOLING AND HEATING AIRFLOW AND POWER VS. EXTERNAL STATIC PRESSURE WITH FILTERCOOLINGOUTDOORUNIT SIZE(TONS)5**43.53AIRFLOWSETTINGLow(350 CFM/TON)Normal **(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)Low(350 CFM/TON)Normal(400 CFM/TON)High(450 CFM/TON)DIP SWITCH SETTINGEXTERNAL STATIC PRESSURESW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9OFFOFFOFFONONONOFFOFFOFFONONONOFFOFFOFFOFFOFFOFFONONONONONONOFFOFFONOFFOFFONOFFOFFONOFFOFFONONOFFOFFONOFFOFFONOFFOFFONOFFOFFCFMCFMCFMCFMCFMCFMCFMCFMCFMCFMCFMCFM1665188421471274149017151132129114869721110125416651895208712891516171511681302151810051142126816841905202513341533171511861332154210211148129016651895196013481541172411861372156510151154131816751863188013481549171511861372156599911541318WATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTSWATTS522751117027137757519226338811918023862188411903344956712663575032012603187471040122042960076935044960926532940583011201230545672879424547711331404528939123012506377961020495646809405488607HEATINGAIRFLOWSETTINGLOWMEDIUM LOWMEDIUM HIGH **HIGHDIP SWITCH SETTINGEXTERNAL STATIC PRESSURESW 7 SW 8 0.1 0.3 0.5 0.7 0.9ONOFFONOFFONONOFFOFFCFMCFMCFMCFM871105111781389876108112131421894110412471442890110412471473871108712601483WATTSWATTSWATTSWATTS104160219311155229285415221306389519282380466627336445550715NOTES:1. *FIRST LETTER MAY BE ""A"" OR ""T""“2. **FACTORY SETTING.3. CONTINUOUS FAN SETTING: HEATING OR COOLING AIRFLOW IS APPROXIMATELY 50% OF SELECTED COOLING VALUE.4. FOR VARIABLE SPEED: LOW SPEED AIRFLOWS ARE APPROXIMATELY 30% OF LISTED VALUES.5. LOW 350 CFM/TON IS RECOMMENDED FOR VARIABLE SPEED APPLICATION FOR COMFORT & HUMID CLIMATE SETTING:NORMAL IS 400 CFM/TON: HIGH 450 CFM/TON IS FOR DRY CLIMATE SETTING.Pub. No. 12-1205-0315


PerformanceDataModelHeatingCapacityCFM vs. Temperature Rise800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 200070,000 72 65 59 54 50 46 43HighboyAHV1M087A936SA87,000 90 81 73 67 62 58 5498,000 101 91 82 76 70 65 60114,000 117 106 96 88 81 75 7070,000 65 59 54 50 46 43 41 38 36 34 32HighboyAHV1M087A948SA87,000 81 73 67 62 58 54 50 47 45 42 4098,000 91 82 76 70 65 60 57 53 50 48 45114,000 106 96 88 81 75 70 66 62 59 56 5370,000 72 65 59 54 50 46 43 41LowboyFront Flue<strong>ALF</strong>1M087A936SA87,000 90 81 73 67 62 58 54 5098,000 101 91 82 76 70 65 60 57114,000 117 106 96 88 81 75 70 6670,000 72 65 59 54 50 46 43 41 38 36 34LowboyFront Flue<strong>ALF</strong>1M087A948SA87,000 90 81 73 67 62 58 54 50 47 45 4298,000 101 91 82 76 70 65 60 57 53 50 48114,000 117 106 96 88 81 75 70 66 62 59 5670,000 81 72 65 59 54 50 46 43 41 38LowboyRear FlueALR1M087A936SA87,000 101 90 81 73 67 62 58 54 50 4798,000 113 101 91 82 76 70 65 60 57 53114,000Notallowed117 106 96 88 81 75 70 66 6270,000 72 65 59 54 50 46 43 41 38 36LowboyRear FlueALR1M087A936SA87,000 90 81 73 67 62 58 54 50 47 4598,000 101 91 82 76 70 65 60 57 53 50114,000 117 106 96 88 81 75 70 66 62 5970,000 72 65 59 54 50 46 43 41Downflow/HorizontalADF1M087A936SA87,000 90 81 73 67 62 58 54 5098,000 101 91 82 76 70 65 60 57114,000 117 106 96 88 81 75 70 6670,000 65 59 54 50 46 43 41 38 36 34Downflow/HorizontalADF1M087A948SA87,000 81 73 67 62 58 54 50 47 45 4298,000 91 82 76 70 65 60 57 53 50 48114,000 106 96 88 81 75 70 66 62 59 56The unshaded area is the recommended operating range for HEATING comfort16 Pub. No. 12-1205-03


ElectricalDataELECTRICAL DIAGRAMS FOR PSC 4 SPEED BLOWER DOWNFLOW / HORIZONTAL FURNACESPub. No. 12-1205-0317


ElectricalDataELECTRICAL DIAGRAMS FOR PSC 4 SPEED BLOWER HIGHBOY & LOWBOY FURNACES18 Pub. No. 12-1205-03


ElectricalDataPub. No. 12-1205-0319


ElectricalData20 Pub. No. 12-1205-03


FieldWiringLOW VOLTAGE HOOK UP DIAGRAMS FOR OIL FURNACE & SINGLE STAGE COOLING PSC 4 SPEED MOTORSTHERMOSTATFURNACEFAN CENTERAIRCONDITIONERTHERMOSTATFURNACEFAN CENTERAIRCONDITIONERRCOIL BURNER PRIMARYB/CR1OIL BURNER PRIMARYB/CR1Blower Motor Terminal Blocks and WiringPub. No. 12-1205-0321


FieldWiringVARIABLE SPEED LOW VOLTAGE HOOK UP DIAGRAMS FOR OIL FURNACE AND SINGLE STAGE COOLINGVARIABLE SPEED V3, V5 LOW VOLTAGE WIRINGCONNECTIONS LOCATIONSRoute electrical power circuit through outside<strong>furnace</strong> wall and into junction box and make highvoltage connections inside box according to theNEC and local codes.Low VoltageTerminal BoardMAKE LOW VOLTAGECONNECTIONS HEREVARIABLE SPEED OIL FURNACE SINGLE STAGE COOLINGTHERMOSTATRONE STAGE VSOIL FURNACEY1/YLOW3RSINGLE STAGEAIR CONDITIONEROil BurnerPrimary ControlY/Y1W2W1Y/Y2R1YGGODO NOT MAKE ANYCONNECTIONS HEREBW1R1B CBKBOIL BURNER PRIMARYR1"R" to "O" and "R" to "BK" are Factory Installed Jumpers22 Pub. No. 12-1205-03


FieldWiringVARIABLE SPEED LOW VOLTAGE HOOK UP DIAGRAMS FOR OIL FURNACE AND TWO STAGE / STEP COOLINGVARIABLE SPEED OIL FURNACE TWO STAGE COOLINGWITH 24V RELAYTHERMOSTATONE STAGE VSOIL FURNACETWO STAGEAIR CONDITIONERVARIABLE SPEED OIL FURNACE TWO STEP COOLINGWITH 24V RELAYONE STAGE VS TWO STEPTHERMOSTATOIL FURNACE AIR CONDITIONERY2RY/Y1GY/Y2W3RW2W1Y1/YLOGY2RY1Y2RY/Y1GBKW3RW2W1Y/Y2GNote AY2Y1BW1R1OB CBKBBW1R1OB CY1/YLOOIL BURNER PRIMARYBOIL BURNER PRIMARYR1R1"R" to "O" and "R" to "BK" are Factory Installed JumpersNote A - Cut/remove the factory installed "R" to "BK" jumper at the indoor unit."R" to "O" and "R" to "BK" are Factory Installed JumpersPub. No. 12-1205-0323


Dimensions1.18AHV1MO87A936, 48,V3,V5SAA OUTLINE DRAWING(ALL DIMENSIONS ARE IN INCHES)MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALSFurnace casing sides and rear 3"Front <strong>furnace</strong> casing to closet door1 8"Furnace flue pipe / vent connector 9"31.0320.022.130.104.4520.030.076.5025.0047.1324.0434.2516.1314.1626.003.75Highboy Vertical1.000.886.50LC58.004.5910.061.0019.004.54Furnace casing top 3"Supply air plenum (any side) 3"Supply air ducts within 6 feet of the <strong>furnace</strong>. 3"* NOTE: Filter FrameShipped unassembled& packed in blowercompartment6.0024 Pub. No. 12-1205-03


DimensionsAIRFLOW61.2511.1222.2516.1316.13ADF1MO87A936, 48V3,V5SAA OUTLINE DRAWING(ALL DIMENSIONS ARE IN INCHES)MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALSFurnace casing sides and rear 3"Front <strong>furnace</strong> casing to closet door1 8"Furnace flue pipe / vent connector 9"Furnace casing top 3"Supply air plenum (any side) 3"Supply air ducts within 6 feet of the <strong>furnace</strong>. 3"Notes:1 The Horizontal / Downflow model requires 22" from the front casing of the <strong>furnace</strong> to thecloset door.2 Adequate clearance from the supply end surface of the <strong>furnace</strong> casing to combustiblematerials are provided by the design of the accessory mounting base when used with theHorizontal / Downflow <strong>furnace</strong> model applied in the Downflow configuration.0.750.7529.82Downflow / Horizontal - Front Flue16.1316.1322.253.23Pub. No. 12-1205-0325


Dimensions<strong>ALF</strong>1MO87A936, 48V3,V5SAA OUTLINE DRAWING(ALL DIMENSIONS ARE IN INCHES)MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALSFurnace casing sides and rear 3"Front <strong>furnace</strong> casing to closet door1 8"Furnace flue pipe / vent connector 9"Furnace casing top 3"Supply air plenum (any side) 3"6.5047.0020.03 12.532.382.0010.064.506.000.63Lowboy - Front Flue4.540.7222.0620.0317.0040.7510.133.75Supply air ducts within 6 feet of the <strong>furnace</strong>. 3"LC10.881.001.003.1326 Pub. No. 12-1205-03


DimensionsALR1MO87A936, 48V3,V5SAA OUTLINE DRAWING(ALL DIMENSIONS ARE IN INCHES)MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALSFurnace casing sides and rear 3"Front <strong>furnace</strong> casing to closet door1 8"Furnace flue pipe / vent connector 9"Furnace casing top 3"Supply air plenum (any side) 3"Supply air ducts within 6 feet of the <strong>furnace</strong>. 3"47.0020.03 12.530.7222.062.382.0010.0620.032.054.5040.756.0010.130.63Lowboy Rear Flue17.003.75Notes:1 Lowboy Rear Flue model requires 3" from the <strong>furnace</strong> front casing to the closet door.0.881.003.131.0029.845Pub. No. 12-1205-0327


American Standard Inc6200 Troup HighwayTyler, TX 75707An American-Standard CompanySince American Standard Inc has a policy of continuous product improvement, it reserves the right to changedesign and <strong>spec</strong>ifications without notice.