TotalPac®X Firecycle III Deluge - FIREFLEX SYSTEMS
TotalPac®X Firecycle III Deluge - FIREFLEX SYSTEMS
TotalPac®X Firecycle III Deluge - FIREFLEX SYSTEMS
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
TOTALPAC ® XDatasheet<strong>Firecycle</strong> ® <strong>III</strong> <strong>Deluge</strong> systemWiring diagramWaterflowAlarm switchTBA1234DFLTBBheater(optional)Light(optional)Main valveSup'v switch5678DFLFactory wiredN.C. solenoid valve(See table below for details)910111213DFLNOTES:- ALL DEVICES ARE SHOWN IN THEIRNORMAL SUPERVISORY STATE.- DRY CONTACTS RATINGS:PRESS. SWITCHES: 2.0A. 30VDC / 10A. 125/250 VACSUPV. SWITCHES: 0.5A. 125 VDC / .025A. 250 VAC / 10A 125/250VACUSE ONLY WITH POWER LIMITED CIRCUITSFactory wiredN.O. solenoid valve(See table below for details)Low temperatureSup'v switch(optional)Shut-off valveSup'v switch(optional)1415161718192021222324DFL DFL DFL- USE END-OF-LINE DEVICES COMPATIBLE WITH THERELEASE CONTROL PANEL USED (NOT INCLUDED).SOLENOID VALVE ELECTRICAL RATINGSViking P/N Description Voltage Watts DC AmpsPressureRating1159111596N.C.N.O.24 Vdc24 Vcc10 DC10 DC416mA416mA300 psi(2068 kPa)300 psi(2068 kPa)Notes:1. Solenoid Valve is UL Listed as Fire Protection Special System Water Control Release Service(UL 429A Product category VLTR).2. Voltage Drop: For proper operation, make sure that voltage at the solenoid valve is at least85% of nameplate rating.FM-076Z-0-34A7 of 10 FM-076D-0-27C