TAR-225C Compressed Air Foam Total Flooding Nozzles
TAR-225C Compressed Air Foam Total Flooding Nozzles
TAR-225C Compressed Air Foam Total Flooding Nozzles
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Table 1 - Permitted nozzle spacingfor Hydrocarbon Liquids:Dimension " H " Dimension " L "6'-7½" 2.0 m. 16'-0" 4.88 m.7'-8¾" 2.36 m. 15'-6" 4.72 m.8'-8" 2.64 m. 15'-0" 4.57 m.9'-5½" 2.88 m. 14'-6" 4.42 m.10'-2" 3.1 m. 14'-0" 4.27 m.10'-10" 3.3 m. 13'-6" 4.11 m.11'-5½" 3.49 m. 13'-0" 3.96 m.12'-0" 3.66 m. 12-'6" 3.81 m.12'-3" 3.73 m. 12'-3" 3.73 m.This table may be interpolated using the formula:H = √ 300 – L 2Nozzle spacing:hlTable 2 - Permitted nozzle spacingfor Polar Solvents:Dimension " H " Dimension " L "6'-0" 1.83 m. 12'-9¾" 3.91 m.7'-0" 2.13 m. 12'-3½" 3.75 m.8'-0" 2.44 m. 11'-8" 3.56 m.9'-0" 2.74 m. 10'-11" 3.33 m.10'-0" 3.05 m. 10'-0" 3.05 m.This table may be interpolated using the formula:H = √ 200 – L 2Typical nozzle discharge:1. ApprovalsF.M.: 3019601FM-090K-0-4CSystems Inc.1935, Lionel-Bertrand Blvd.Boisbriand, QC, Canada J7H 1N8T: (450) 437-3473 • Toll Free: (866) 347-3353F: (450) 437-1930 • Web Site : http://www.fireflex.comE-Mail : info@fireflex.com