Table 1 - Permitted nozzle spacingfor Hydrocarbon Liquids:Dimension " H " Dimension " L "6'-7½" 2.0 m. 16'-0" 4.88 m.7'-8¾" 2.36 m. 15'-6" 4.72 m.8'-8" 2.64 m. 15'-0" 4.57 m.9'-5½" 2.88 m. 14'-6" 4.42 m.10'-2" 3.1 m. 14'-0" 4.27 m.10'-10" 3.3 m. 13'-6" 4.11 m.11'-5½" 3.49 m. 13'-0" 3.96 m.12'-0" 3.66 m. 12-'6" 3.81 m.12'-3" 3.73 m. 12'-3" 3.73 m.This table may be interpolated using the formula:H = √ 300 – L 2Nozzle spacing:hlTable 2 - Permitted nozzle spacingfor Polar Solvents:Dimension " H " Dimension " L "6'-0" 1.83 m. 12'-9¾" 3.91 m.7'-0" 2.13 m. 12'-3½" 3.75 m.8'-0" 2.44 m. 11'-8" 3.56 m.9'-0" 2.74 m. 10'-11" 3.33 m.10'-0" 3.05 m. 10'-0" 3.05 m.This table may be interpolated using the formula:H = √ 200 – L 2Typical nozzle discharge:1. ApprovalsF.M.: 3019601FM-090K-0-4CSystems Inc.1935, Lionel-Bertrand Blvd.Boisbriand, QC, Canada J7H 1N8T: (450) 437-3473 • Toll Free: (866) 347-3353F: (450) 437-1930 • Web Site : http://www.fireflex.comE-Mail : info@fireflex.com