BURNER CHARTSOIL BURNERSBOILER NOZZLE PUMP SETTINGSBURNERMODEL MFR/TYPE PRESSURE AIR BAND SHUTTER HEATBECKETT DELAVAN<strong>CT</strong>-6 100 PSI 0 7.00 F16AFG 2.00 80° BBECKETT DELAVAN<strong>CT</strong>-10 100 PSI 0 7.00 F300SF 3.00 80° BBECKETT DELAVAN<strong>CT</strong>-15 100 PSI 0 7.00 F300SF 4.50 80° BBECKETT HAGO<strong>CT</strong>-20 150 PSI 0 7 3CF-800 5.00 60° PBECKETT HAGO<strong>CT</strong>-25 275 PSI 5 - 3CF-1400 4.50 60° PBECKETT DELAVAN<strong>CT</strong>-35 150/300 PSI 3/5 7.00 F16CF-2300 6.00 45° PBECKETT DELAVAN<strong>CT</strong>-50 140/275 PSI 3/5 - 3CF-2300 9.00 80° BNOTES:Air in the oil lines is the main cause of burner malfunction. Prevent air from entering the oillines by carefully installing the proper fittings.Always use flare fittings for oil line connections. Never use compression fittings for oil connections.Teflon® type tape should never be used on any oil line connections. the use of Teflon® typetape will void most burner warranties.FM-148 COLUMBIA BOILER COMPANY, REV 6-06- 30 -