6.7.2 Behavior in the event of an error (with standard setting)<br />

The behavior of the servo amplifier always depends on the current setting of a number of<br />

different parameters (e.g., ACTFAULT, VBUSMIN, VELO, STOPMODE, etc.; see online<br />

help). The diagram shows the startup procedure and the procedure that the internal control<br />

system follows in the event of one or more electrical supply phases failing, assuming<br />

that the standard parameter settings apply.<br />

(F16/F19 = error messages Mains BTB /input phase, F05 = error message Undervoltage)<br />

Even if there is no intervention from an external control system (in the example, the<br />

ENABLE signal remains active), the motor is immediately braked using the emergency<br />

stop ramp if an input phase error is detected and assuming that no changes have been<br />

made to the factory setting (ACTFAULT=1).<br />

32 SERVOSTAR <strong>300</strong> Instructions Manual