4.1.1.1. Study 1 / diagram 2The supply end earth protection device can be implemented using GFP devices ofthe Source <strong>Ground</strong> Return type of which the measuring CTs are installed on this link(see diagram 26b).DB117288Diagram 26b - "Source <strong>Ground</strong> Return" type systemIn normal N operation:b a 0 is verified because it deals with a PEb a 1 a 2 are verified as well (currents in the neutral conductor cannot flow in the PEand the earth circuits)b b 1 is verifiedb b 2 is not verified because it deals with a PE common to 2 parts of the installationb b 3 can be verified without any problems.Implemented GFP devices ensure installation safety because maximum leakagecurrent for both installations is always limited to 1200 A.But supply is interrupted because an insulation fault leads to deenergisation of theentire installation.For example, a fault on U2 leads to the deenergisation of U1 and U2.In R1 or R2 replacement operation:All operation criteria are verified.To completely resolve the problem linked to b 2 criterion, one can:b implement a CT coupling system (Study 2)b upgrade the installation system (Study 3).25