Effective use of air distribution and capacity<strong>GEA</strong> <strong>MPower</strong> - <strong>Geko</strong>Fan Coil Units | Data & FactsAir Treatment


Table of Contents<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitSizes .......................................................................................................... 1.2Fan Coil Unit Components ......................................................................... 2Unit Selection ............................................................................................... 3Unit Description ........................................................................................... 4Recirculating Air Unit Cooling and Heating .............................................. 6Accessories/Valves .............................................................................................. 7Recirculating Air Unit Cooling and Heating .............................................. 8Accessories/Valves .............................................................................................. 9Recirculating Air Unit Heating .................................................................. 10Accessories/Valves ............................................................................................ 11Recirculating Air Unit Heating .................................................................. 12Accessories/Valves ............................................................................................ 13Pressure Drop in Heat Exchanger, Warm and Chilled Water ................ 14Power and Current Consumption ............................................................. 15Capacity Overview for Different Operating Points Size 1....................... 16Overview of Acoustic Data for Different Operating Points, Size 1 ...................... 17Capacity Overview for Different Operating Points Size 2....................... 18Overview of Acoustic Data for Different Operating Points, Size 2 ...................... 19Capacity Overview for Different Operating Points Size 3....................... 20Overview of Acoustic Data for Different Operating Points, Size 3 ...................... 21Capacity Overview for Different Operating Points Size 4 ...................... 22Overview of Acoustic Data for Different Operating Points, Size 4 ...................... 23Samples for Capacity Definition .............................................................. 24Installation Samples .................................................................................. 28Dimensions of Basic Units ....................................................................... 29Dimensions of Accessories ...................................................................... 31Overview of ValvesSelection Tables.................................................................................................. 33Valve Actuators .................................................................................................. 34Valve Bodies ...................................................................................................... 35Shut-off Valves ................................................................................................... 36Ball Traps ........................................................................................................... 37Control via Thermostat / Speed Switches / Control by Others ............. 38Control System <strong>GEA</strong> MATRIX .................................................................. 40Product Type Code .................................................................................... 51Copyright noteDisclosing, copying, distributing or taking any action in reliance on the contents of thisdocument is strictly prohibited without express prior consent. Violations entail liabilityfor any damages or other liability arising. All rights in relation to patents, utility patentsor design patents are reserved.1.1 2 PR-2009-0015-GB • Subject to modifications • Status 10/2009


Sizes<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitSize Width Air volume flow Sound power level 1)1•Heating capacity Q H•Cooling capacity Q K[mm] [m 3 /h] [dB(A)] [kW]2.8-11,2975 515-1215 29-483.0-6,12341275 685-1555 32-531575 810-2020 27-471775 1000-2460 30-514.1-15,54.4-8,75.2-19,54.0-10,56.2-23,46.1-12,71) Sound level measured at unit casing, modular unit, capacity stage 1, filter class G2, without external pressure, without accessories. For otheracoustic data refer to „Sample for capacity definition“, page 24 to page 27.2)Capacity data apply for input parameters: WWP 70/50°C, t L1 = +20 °C; CWP 6/12 °C, t L1 = 27 °C, 46 % r.h. With other input parameters thefollowing correction factors for approximate estimation of performance data should be applied.Correction factors 3)For calculating performance dataaccording EUROVENT classification -the following correction factors can beused:Cooling (2-pipe system): 1,01Cooling (4-pipe system): 0,92Heating (2-pipe system): 0,70Heating (4-pipe system): 1,22Sound power 4) :+3 dBCorrection factors f K for cooling Correction factors f H for heating capacity• •capacity Q KQ H (recirculating air t L1 = 20 °C)ChilledwatertemperatureAir intake: t L1 [°C], ϕ 1 [% r.h.]Warmwater temperature2-pipe system airintake: t L1 [°C]4-pipe systemAir air intake: t L1[°C][°C] 32/40 30/40 27/46 26/50 24/50 [°C] +10 +15 +20 +10 +15 +206/12 1.40 1.19 1.00 0.97 0.76 90/70 1.84 1.71 1.57 1.86 1.73 1.597/13 1.39 1.17 0.98 0.96 0.75 80/60 1.56 1.43 1.29 1.57 1.43 1.308/12 1.37 1.15 0.97 0.94 0.73 70/55 1.37 1.24 1.10 1.38 1.24 1.118/14 1.20 1.00 0.81 0.78 0.57 70/50 1.28 1.14 1.00 1.28 1.14 1.0010/15 1.08 0.88 0.71 0.67 0.49 60/50 1.19 1.05 0.91 1.19 1.06 0.9212/16 0.96 0.77 0.60 0.56 0.44 60/40 0.99 0.85 0.70 0.98 0.84 0.7012/18 0.82 0.66 0.50 0.44 – 50/40 0.90 0.77 0.63 0.91 0.77 0.6314/18 0.77 0.65 0.49 0.44 0.34 40/30 0.62 0.48 0.34 0.62 0.48 0.333) All indicated correction factors are arithmetically calculated for different unit configurations and are to be used for only approximate estimationof performance data with other parameters. Exact data and other parameters can be obtained from our staff.4) Maximum figure based on EUROVENT 0 tolerance standard1.21PR-2009-0015-GB • Subject to modifications • Status 10/2009


Fan Coil Unit Components<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitFig. 1:Unit components (depending on unit model)Pos. 1: Basic casingPos. 2: Fixing bracketPos. 3: Heat exchangerPos. 4: FanPos. 5: Condensate trayPos. 6: Condensate pumpPos. 7: Service panelPos. 8: Filter coverPos. 9: Filter elementPos. 10: Electric switch boxPos. 11: Contact protection<strong>GEA</strong> participates in the EUROVENT certification programme.The certified products are accordingly listed by the EUROVENT.2 PR-2009-0015-GB • Subject to modifications • Status 10/2009


Druckverluste im Wärmetauscher4 Rohrreihen Kühlen, 2-Leiter-System251322015109,08,07,06,05,04,54,0303,53,02,52,01,51,00,90,80,70,60,550607080901 01502 02503 03504 04505 06 7 0Wasservolumenstrom V W [l/h]8 09 01 0Abb. 25.3<strong>GEA</strong> Top-<strong>Geko</strong> • ˜nderungen vorbehalten • Stand 08/00 (D) 2515 02 0<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitUnit SelectionUnit Description 4RecirculatingairCooling andHeating 4-Pipe Chilled and Warm Water 6Cooling orHeating 2-Pipe Chilled or Warm Water 8Heating 2-Pipe Warm Water 10Cooling 2-Pipe Chilled Warm Water 12DruckverlustDp [kPa]6 5 4 7Technical Data, Dimensions and Specification ofAccessories 14Valves 33<strong>GEA</strong> MATRIX Control System/Thermostat Switches 38PR-2009-0015-GB • Subject to modifications • Status 10/2009 3


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitUnit DescriptionHeat exchangerfor warm/chilled water(2-pipe system)Heat exchangerfor warm/chilled water(4-pipe system)Copper pipes with drawnaluminium fins, supplied with ½"connection, internal thread, airvent and drain screwsmax. inlet temperature 90 °Cmax. operating pressure 16 barFig. 7Centrifugal fan 230 V~ 50/60 HzCentrifugal fan with low noisemaintenance-free sleevebearings, high pressurestability, protection type IP00,insulation class BType and fan number dependon unit size and selectionFig. 8Condensate pump (optional) Filter As an option, formingcondensate can be drained usinga condensate pump. Highoperational safety throughcontact-free sensors.Regenerative filter hose onclip-on frame, filter quality G2(EN 779) or G3 (EN 779)Fig. 9Fixing and connecting bracketFixing and connecting bracketprovides different possibilitiesfor ceiling mounting andconnecting the unit and itsadd-on modules.Fig. 10PR-2009-0015-GB • Subject to modifications • Status 10/2009 5


Recirculating Air Unit Heating and Cooling4-Pipe Chilled and Warm WaterSizes 1 to 4CWP 6/12 °Ct L1 = +27 °Cϕ 1 = 46 % r.h.WWP 70/50 °Ct L1 = +20 °C<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitDesignModular (G)Compact (M)Speed stagesAir flow rate**Cooling capacityCapacity stage 1 Capacity stage 2Pressure dropHeating capacityPressure dropCooling capacityPressure dropHeating capacityPressure dropSound power air intake**Sound power airdischarge**•Q K Δp K•Q H Δp H•Q K Δp K•Q H Δp H[m 3 /h] kW kPa kW kPa kW kPa kW kPa dB(A) dB(A) dB(A)1 515 3.1 17.9 2.8 2.0 3.0 7.1 3.7 4.3 40 41 292 685 3.7 25.6 3.3 2.6 3.6 10.0 4.3 5.7 44 46 34Terminal box (select sheet steel electric3 915 4.4 34.9 3.8 3.4 4.3 13.9 5.1 7.5 52 54 41 1switch box with <strong>GEA</strong> MATRIX)4 1080 4.8 40.9 4.0 3.8 4.8 16.6 5.5 8.7 56 58 455 1215 5.0* 41.9 4.3 4.2 5.1 18.7 5.8 9.7 58 62 481 685 4.4 43.9 4.1 5.4 4.4 18.3 5.2 10.8 42 45 322 930 5.2* 53.7 4.8 7.1 5.4 26.5 6.3 15.1 50 53 403 1115 5.6* 53.7 5.3 8.5 6.0 32.5 6.9 17.8 54 58 44 24 1295 6.0* 53.6 5.7 9.6 6.6 38.6 7.5 20.8 58 62 485 1555 6.4* 53.6 6.2 11.2 7.3 46.9 8.1* 23.2 63 67 53 Speed combination1 815 5.3 26.3 5.2 10.3 4.9 4.6 6.2 4.3 38 38 27A 1-2-32 1150 6.7 40.3 6.3 14.5 6.3 7.2 7.7 6.4 44 45 33 B 2-3-43 1380 7.4* 47.5 6.9 17.2 7.1 9.0 8.5 7.8 48 49 37 3C 3-4-54 1670 8.0* 47.5 7.7 20.6 8.0 11.0 9.4 9.3 52 54 42 E 1-3-55 2020 8.6* 47.4 8.2* 22.2 8.9 13.6 10.4 11.2 57 60 47 H 1-2-3-4-51 1000 6.4 40.1 6.2 15.6 6.1 7.3 7.5 6.5 40 43 302 1380 7.7* 51.5 7.4 21.2 7.6 10.8 9.0 9.2 47 50 373 1730 8.5* 51.4 8.2* 24.5 8.7 14.1 10.3 11.7 52 55 424 2065 9.1* 51.3 8.6* 24.5 9.7 17.0 11.2 13.7 57 60 475 2460 9.7* 51.3 9.2* 24.6 10.7 20.4 12.2 16.3 62 64 511 515 3.1 17.9 2.8 2.0 3.0 7.1 3.7 4.3 40 41 292 680 3.7 25.3 3.2 2.6 3.6 10.0 4.3 5.7 44 46 343 905 4.4 34.5 3.7 3.3 4.3 14.0 5.0 7.4 52 54 414 1065 4.8 40.4 4.0 3.8 4.7 16.3 5.5 8.6 56 58 455 1190 5.0* 41.9 4.2 4.2 5.0 18.3 5.8 9.5 58 62 481 685 4.4 43.9 4.1 5.4 4.4 18.3 5.2 10.8 42 45 32Sound power casing**Size41Sheet steel electric switch box withterminal strip or for integrated control2 925 5.2* 53.7 4.8 7.1 5.4 26.4 6.3 15.0 50 53 40 Speed combination3 1105 5.6* 53.7 5.3 8.4 6.0 32.7 6.9 17.7 54 58 44 2K 1-2-34 1275 5.9* 53.6 5.6 9.4 6.5 37.7 7.4 20.4 58 62 48 L 2-3-45 1515 6.3* 53.6 6.1 11.0 7.2 45.5 8.0* 23.2 63 67 53 M 3-4-51 805 5.2 25.9 5.2 10.2 4.9 4.5 6.2 4.3 38 38 273O 1-3-52 1135 6.6 39.6 6.2 14.3 6.2 7.0 7.6 6.3 44 45 33 R 1-2-3-4-53 1360 7.4* 47.6 6.9 17.0 7.0 8.8 8.4 7.6 48 49 374 1635 8.0* 47.5 7.6 20.2 8.0 11.0 9.4 9.3 52 54 425 1965 8.6* 47.4 8.1* 22.2 8.8 13.2 10.2 11.0 57 60 471 1000 6.4 40.1 6.2 15.6 6.1 7.2 7.5 6.5 40 43 302 1365 7.7* 51.5 7.3 20.9 7.5 10.7 9.0 9.1 47 50 373 1700 8.5* 51.4 8.2* 24.5 8.6 13.8 10.2 11.5 52 55 424 2015 9.0* 51.3 8.6* 24.5 9.6 16.8 11.1 13.4 57 60 475 2375 9.6* 51.3 9.0* 24.5 10.5 19.6 12.0 15.7 62 64 511 2Capacity stage4FilterG2 mat filter 2G3 mat filter 3Motor thermal contact5-speedmotorIntegratedTC0External TC 1Medium connection - front connectionside, facing dischargeCeilingleft 3right 4Condensate linewith drainage 0with condensate pump *** 1Data apply to basic units with filter class G2, without accessories and externalpressure. Refer to table on page 24 for other operating points.* Capacity at max. allowed medium flow rate** Air flow rates and sound data for capacity stage 1*** sheet steel electrical control box necessaryOrdercodeG M • U W W .6 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitAccessories/ValvesRecirculating Air Unit Heating and Cooling4-Pipe Chilled and Warm Water, Sizes 1 to 4AccessoriesSpare filter hosesFilter class G2 8 2 3Filter class G3 8 3 3Flexible dischargeconnectorAir intake 1 1 1Air discharge** 1 1 2Box with roundconnectorAir intake 0 4 1Air discharge**0 4 2Cover cap for round connector DN200(irrespective of size) *Air intake 7 1 1Air discharge 7 1 2Sound attenuationmoduleSuspension rail(irrespective ofsize) *Air intake 2 1 1Air discharge** 2 1 2950 mm 6 1 31550 mm 6 2 32150 mm 6 3 3Contact protection Air intake 5 1 1Sizes 1 to 4* 0, if irrespective of size** Only for basic units inmodular configurationOrder codeZ G M • AValvesMATRIX 500MATRIX 2000MATRIX 3000/4000Terminal boxActuator Operating voltage/circuit• • • • 2-point 230 V AC 2) Topen/• • • close1), 2)24 V AC Q3-point 230 V AC Ropen/• •stop/24 V AC 1) Nclose 230 V AC + 2 contacts Ccontinu-•Connection/shut-offInlet/outlet with external thread 0Inlet/outlet with solder fitting 1Inlet/outlet + ball trap with external thread 2Inlet/outlet + ball trap with solder fitting 3Inlet + ball trap/outlet + shut-off valve with externalthread4Inlet + ball trap/outlet + shut-off valve with solderfitting5HeatingcircuitCoolingcircuit2 3k vs -valuesCooling/Heating0.25 ≡ 030.40 ≡ 040.63 ≡ 061.00 ≡ 101,60 2) ≡ 162.50 ≡ 254,00 2) ≡ 40Medium connectionleft Lright R1) 24 V-transformer to be provided byothers2) k vs -values for open/close actuators(T,Q) only k vs 1,6 and 4,0 possibleous 0/2 ... 10 V = 24 V AC 1) S V G M • •Order codeCooling circuitHeating circuitPR-2009-0015-GB • Subject to modifications • Status 10/2009 7


Recirculating Air Unit Heating or Cooling2-Pipe Chilled or Warm WaterSizes 1 to 4CWP 6/12 °Ct L1 = +27 °Cϕ 1 = 46 % r.h.WWP 70/50 °Ct L1 = +20 °C<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitDesignModular (G)Compact (M)Speed stagesAir flow rate**Cooling capacityCapacity stage 1 Capacity stage 2Pressure dropHeating capacityPressure dropCooling capacityPressure dropHeating capacityPressure dropSound power air intake**Sound power airdischarge**•Q K Δp K•Q H Δp H•Q K Δp K•Q H Δp H[m 3 /h] kW kPa kW kPa kW kPa kW kPa dB(A) dB(A) dB(A)1 515 3.0 7.1 5.5 2.0 3.4 5.2 5.9 1.3 40 41 292 685 3.6 10.1 6.7 2.9 4.2 7.6 7.4 2.1 44 46 34Terminal box (select sheet steel electric3 915 4.4 14.1 8.2 4.2 5.1 11.1 9.3 3.1 52 54 41 1switch box with <strong>GEA</strong> MATRIX)4 1080 4.8 16.9 9.2 5.2 5.6 13.2 10.4 3.9 56 58 455 1215 5.2 19.2 10.0 6.1 6.1 15.2 11.2 4.5 58 62 481 685 4.4 18.3 7.6 4.7 4.9 13.2 8.2 3.2 42 45 322 930 5.4 26.7 9.6 7.2 6.1 19.9 10.4 5.0 50 53 403 1115 6.0 32.8 10.9 9.1 7.0 25.3 12.0 6.4 54 58 44 24 1295 6.6 38.9 12.0 10.9 7.7 30.2 13.5 8.0 58 62 485 1555 7.3* 46.7 13.6 13.7 8.7 37.5 15.5 10.2 63 67 53 Speed combination1 815 5.0 4.6 8.8 1.3 5.4 3.2 9.5 0.8 38 38 27A 1-2-32 1150 6.3 7.2 11.6 2.1 7.1 5.3 12.8 1.5 44 45 33 B 2-3-43 1380 7.2 9.1 13.2 2.6 8.2 6.8 14.7 1.9 48 49 37 3C 3-4-54 1670 8.0 11.2 15.1 3.4 9.4 8.8 17.1 2.5 52 54 42 E 1-3-55 2020 9.0 13.8 17.2 4.3 10.5 10.8 19.5 3.2 57 60 47 H 1-2-3-4-51 1000 6.1 7.3 10.8 1.9 6.7 5.1 11.8 1.3 40 43 302 1380 7.6 10.9 13.8 3.1 8.7 8.2 15.3 2.2 47 50 373 1730 8.8 14.3 16.2 4.1 10.1 10.9 18.1 3.0 52 55 424 2065 9.7 17.2 18.3 5.2 11.4 13.6 20.7 3.8 57 60 475 2460 10.8 20.8 20.7 6.5 12.7 16.4 23.4 4.8 62 64 511 515 3.0 7.1 5.5 2.0 3.4 5.2 5.9 1.3 40 41 292 680 3.6 10.0 6.7 2.9 4.2 7.6 7.4 2.1 44 46 343 905 4.3 13.9 8.1 4.2 5.1 10.9 9.2 3.1 52 54 414 1065 4.8 16.6 9.0 5.1 5.6 13.0 10.3 3.8 56 58 455 1190 5.1 18.7 9.8 5.9 6.0 14.8 11.1 4.4 58 62 481 685 4.4 18.3 7.6 4.7 4.9 13.2 8.2 3.2 42 45 32Sound power casing**Size41Sheet steel electric switch box withterminal strip or for integrated control2 925 5.4 26.5 9.6 7.1 6.2 20.1 10.4 4.9 50 53 40 Speed combination3 1105 6.0 32.5 10.8 9.0 6.9 25.0 12.0 6.4 54 58 44 2K 1-2-34 1275 6.6 38.2 11.9 10.7 7.6 29.5 13.3 7.8 58 62 48 L 2-3-45 1515 7.3 46.4 13.4 13.3 8.5 36.3 15.2 9.9 63 67 53 M 3-4-51 805 4.9 4.5 8.8 1.2 5.4 3.1 9.4 0.8 38 38 273O 1-3-52 1135 6.3 7.1 11.5 2.0 7.0 5.2 12.6 1.4 44 45 33 R 1-2-3-4-53 1360 7.1 8.9 13.1 2.6 8.1 6.7 14.5 1.8 48 49 374 1635 8.0 11.1 14.9 3.3 9.2 8.6 16.9 2.4 52 54 425 1965 8.9 13.4 16.8 4.1 10.3 10.5 19.1 3.1 57 60 471 1000 6.1 7.3 10.8 1.9 6.7 5.2 11.6 1.3 40 43 302 1365 7.5 10.7 13.7 3.0 8.6 8.1 15.1 2.1 47 50 373 1700 8.7 14.0 16.0 4.0 10.0 10.6 17.9 2.9 52 55 424 2015 9.7 17.1 18.0 5.0 11.3 13.2 20.4 3.7 57 60 475 2375 10.6 20.1 20.1 6.1 12.4 15.7 22.8 4.5 62 64 511 2Capacity stage4FilterG2 mat filter 2G3 mat filter 3Motor thermal contact5-speedmotorIntegratedTC0External TC 1Medium connection - front connectionside, facing dischargeCeilingleft 3right 4Condensate linewith drainage 0with condensate pump *** 1Data apply to basic units with filter class G2, without accessories and externalpressure. Refer to table on page 24 for other operating points.* Capacity at max. allowed medium flow rate** Air flow rates and sound data for capacity stage 1*** Sheet steel electrical control box necessaryOrdercodeG M . U W C .8 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitAccessories/ValvesRecirculating Air Unit Heating or Cooling2-Pipe Chilled or Warm Water, sizes 1 to 4AccessoriesSpare filter hosesFilter class G2 8 2 3Filter class G3 8 3 3Flexible dischargeconnectorAir intake 1 1 1Air discharge** 1 1 2Box with roundconnectorAir intake 0 4 1Air discharge**0 4 2Cover cap for round connector DN200(irrespective of size) *Air intake 7 1 1Air discharge 7 1 2Sound attenuationmoduleSuspension rail(irrespective ofsize) *Air intake 2 1 1Air discharge** 2 1 2950 mm 6 1 31550 mm 6 2 32150 mm 6 3 3Contact protection Air intake 5 1 1Sizes 1 to 4* 0, if irrespective of size** Only for basic units inmodular configurationOrder codeZ G M • AValvesMATRIX 500MATRIX 2000MATRIX 3000/4000Terminal boxActuator Operating voltage/circuit• • • • 2-point 230 V AC 2) Topen/• • • close 24 V AC 1), 2) Q3-pointopen/〈 • •stop/closecontinuous•230 V AC R24 V AC 1) N230 V AC + 2 contacts C0/2 ... 10 V = 24 V AC 1) SConnection/shut-offInlet/outlet with external thread 0Inlet/outlet with solder fitting 1Inlet/outlet + ball trap with external thread 2Inlet/outlet + ball trap with solder fitting 3Inlet + ball trap/outlet + shut-off valve with externalthread4Inlet + ball trap/outlet + shut-off valve with solderfitting5Cooling/heating circuit3k vs -valuesCooling/Heating0.25 ≡ 030.40 ≡ 040.63 ≡ 061.00 ≡ 101,60 2) ≡ 162,50 ≡ 254.00 2) ≡ 40Medium connectionleft Lright R1) 24 V-transformer to be provided byothers2) kvs-values for open/close actuators(T,Q) only kvs 1,6 and 4 possibleOrder codeV G M 〈 3 〈Cooling/heating circuitPR-2009-0015-GB • Subject to modifications • Status 10/2009 9


Recirculating Air Unit Heating2-Pipe Warm WaterSizes 1 to 4WWP 70/50 °Ct L1 = +20 °C<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitDesignModular (G)Compact (M)Speed stagesAir flow rate**Cooling capacityCapacity stage 1 Capacity stage 2Pressure dropHeating capacityPressure dropCooling capacityPressure dropHeating capacityPressure dropSound power air intake**Sound power airdischarge**•Q K Δp K•Q H Δp H•Q K Δp K•Q H Δp H[m 3 /h] kW kPa kW kPa kW kPa kW kPa dB(A) dB(A) dB(A)1 515 – – 5.5 2.0 – – 5.9 1.3 40 41 292 685 – – 6.7 2.9 – – 7.4 2.1 44 46 34Terminal box (select sheet steel electric3 915 – – 8.2 4.2 – – 9.3 3.1 52 54 41 1switch box with <strong>GEA</strong> MATRIX)4 1080 – – 9.2 5.2 – – 10.4 3.9 56 58 455 1215 – – 10.0 6.1 – – 11.2 4.5 58 62 481 685 – – 7.6 4.7 – – 8.2 3.2 42 45 322 930 – – 9.6 7.2 – – 10.4 5.0 50 53 403 1115 – – 10.9 9.1 – – 12.0 6.4 54 58 44 24 1295 – – 12.0 10.9 – – 13.5 8.0 58 62 485 1555 – – 13.6 13.7 – – 15.5 10.2 63 67 53 Speed combination1 815 – – 8.8 1.3 – – 9.5 0.8 38 38 27A 1-2-32 1150 – – 11.6 2.1 – – 12.8 1.5 44 45 33 B 2-3-43 1380 – – 13.2 2.6 – – 14.7 1.9 48 49 37 3C 3-4-54 1670 – – 15.1 3.4 – – 17.1 2.5 52 54 42 E 1-3-55 2020 – – 17.2 4.3 – – 19.5 3.2 57 60 47 H 1-2-3-4-51 1000 – – 10.8 1.9 – – 11.8 1.3 40 43 302 1380 – – 13.8 3.1 – – 15.3 2.2 47 50 373 1730 – – 16.2 4.1 – – 18.1 3.0 52 55 424 2065 – – 18.3 5.2 – – 20.7 3.8 57 60 475 2460 – – 20.7 6.5 – – 23.4 4.8 62 64 511 515 – – 5.5 2.0 – – 5.9 1.3 40 41 292 680 – – 6.7 2.9 – – 7.4 2.1 44 46 343 905 – – 8.1 4.2 – – 9.2 3.1 52 54 414 1065 – – 9.0 5.1 – – 10.3 3.8 56 58 455 1190 – – 9.8 5.9 – – 11.1 4.4 58 62 481 685 – – 7.6 4.7 – – 8.2 3.2 42 45 32Sound power casing**Size41Sheet steel electric switch box withterminal strip or for integrated control2 925 – – 9.6 7.1 – – 10.4 4.9 50 53 40 Speed combination3 1105 – – 10.8 9.0 – – 12.0 6.4 54 58 44 2K 1-2-34 1275 – – 11.9 10.7 – – 13.3 7.8 58 62 48 L 2-3-45 1515 – – 13.4 13.3 – – 15.2 9.9 63 67 53 M 3-4-51 805 – – 8.8 1.2 – – 9.4 0.8 38 38 273O 1-3-52 1135 – – 11.5 2.0 – – 12.6 1.4 44 45 33 R 1-2-3-4-53 1360 – – 13.1 2.6 – – 14.5 1.8 48 49 374 1635 – – 14.9 3.3 – – 16.9 2.4 52 54 425 1965 – – 16.8 4.1 – – 19.1 3.1 57 60 471 1000 – – 10.8 1.9 – – 11.6 1.3 40 43 302 1365 – – 13.7 3.0 – – 15.1 2.1 47 50 373 1700 – – 16.0 4.0 – – 17.9 2.9 52 55 424 2015 – – 18.0 5.0 – – 20.4 3.7 57 60 475 2375 – – 20.1 6.1 – – 22.8 4.5 62 64 511 2Capacity stage4FilterG2 mat filter 2G3 mat filter 3Motor thermal contact5-speedmotorIntegratedTC0External TC 1Medium connection - front connectionside, facing dischargeCeilingleft 3right 4Data apply to basic units with filter class G2, without accessories and externalpressure. Refer to table on page 24 for other operating points.* Capacity at max. allowed medium flow rate** Air flow rates and sound data for capacity stage 1OrdercodeG M . U O W . 010 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitAccessories/ValvesRecirculating Air Unit Heating2-Pipe Warm Water, Sizes 1 to 4AccessoriesSpare filter hosesFilter class G2 8 2 3Filter class G3 8 3 3Flexible dischargeconnectorAir intake 1 1 1Air discharge** 1 1 2Box with roundconnectorAir intake 0 4 1Air discharge**0 4 2Cover cap for round connector DN200(irrespective of size) *Air intake 7 1 1Air discharge 7 1 2Sound attenuationmoduleSuspension rail(irrespective ofsize) *Air intake 2 1 1Air discharge** 2 1 2950 mm 6 1 31550 mm 6 2 32150 mm 6 3 3Contact protection Air intake 5 1 1Sizes 1 to 4* 0, if irrespective of size** Only for basic units inmodular configurationOrder codeZ G M • AValvesMATRIX 500MATRIX 2000MATRIX 3000/4000Terminal boxConnection/shut-offInlet/outlet with external thread 0Inlet/outlet with solder fitting 1Inlet/outlet + ball trap with external thread 2Inlet/outlet + ball trap with solder fitting 3Inlet + ball trap/outlet + shut-off valve with externalthread4Inlet + ball trap/outlet + shut-off valve with solderfitting5Heating circuit2 3k vs -valuesCooling/Heating0.25 ≡ 030.40 ≡ 040.63 ≡ 061.00 ≡ 101,60 2) ≡ 162.50 ≡ 254,00 2) ≡ 40Medium connectionleft Lright RActuator Operating voltage/circuit• • • • 2-point 230 V AC 2) Topen/• • • close 24 V AC1), 2) Q3-point 230 V AC Ropen/〈 • •stop/24 V AC 1) Nclose 230 V AC + 2 contacts Ccontinu-•ous 0/2 ... 10 V = 24 V AC 1) S V G M • •1) 24 V-transformer to be provided byothers2) k vs -values for open/close actuators(T,Q) only k vs 1,6 and 4,0 possibleOrder codeHeating circuitPR-2009-0015-GB • Subject to modifications • Status 10/2009 11


Recirculating Air Unit Cooling2-Pipe Chilled WaterSizes 1 to 4CWP 6/12 °Ct L1 = +27 °Cϕ 1 = 46 % r.h.<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitDesignModular (G)Compact (M)Speed stagesAir flow rate**Cooling capacityCapacity stage 1 Capacity stage 2Pressure dropHeating capacityPressure dropCooling capacityPressure dropHeating capacityPressure dropSound power air intake**Sound power airdischarge**•Q K Δp K•Q H Δp H•Q K Δp K•Q H Δp H[m 3 /h] kW kPa kW kPa kW kPa kW kPa dB(A) dB(A) dB(A)1 515 3.0 7.1 – – 3.4 5.2 – – 40 41 292 685 3.6 10.1 – – 4.2 7.6 – – 44 46 34Terminal box (select sheet steel electric3 915 4.4 14.1 – – 5.1 11.1 – – 52 54 41 1switch box with <strong>GEA</strong> MATRIX)4 1080 4.8 16.9 – – 5.6 13.2 – – 56 58 455 1215 5.2 19.2 – – 6.1 15.2 – – 58 62 481 685 4.4 18.3 – – 4.9 13.2 – – 42 45 322 930 5.4 26.7 – – 6.1 19.9 – – 50 53 403 1115 6.0 32.8 – – 7.0 25.3 – – 54 58 44 24 1295 6.6 38.9 – – 7.7 30.2 – – 58 62 485 1555 7.3* 46.7 – – 8.7 37.5 – – 63 67 53 Speed combination1 815 5.0 4.6 – – 5.4 3.2 – – 38 38 27A 1-2-32 1150 6.3 7.2 – – 7.1 5.3 – – 44 45 33 B 2-3-43 1380 7.2 9.1 – – 8.2 6.8 – – 48 49 37 3C 3-4-54 1670 8.0 11.2 – – 9.4 8.8 – – 52 54 42 E 1-3-55 2020 9.0 13.8 – – 10.5 10.8 – – 57 60 47 H 1-2-3-4-51 1000 6.1 7.3 – – 6.7 5.1 – – 40 43 302 1380 7.6 10.9 – – 8.7 8.2 – – 47 50 373 1730 8.8 14.3 – – 10.1 10.9 – – 52 55 424 2065 9.7 17.2 – – 11.4 13.6 – – 57 60 475 2460 10.8 20.8 – – 12.7 16.4 – – 62 64 511 515 3.0 7.1 – – 3.4 5.2 – – 40 41 292 680 3.6 10.0 – – 4.2 7.6 – – 44 46 343 905 4.3 13.9 – – 5.1 10.9 – – 52 54 414 1065 4.8 16.6 – – 5.6 13.0 – – 56 58 455 1190 5.1 18.7 – – 6.0 14.8 – – 58 62 481 685 4.4 18.3 – – 4.9 13.2 – – 42 45 322 925 5.4 26.5 – – 6.2 20.1 – – 50 53 40 Speed combination3 1105 6.0 32.5 – – 6.9 25.0 – – 54 58 44 2K 1-2-34 1275 6.6 38.2 – – 7.6 29.5 – – 58 62 48 L 2-3-45 1515 7.3 46.4 – – 8.5 36.3 – – 63 67 53 M 3-4-51 805 4.9 4.5 – – 5.4 3.1 – – 38 38 27Sound power casing**Size413Sheet steel electric switch box with terminalstrip or for integrated controlO 1-3-52 1135 6.3 7.1 – – 7.0 5.2 – – 44 45 33 R 1-2-3-4-53 1360 7.1 8.9 – – 8.1 6.7 – – 48 49 374 1635 8.0 11.1 – – 9.2 8.6 – – 52 54 425 1965 8.9 13.4 – – 10.3 10.5 – – 57 60 471 1000 6.1 7.3 – – 6.7 5.2 – – 40 43 302 1365 7.5 10.7 – – 8.6 8.1 – – 47 50 373 1700 8.7 14.0 – – 10.0 10.6 – – 52 55 424 2015 9.7 17.1 – – 11.3 13.2 – – 57 60 475 2375 10.6 20.1 – – 12.4 15.7 – – 62 64 511 2Capacity stage4FilterG2 mat filter 2G3 mat filter 3Motor thermal contact5-speedmotorIntegratedTC0External TC 1Medium connection - front connectionside, facing dischargeCeilingleft 3right 4Condensate linewith drainage 0with condensate pump *** 1Data apply to basic units with filter class G2, without accessories and externalpressure. Refer to table on page 24 for other operating points.* Capacity at max. allowed medium flow rate** Air flow rates and sound data for capacity stage 1*** sheet steel electrical control box necessaryOrdercodeG M . U W O .12 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitAccessories/ValvesRecirculating Air Unit Cooling2-Pipe Chilled Water, Sizes 1 to 4AccessoriesSpare filter hosesFilter class G2 8 2 3Filter class G3 8 3 3Flexible dischargeconnectorAir intake 1 1 1Air discharge** 1 1 2Box with roundconnectorAir intake 0 4 1Airdisharge**0 4 2Cover cap for round connector DN200(irrespective of size) *Air intake 7 1 1Air discharge 7 1 2Sound attenuationmoduleSuspension rail(irrespective ofsize) *Air intake 2 1 1Air discharge** 2 1 2950 mm 6 1 31550 mm 6 2 32150 mm 6 3 3Contact protection Air intake 5 1 1Sizes 1 to 4* 0, if irrespective of size** Only for basic units inmodular configurationOrder codeZ G M • AValvesMATRIX 500MATRIX 2000MATRIX 3000/4000Terminal boxConnection/shut-offInlet/outlet with external thread 0Inlet/outlet with solder fitting 1Inlet/outlet + ball trap with external thread 2Inlet/outlet + ball trap with solder fitting 3Inlet + ball trap/outlet + shut-off valve with externalthread4Inlet + ball trap/outlet + shut-off valve with solderfitting5Cooling circuit2 3k vs -valuesCooling/Heating0.25 ≡ 030.40 ≡ 040.63 ≡ 061.00 ≡ 101,60 2) ≡ 162.50 ≡ 254,00 2) ≡ 40Medium connectionleft Lright RActuator Operating voltage/circuit• • • • 2-point 230 V AC 2) Topen/• • • close1), 2)24 V AC Q3-point 230 V AC Ropen/〈 • •stop/24 V AC 1) Nclose 230 V AC + 2 contacts Ccontinu-•ous 0/2 ... 10 V = 24 V AC 1) S V G M • •1) 24 V-transformer to be provided byothers2) k vs -values for open/close actuators(T,Q) only k vs 1,6 and 4,0 possibleOrder codeCooling circuitPR-2009-0015-GB • Subject to modifications • Status 10/2009 13


Pressure Drop in Heat Exchanger, Warm and Chilled Water<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitCooling in 2-pipe systemHeating in 2-pipe system252520BG/LG*2/14/120BG/LG*2/14/1151/13/1151/13/1Pressure drop [kPa]109,08,07,06,05,04,54,03,53,02/21/24/23/2Pressure drop [kPa]109,08,07,06,05,04,54,03,53,02/21/24/23/22,52,52,02,01,51,51,00,90,80,70,61,00,90,80,70,60,50,550607080100901502002503003504004505006007008009001000•Water flow rate V w [l/h]1500200050607080100901502002503003504004505006007008009001000•Water flow rate V w [l/h]15002000Cooling in 4-pipe systemHeating in 4-pipe system25252015BG/LG*2/11/14/13/12015BG/LG*4/1 1/23/12/22/13/21/14/2Pressure drop [kPa]109,08,07,06,05,04,54,03,53,02,52/21/24/23/2Pressure drop [kPa]109,08,07,06,05,04,54,03,53,02,52,02,01,51,51,00,90,80,70,61,00,90,80,70,60,50,55060708090100150200250300350400450500600700800900•Water flow rate V w [l/h]1000150020005060708090100150200250300350400450500600700800900•Water flow rate V w [l/h]100015002000* Size = Size, CS = Capacity stage14 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitPower and Current ConsumptionMaximum power and current consumptionSize Speed Air flow rate [m 3 /h]Capacity [W]MotorCurrent [A]1 515 100 0.662 685 131 0.7413 915 184 0.864 1080 197 0.915 1215 212 0.981 685 131 0.752 930 194 0.9023 1115 212 0.984 1295 233 1.075 1555 278 1.321 815 133 0.782 1150 184 0.8533 1380 221 1.024 1670 264 1.225 2020 300 1.381 1000 163 0.852 1380 225 1.0443 1730 264 1.214 2065 303 1.385 2460 358 1.64Note: the current table applies for modular units, capacity stage 1 and filter class G2. Power and current consumptiondecreases in other units variants and/or in case of mounted air side accessories and additional external static pressuredrop.PR-2009-0015-GB • Subject to modifications • Status 10/2009 15


Capacity Overview for Different Operating PointsSize 1180CWP 6/12 °Ct L1 = +27 °Cϕ L1 = 46 % r.h.WWP 70/50 °Ct L1 = +20 °C<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitStatic pressure [Pa]160140120100806040Speed 1Speed 5Speed 4Speed 3Speed 2•1: Compact basic unit (0 cap), basic unitCS2, air intake sound attenuator, contactprotection, discharge plenum (0 cap)2: Compact basic unit (1 cap), air intakeplenum (0 cap), discharge plenum(1 cap)3: Discharge sound attenuator4: Basic unit filter class G35: Air intake box (1 cap)6: Compact basic unit (2 caps), dischargeplenum (2 caps)7: Air intake box (2 cap) 2000 200 400 600 800 1000 1200 1400Air flow rate [m³/h]System2-pipe system4-pipe systemAir flowrate* Capacity at max. allowed medium flow rateCapacity stage 1 Capacity stage 2Cooling capacityPressuredropHeating capacityPressuredropCoolingcapacityPressuredropHeatingcapacityPressuredrop•Q K Δp K•Q H Δp H•Q K Δp K•Q H Δp H[m 3 /h] [kW] [kPa] [kW] [kPa] [kW] [kPa] [kW] [kPa]1200 5.1 18.9 9.9 6.0 6.1 15.3 11.3 4.51150 5.0 18.1 9.7 5.7 5.9 14.6 11.0 4.31100 4.9 17.2 9.3 5.4 5.8 13.8 10.6 4.01050 4.7 16.4 8.9 5.0 5.6 13.1 10.3 3.81000 4.6 15.5 8.7 4.8 5.4 12.3 10.0 3.6950 4.5 14.7 8.4 4.5 5.2 11.6 9.6 3.3900 4.4 14.1 8.1 4.2 5.1 11.0 9.3 3.1850 4.2 13.2 7.8 3.9 4.9 10.2 8.9 2.9800 4.0 12.2 7.5 3.6 4.7 9.4 8.5 2.7750 3.9 11.3 7.1 3.3 4.5 8.7 8.0 2.4700 3.7 10.4 6.8 3.0 4.2 7.9 7.6 2.2650 3.5 9.5 6.5 2.7 4.0 7.1 7.1 1.9600 3.3 8.6 6.1 2.5 3.8 6.5 6.7 1.7550 3.2 7.8 5.7 2.2 3.6 5.7 6.2 1.5500 3.0 6.9 5.3 1.9 3.3 5.0 5.8 1.3450 2.7 5.9 4.9 1.6 3.0 4.2 5.3 1.1400 2.5 5.0 4.4 1.3 2.7 3.5 4.8 0.91200 5.0* 41.9 4.3 4.2 5.1 18.9 5.9 9.81150 4.9* 41.9 4.2 4.0 5.0 18.1 5.7 9.41100 4.9* 41.9 4.1 3.9 4.9 17.2 5.6 9.01050 4.8 39.8 4.0 3.7 4.7 16.4 5.5 8.71000 4.7 38.5 3.9 3.7 4.6 15.5 5.3 8.3950 4.5 36.4 3.8 3.5 4.5 14.7 5.2 7.9900 4.4 34.3 3.7 3.3 4.4 14.1 5.0 7.5850 4.2 32.1 3.6 3.2 4.2 13.2 4.9 7.2800 4.1 30.0 3.5 3.0 4.0 12.2 4.8 6.7750 3.9 27.9 3.4 2.8 3.9 11.3 4.6 6.3700 3.8 25.8 3.3 2.6 3.7 10.4 4.4 5.9650 3.6 24.0 3.2 2.5 3.5 9.5 4.2 5.4600 3.4 21.7 3.1 2.3 3.3 8.6 4.0 5.0550 3.2 19.5 2.9 2.1 3.2 7.8 3.9 4.6500 3.0 17.2 2.8 1.9 3.0 6.9 3.6 4.1450 2.8 15.3 2.6 1.7 2.7 5.9 3.4 3.7400 2.6 13.0 2.4 1.5 2.5 5.0 3.2 3.216 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitOverview of Acoustic Data for Different Operating PointsSize 1Sound power level free air intake and discharge(Modular configuration, capacity size 1, filter class G2)Speed Measure point Sound power level L W [dB]12345Octave centre frequency [Hz] not rated rated63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)]Air intake 42 43 44 39 30 21 0 0 48 40Air discharge 42 45 43 39 36 26 0 0 49 41Casing 34 36 34 25 18 9 0 0 40 29Air intake 47 48 48 44 36 29 19 0 53 44Air discharge 46 49 48 45 41 34 28 0 53 46Casing 38 40 39 30 24 16 10 0 44 33Air intake 53 55 56 52 44 39 33 27 60 52Air discharge 52 55 56 52 50 43 39 31 61 54Casing 45 47 47 38 32 26 22 12 51 41Air intake 56 59 59 55 48 43 38 34 64 56Air discharge 54 59 59 56 54 48 44 36 64 58Casing 47 51 50 42 36 30 27 18 55 45Air intake 59 61 62 58 51 46 42 38 66 58Air discharge 58 61 62 59 58 51 48 42 67 61Casing 50 53 53 44 39 33 31 23 57 48Sound power level with other operating pointsAir flow rateSum level L W[dB(A)][m³/h] Air intake Air discharge Casing1200 – – – – 58 – – – – 61 – – – – 481150 – – – – 58 – – – – 61 – – – – 471100 – – – – 58 – – – – 61 – – – – 471050 – – – 56 58 – – – 58 61 – – – 45 471000 – – – 56 58 – – – 58 60 – – – 45 47950 – – – 56 57 – – – 58 60 – – – 45 46900 – – 52 56 57 – – 54 58 60 – – 41 45 46850 – – 53 56 57 – – 55 58 60 – – 42 45 46800 – – 53 56 57 – – 55 58 59 – – 42 45 46750 – – 53 56 57 – – 55 58 59 – – 42 45 45700 – – 54 56 57 – – 55 58 59 – – 42 45 45650 – 47 54 56 56 – 49 56 58 59 – 36 43 44 45600 – 50 55 56 – – 53 56 57 – – 39 43 44 –550 – 53 55 – – – 56 56 – – – 43 43 – –500 42 56 – – – 43 60 – – – 31 46 – – –450 47 – – – – 49 – – – – 37 – – – –400 53 – – – – 55 – – – – 43 – – – –Speed 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5Acoustic insulation of sound attenuator (accessories)Octave centre frequency [Hz]Sum levelapprox. Δ LW[dB]63 125 250 500 1000 2000 4000 8000 Intake 10Acoustic insulation [dB] 3 3 8 16 21 25 17 13 Air discharge 12PR-2009-0015-GB • Subject to modifications • Status 10/2009 17


Capacity Overview for Different Operating PointsSize 2CWP 6/12 °Ct L1 = +27 °Cϕ L1 = 46 % r.h.WWP 70/50 °Ct L1 = +20 °C<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitStatic pressure [Pa]Speed 5Speed 4Speed 3Speed 2Speed 11: Contact protection2: Basic unit CS23: Air intake sound attenuator4: Compact basic unit (0 caps),discharge plenum (0 caps)5: Air intake box (0 caps)6: Discharge sound attenuator7: Compact basic unit (1 cap), dischargeplenum (1 cap)8: Basic unit filter class G39: Air intake box (1 cap)10: Compact basic unit (2 caps),discharge plenum (2 caps)11: Air intake box (2 caps) • Air flow rate [m³/h]System2-pipe system4-pipe systemAir flowrate* Capacity at max. allowed medium flow rateCapacity stage 1 Capacity stage 2CoolingcapacityPressuredropHeatingcapacityPressuredropCoolingcapacityPressuredropHeatingcapacityPressuredrop•Q K Δp K•Q H Δp H•Q K Δp K•Q H Δp H[m 3 /h] [kW] [kPa] [kW] [kPa] [kW] [kPa] [kW] [kPa]1550 7.3* 46.8 13.6 13.7 8.7 38.1 15.6 10.41500 7.3 45.9 13.3 13.1 8.5 36.6 15.3 10.01440 7.1 43.8 12.9 12.5 8.3 34.8 14.9 9.51380 6.9 41.8 12.6 11.8 8.1 33.0 14.4 9.01320 6.7 39.8 12.2 11.2 7.8 31.2 13.8 8.31260 6.5 37.7 11.8 10.6 7.6 29.5 13.3 7.81200 6.3 35.7 11.4 9.9 7.3 27.7 12.8 7.21140 6.1 33.6 11.0 9.3 7.2 26.4 12.3 6.71080 6.0 32.2 10.6 8.7 6.9 24.5 11.9 6.31020 5.7 30.0 10.2 8.1 6.6 22.7 11.4 5.8960 5.5 27.8 9.8 7.5 6.3 20.9 10.8 5.2900 5.3 25.6 9.4 6.9 6.0 19.3 10.2 4.7840 5.0 23.5 8.8 6.2 5.7 17.4 9.6 4.3780 4.8 21.4 8.3 5.5 5.4 15.8 9.0 3.8720 4.6 19.6 7.8 4.9 5.1 14.1 8.5 3.4660 4.3 17.4 7.3 4.4 4.8 12.5 7.9 3.0600 4.0 15.2 6.7 3.8 4.4 10.7 7.3 2.61550 6.4* 53.6 6.2 11.2 7.3* 46.8 8.2* 23.11500 6.3* 53.6 6.1 10.9 7.3 45.9 8.0* 23.11440 6.2* 53.6 6.0 10.5 7.1 43.8 7.9 22.91380 6.1* 53.6 5.9 10.1 6.9 41.8 7.8 22.31320 6.0* 53.6 5.7 9.7 6.7 39.8 7.6 21.41260 5.9* 53.6 5.6 9.3 6.5 37.7 7.4 20.41200 5.8* 53.7 5.5 8.9 6.3 35.7 7.2 19.41140 5.7* 53.7 5.4 8.7 6.1 33.6 7.0 18.41080 5.6* 53.7 5.2 8.2 6.0 32.2 6.8 17.41020 5.4* 53.7 5.1 7.8 5.7 30.0 6.6 16.4960 5.3* 53.7 4.9 7.4 5.5 27.8 6.4 15.4900 5.1* 53.8 4.7 6.9 5.3 25.6 6.2 14.7840 5.0* 53.8 4.6 6.5 5.0 23.5 5.9 13.6780 4.8 52.1 4.4 6.0 4.8 21.4 5.7 12.5720 4.5 46.9 4.2 5.6 4.6 19.6 5.4 11.4660 4.3 41.8 4.0 5.1 4.3 17.4 5.1 10.5600 4.0 36.9 3.8 4.6 4.0 15.2 4.8 9.318 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitOverview of Acoustic Data for Different Operating PointsSize 2Sound power level free air intake and discharge(Modular configuration, capacity size 1, filter class G2)Speed Measure point Sound power level L W [dB]12345Octave centre frequency [Hz] not rated rated63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)]Air intake 45 48 46 40 35 32 23 0 51 43Air discharge 44 48 47 44 39 33 25 0 52 45Casing 36 40 37 28 22 17 9 0 43 32Air intake 53 56 53 48 43 38 34 26 59 50Air discharge 51 56 55 52 48 43 39 31 60 53Casing 44 48 45 36 30 25 22 12 51 40Air intake 63 60 58 52 47 43 39 35 66 54Air discharge 57 60 60 56 53 47 45 39 65 58Casing 53 52 50 40 35 30 28 20 57 44Air intake 58 63 61 55 52 47 43 40 67 58Air discharge 59 64 64 59 57 51 49 44 69 62Casing 51 56 54 44 39 34 32 25 59 48Air intake 63 68 65 59 57 52 49 46 71 62Air discharge 62 67 69 64 62 56 54 49 73 67Casing 54 60 58 48 44 38 37 31 63 53Sound power level with other operating pointsAir flow rateSum level L W[dB(A)][m³/h] Air intake Air discharge Casing1550 – – – – 62 – – – – 67 – – – – 531500 – – – – 62 – – – – 66 – – – – 521440 – – – – 62 – – – – 66 – – – – 521380 – – – – 61 – – – – 65 – – – – 511320 – – – – 61 – – – – 64 – – – – 511260 – – – 58 60 – – – 62 64 – – – 48 501200 – – – 58 60 – – – 61 63 – – – 48 501140 – – – 57 60 – – – 61 63 – – – 47 491080 – – 54 57 59 – – 58 60 62 – – 44 47 481020 – – 55 57 59 – – 58 60 61 – – 44 47 48960 – – 55 57 58 – – 58 60 61 – – 44 46 47900 – 50 55 57 58 – 54 57 59 60 – 40 44 46 47840 – 51 55 57 – – 54 57 59 – – 41 44 46 –780 – 52 55 – – – 54 57 – – – 41 44 – –720 – 53 55 – – – 55 57 – – – 42 44 – –660 46 54 – – – 48 55 – – – 35 42 – – –600 53 – – – – 54 – – – – 42 – – – –Speed 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5Acoustic insulation of sound attenuator (accessories)Octave centre frequency [Hz]Sum levelapprox. Δ LW[dB]63 125 250 500 1000 2000 4000 8000 Intake 10Acoustic insulation [dB] 3 3 8 16 21 25 17 13 Air discharge 12PR-2009-0015-GB • Subject to modifications • Status 10/2009 19


Capacity Overview for Different Operating PointsSize 3Static pressure [Pa]1601401201008060Speed 1CWP 6/12 °Ct L1 = +27 °Cϕ 1 = 46 % r.h.Speed 2Speed 3Speed 4Speed 5WWP 70/50 °Ct L1 = +20 °C<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil Unit1: Contact protection2: Basic unit CS2 intake sound attenuator3: Compact basic unit (0 caps), dischargeplenum (0 caps)4: Air intake box (0 caps)5: Compact basic unit (1 cap), dischargeplenum (1 cap), discharge soundattenuator6: Basic unit filter class G37: Air intake box (1 cap)8: Compact basic unit (2 caps), dischargeplenum (2 caps)9: Air intake box (2 caps)10: Compact basic unit (3 caps), dischargeplenum (3 caps)11: Air intake box (3 cap)40200• 0 500 1000 1500 2000 2500Air flow rate [m³/h]System2-pipe system4-pipe systemAir flowrateCapacity stage 1 Capacity stage 2CoolingcapacityPressuredropHeatingcapacityPressuredropCoolingcapacityPressuredropHeatingcapacityPressuredrop•Q K Δp K•Q H Δp H•Q K Δp K•Q H Δp H[m 3 /h] [kW] [kPa] [kW] [kPa] [kW] [kPa] [kW] [kPa]2000 9.0 13.7 17.0 4.2 10.6 10.9 19.6 3.21900 8.7 12.9 16.5 4.0 10.2 10.3 18.9 3.01800 8.4 12.2 15.9 3.7 9.8 9.6 18.2 2.81700 8.1 11.4 15.3 3.5 9.5 8.9 17.4 2.61600 7.9 10.9 14.7 3.2 9.2 8.4 16.7 2.41500 7.6 10.0 14.0 2.9 8.7 7.7 15.9 2.21400 7.2 9.2 13.4 2.7 8.3 7.0 15.0 2.01300 6.9 8.4 12.7 2.4 7.9 6.4 14.1 1.71200 6.5 7.6 12.0 2.2 7.4 5.7 13.2 1.51100 6.1 6.8 11.3 2.0 6.9 5.0 12.4 1.41000 5.8 6.1 10.5 1.7 6.5 4.5 11.4 1.2900 5.3 5.3 9.6 1.5 5.9 3.8 10.5 1.0800 4.9 4.5 8.7 1.2 5.4 3.1 9.4 0.8700 4.4 3.7 7.9 1.0 4.8 2.5 8.3 0.7600 3.9 3.0 6.8 0.8 4.1 1.9 7.3 0.5500 3.3 2.2 5.9 0.6 3.4 1.4 6.1 0.42000 8.6* 47.5 8.2* 22.1 9.0 13.7 10.4 11.31900 8.4* 47.5 8.0* 22.1 8.7 12.9 10.1 10.81800 8.3* 47.6 7.9 21.6 8.4 12.2 9.8 10.21700 8.1* 47.6 7.7 20.5 8.1 11.4 9.5 9.61600 7.9* 47.6 7.5 19.8 7.9 10.9 9.3 9.21500 7.7* 47.6 7.2 18.6 7.6 10.0 9.0 8.61400 7.5* 47.6 7.0 17.4 7.2 9.2 8.6 8.01300 7.3 46.7 6.7 16.3 6.9 8.4 8.3 7.41200 6.9 42.4 6.4 15.1 6.5 7.6 7.9 6.71100 6.5 38.1 6.1 13.8 6.1 6.8 7.5 6.11000 6.1 33.9 5.9 12.8 5.8 6.1 7.1 5.6900 5.7 30.0 5.5 11.5 5.3 5.3 6.7 4.9800 5.2 25.7 5.2 10.1 4.9 4.5 6.2 4.3700 4.7 21.5 4.8 8.8 4.4 3.7 5.7 3.7600 4.2 17.5 4.4 7.5 3.9 3.0 5.1 3.0500 3.6 13.2 3.9 6.1 3.3 2.2 4.5 2.3* Capacity at max. allowed medium flow rate= for values in sample calculation refer to pages 24 - 2720 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitOverview of Acoustic Data for Different Operating PointsSize 3Sound power level free air intake and discharge(Modular configuration, capacity size 1, filter class G2)Speed Measure point Sound power level L W [dB]12345Octave centre frequency [Hz] not rated rated63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)]Air intake 42 43 42 36 29 0 0 0 47 38Air discharge 42 42 42 36 33 19 0 0 47 38Casing 34 34 33 22 16 0 0 0 39 27Air intake 47 49 48 42 36 27 0 0 53 44Air discharge 47 48 47 43 40 33 23 0 53 45Casing 39 41 39 29 22 15 5 0 44 33Air intake 50 53 52 46 40 33 25 0 57 48Air discharge 50 52 52 47 44 38 30 0 57 49Casing 42 44 43 33 26 20 13 0 48 37Air intake 54 57 57 51 45 38 33 25 61 52Air discharge 55 57 56 52 49 43 38 29 62 54Casing 47 49 48 38 31 26 21 10 53 42Air intake 60 62 61 55 50 44 40 35 66 57Air discharge 61 62 61 57 54 49 45 38 67 60Casing 52 54 52 43 37 31 28 20 58 47Sound power level with other operating pointsAir flow rateSum level L W [dB(A)][m³/h] Air intake Air discharge Casing2000 – – – – 57 – – – – 60 – – – – 471900 – – – – 57 – – – – 59 – – – – 471800 – – – – 57 – – – – 59 – – – – 461700 – – – – 57 – – – – 59 – – – – 461600 – – – 53 57 – – – – 59 – – – 42 461500 – – – 53 57 – – – 55 59 – – – 43 461400 – – – 54 57 – – – 56 59 – – – 43 461300 – – 49 54 57 – – 50 56 59 – – 38 44 461200 – – 50 55 57 – – 52 57 59 – – 39 44 461100 – 45 51 55 57 – 46 53 57 59 – 34 41 45 461000 – 46 53 56 57 – 48 54 58 59 – 36 42 45 46900 – 48 54 56 57 – 50 55 58 59 – 37 43 46 46800 38 50 55 57 – 39 52 57 59 – 27 39 44 46 –700 43 52 57 – – 43 54 58 – – 32 41 46 – –600 47 54 58 – – 48 56 59 – – 37 43 47 – –500 52 56 – – – 53 58 – – – 41 45 – – –Speed 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5= for values in sample calculation refer to pages 24 - 27Acoustic insulation of sound attenuator (accessories)Octave centre frequency [Hz]Sum levelapprox. Δ LW[dB]63 125 250 500 1000 2000 4000 8000 Intake 10Acoustic insulation [dB] 3 3 8 16 21 25 17 13 Air discharge 12PR-2009-0015-GB • Subject to modifications • Status 10/2009 21


Capacity Overview for Different Operating PointsSize 4Static pressure [Pa]1601401201008060Speed 1CWP 6/12 °Ct L1 = +27 °Cϕ 1 = 46 % r.h.Speed 2Speed 3Speed 4WWP 70/50 °Ct L1 = +20 °CSpeed 5<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil Unit1: Contact protection2: Basic unit CS2, intake sound attenuator3: Air intake box (0 caps)4: Compact basic unit (0 cap), basic unitfilter class G3, air intake plenum (1 cap),air discharge plenum (0 cap)5: Discharge sound attenuator6: Compact basic unit (1 cap), dischargeplenum (1 cap)7: Air intake box (2 caps)8: Compact basic unit (2 caps), dischargeplenum (2 caps)9: Air intake box (3 cap)10: Compact basic unit (3 caps), dischargeplenum (3 caps)402000 500 1000 1500 2000 2500Air volume flow [m³/h]• System2-pipe system4-pipe systemAir flowrate* Capacity at max. allowed medium flow rateCapacity stage 1 Capacity stage 2Cooling Pressure Heating Pressure Cooling Pressure Heating Pressurecapacity drop capacity drop capacity drop capacity drop• • ••Q K Δp K Q H Δp H Q K Δp K Q H Δp H[m 3 /h] [kW] [kPa] [kW] [kPa] [kW] [kPa] [kW] [kPa]2400 10.6 20.3 20.3 6.2 12.6 16.3 23.3 4.72300 10.4 19.4 19.5 5.8 12.3 15.5 22.6 4.52200 10.1 18.5 19.1 5.6 11.9 14.7 21.9 4.22100 9.8 17.6 18.5 5.3 11.6 13.9 21.2 4.02000 9.7 16.9 17.9 5.0 11.3 13.3 20.5 3.71900 9.3 16.0 17.3 4.6 10.9 12.5 19.7 3.51800 9.0 15.0 16.7 4.3 10.5 11.6 19.0 3.31700 8.7 14.0 16.0 4.0 10.1 10.8 18.0 3.01600 8.4 13.0 15.3 3.7 9.6 10.0 17.2 2.71500 8.0 12.1 14.7 3.4 9.2 9.2 16.3 2.51400 7.7 11.1 14.0 3.1 8.7 8.3 15.5 2.21300 7.4 10.3 13.3 2.9 8.3 7.6 14.6 2.01200 6.9 9.3 12.5 2.6 7.8 6.8 13.6 1.81100 6.5 8.3 11.6 2.2 7.4 6.1 12.7 1.61000 6.1 7.3 10.8 1.9 6.7 5.1 11.8 1.3900 5.6 6.3 9.9 1.7 6.2 4.4 10.7 1.1800 5.2 5.4 9.1 1.4 5.6 3.7 9.6 0.9700 4.6 4.4 8.1 1.1 5.0 3.0 8.5 0.72400 9.6* 51.4 9.1* 24.4 10.6 20.3 12.2 16.22300 9.5* 51.4 8.9* 24.4 10.4 19.4 11.9 15.52200 9.3* 51.4 8.9* 24.4 10.1 18.5 11.7 14.82100 9.2* 51.4 8.8* 24.4 9.8 17.6 11.4 14.22000 9.0* 51.4 8.6* 24.4 9.7 16.9 11.1 13.51900 8.8* 51.5 8.4* 24.4 9.3 16.0 10.9 13.11800 8.7* 51.5 8.3* 24.4 9.0 15.0 10.6 12.31700 8.5* 51.5 8.2* 24.3 8.7 14.0 10.2 11.61600 8.3* 51.5 8.0 24.3 8.4 13.0 9.9 10.91500 8.0* 51.5 7.7 22.9 8.0 12.1 9.5 10.21400 7.8* 51.6 7.4 21.4 7.7 11.1 9.1 9.41300 7.5* 51.6 7.1 20.0 7.4 10.3 8.7 8.71200 7.2 49.9 6.9 18.8 6.9 9.3 8.4 8.11100 6.8 45.5 6.6 17.2 6.5 8.3 8.0 7.31000 6.4 40.1 6.2 15.6 6.1 7.3 7.5 6.5900 5.4 30.0 5.5 12.5 5.2 5.4 6.5 5.0800 5.4 30.0 5.5 12.5 5.2 5.4 6.5 5.0700 4.9 25.2 5.0 10.7 4.6 4.4 5.9 4.222 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitOverview of Acoustic Data for Different Operating PointsSize 4Sound power level free air intake and discharge(Modular configuration, capacity size 1, filter class G2)Speed Measure point Sound power level L W [dB]12345Octave centre frequency [Hz] not rated rated63 125 250 500 1000 2000 4000 8000 [dB] [dB(A)]Air intake 46 47 45 37 32 22 0 0 51 40Air discharge 46 49 45 41 36 28 18 0 52 43Casing 38 40 36 26 19 10 0 0 43 31Air intake 51 54 52 45 39 33 27 0 58 47Air discharge 49 54 52 48 44 37 32 0 58 50Casing 43 46 43 33 26 20 15 0 49 37Air intake 56 59 57 50 44 39 35 26 62 52Air discharge 56 59 57 53 49 43 39 30 63 55Casing 48 51 48 38 31 26 22 12 54 42Air intake 60 64 61 55 49 44 41 36 67 57Air discharge 60 64 62 58 54 49 46 39 68 60Casing 52 56 53 42 36 31 29 21 59 47Air intake 63 68 66 59 54 49 46 43 71 62Air discharge 64 67 67 62 59 54 51 45 72 64Casing 56 60 57 46 41 36 34 27 63 51Sound power level with other operating pointsAir flow rateSum level L W[dB(A)][m³/h] Air intake Air discharge Casing2400 – – – – 62 – – – – 64 – – – – 512300 – – – – 61 – – – – 64 – – – – 512200 – – – – 61 – – – – 63 – – – – 502100 – – – – 61 – – – – 63 – – – – 502000 – – – – 60 – – – – 62 – – – – 501900 – – – 57 60 – – – 60 62 – – – 47 491800 – – – 57 60 – – – 60 62 – – – 47 491700 – – 52 57 59 – – 55 59 61 – – 42 47 481600 – – 53 57 59 – – 55 59 61 – – 43 47 481500 – – 54 57 59 – – 56 59 60 – – 43 47 481400 – – 54 57 – – – 56 59 – – – 44 47 –1300 – 48 55 57 – – 51 56 59 – – 38 44 47 –1200 – 50 56 – – – 52 57 – – – 40 45 – –1100 – 51 56 – – – 53 57 – – – 41 45 – –1000 40 53 57 – – 43 54 58 – – 31 42 46 – –900 45 54 – – – 47 55 – – – 35 43 – – –800 49 55 – – – 51 57 – – – 39 45 – – –700 54 – – – – 55 – – – – 43 – – – –Speed 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5Acoustic insulation of sound attenuator (accessories)Octave centre frequency [Hz]Sum levelapprox. Δ LW[dB]63 125 250 500 1000 2000 4000 8000 Intake 10Acoustic insulation [dB] 3 3 8 16 21 25 17 13 Air discharge 12PR-2009-0015-GB • Subject to modifications • Status 10/2009 23


Samples for Capacity Definition<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitThe tables with capacity data on pages 6 to 12 indicated cooling and heating capacityas well as sound power level of the <strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> of modular configuration witha G2 filter and without mounted air side accessories and/or additional external staticpressure.A different unit configuration and using air side accessories like air intake and dischargeplenums or sound attenuation modules change internal and external air sideresistance. Air ducts and discharges connected by others can increase air side staticpressure drop that must be covered by the <strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong>. In such a way the airflow rate of the unit decreases which results in reduced cooling and/or heating capacity.The sound level emitted in air ducts by others and via unit casing is also influencedby the size of air side resistance.The diagrams and tables given on pages 14 to 23 make it possible to calculate performancedata for such operating conditions that are different from "a least complicatedsituation".The following sample demonstrates the basic procedure:1: Pre-selection of unit size2: Determination of unit characteristics curve and actual operating point.3: Calculation of actual cooling and/or heating capacity4: If necessary - conversion of calorific output in other air/medium units5: Determination of actual sound power level6: Calculation of expected indoor sound pressure levelExample In an open plan office with a suspended ceiling of size 20 x 10 x 4 m 2 <strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong>s in compact configuration are to be installed:Cooling load: 12 kW at air intake 27 °C/46 % r.h. and chilled water 6/12 °C (total indoor cooling load)Max. sound pressure level: 45 dB(A) as of VDI 2081Accessories: – 2 discharge cover caps DN200 (only 3 out of 5 connectors should be used)– Air intake sound attenuator– Intake flexible connectionFilter class: G3External static pressure 35 Pa at 1000 m³/h (per unit)drop:1. Pre-selection of unit size Based on the projected air flow rate of around 1000 m³/h and max. allowed sound levelunit size 3 in capacity stage 2 and speed 2 is selected. The following preliminary capacityis calculated:Air flow rate: 1000 m³/h at app. 40 Pa static pressure (refer to unit curve speed 2, page 20)Cooling capacity: 6,5 kW (refer to table „Overview of capacity for different operating points size 3“page 20)Sound power level: 48 dB(A) (refer to table „Sound power level with other operating points“ on page 21)**) Note: In this case only discharge related sound level is considered, because a sound attenuator is providedon the intake side.2. Determination of unitcurveExampleIn characteristics curve field on page 20 the curve of external static pressure drop isentered. The points of the curve can be calculated using the formuladp2 = dp1 * (V2/V1)².dp1 = 35 PaV1 = 1000 m³/hV2 = 1500 m³/hdp2 = 35 Pa * (1500/1000)² = 78,8 PaCharacteristics curves of additional unit internal pressure drops (capacity stage 2 andfilter class G3) and pressure drops of air side accessories (air intake sound attenuator,compact basic unit with 2 caps) are added up to „unit characteristics curve“ which is asum of all additional external and internal pressure drops.24 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitSamples for Capacity DefinitionExampleThe task is to arrive at the sum of individual pressure losses at V = 1500 m³/hdp Capacity stage 2 = 5,0 Pa (as indicated on curve)dp Intake sound attenuator = 5,0 Pa (as indicated on curve)dp Filter class G3 = 12,5 Pa (as indicated on curve)dp Compact basic unit 2 caps = 19,5 Pa (as indicated on curve)dp External = 78,8 Pa (based on previous sample calculation)dp unit = (5,0 + 5,0 + 12,5 + 19,5 + 78,8) Pa = 120,8 PaThe intersection point of this unit curve with the unit curve of speed 2 is identical to theactual operating point of unit at speed 2.This results in air flow rate of around 980 m³/h (refer to Fig. 11).160140Unit characteristics curve120External static pressure drop100Speed 2Static pressure [Pa]806040Compact basic unit with 2 caps2009800 500 1000 1500 2000 2500Air flow rate [m³/h]Filter class G3Air intake attenuatorCapacity stage 2Fig. 11: Size 3 - curve field3. Determination of actualcooling capacity4. Conversion of calorificoutput in other air/mediumunits (if required)5. Determination of actualsound power level of unit.The actual cooling capacity can be interpolated from table data on page 20. Thisresults in cooling capacity of around 6,4 kW.If projected air intake conditions and/or medium temperatures deviate from standardconditions (cooling: air intake 27 °C/46 % r.h., CWP 6/12 °C and heating: air intake20 °C, WWP 70/50 °C for heating), calorific capacity can be adjusted to other parametersusing conversion factors (refer to page 1.2).Using tables „Sound power level with different operating points“ (refer to page 21) thesound power level of the basic unit can be interpolated on air intake, discharge sideand acoustic emission of casing. Air flow rate of 980 m³/h at speed 2 results in thefollowing values:LW intake: approx. 47 dB(A)LW discharge: approx. 49 dB(A)LW casing: approx. 36 dB(A)Because a sound attenuator is mounted on the intake side, the acoustic insulation ofsound attenuator (ΔLW = ca. 10 dB intake side, refer to table „Acoustic insulation ofsound attenuator - sum level“, page 21) must be deducted from the previously calculatedvalue:LW air intake (sound attenuator): approx 37 dB(A)PR-2009-0015-GB • Subject to modifications • Status 10/2009 25


Samples for Capacity Definition<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil Unit6. Calculation of expectedindoor sound pressurelevelTables on pages 6 to 13 (unit selection) and 16 to 23 (Overview of capacity) presentsound power level of basic units on air intake and discharge sides as well as unit casingacoustic emission. These data correspond to unit acoustic emission energy. In orderto determine actual sound level perceived by human ear at a certain point indoors,different factors need to be considered.Sound energy emitted in the air ductwork by others is usually absorbed (= reduced)thanks to absorption and reflection process. The manufacturer usually provides informationon certain components, e.g. acoustic insulation of a sound attenuator. Otherinfluencing factors can be e.g. material and form of air ducts, form and number of crosssection changes, duct ramifications, etc. As a rule, these can be estimated based onthe empirical data of the manufacturer.Sound energy emitted by unit casing in room direction is usually reduced only by thesuspended ceiling. In this case material type and ceiling thickness as well as possiblyused addition insulating material of suspended ceiling play a key role (e.g. mineral woolcoating).Supply and exhaust air flow entering and leaving the room through air ducts generatesflow noise, that to a great extent depends on the used product (refer to manufacturerspecifications). If the difference between sound level before the air duct opening andspecific sound level of duct opening amounts to more than 10 dB, the increase of thetotal level is to be neglected. If the difference is smaller - the level with a higher figuremust be increased by the level difference which is calculated according to the followingformula:Δ L = 10 * log (1+10^(L 1 -L 2 )/10)In our example it is assumed that only one duct opening is used for each unit and thespecific sound level difference exceeds 10 dB.In order to define the anticipated indoor sound pressure level - the previously calculatedA-rated sound power level is used in connection with a conversiondiagram Fig. 12.Conversion of sound power level in sound pressure levelSound Schallpegeldifferenz level difference ΔL=LW - LP - LP [dB] [dB]0510121520253035Fig. 12Unit Gert borders grenzt with an drei three Raumflchen indoor surfacesFreifeld0,5 1 2 3 4 5 6 8 10 15 20 30 40 60 70Abstand Distance von der from Schallquelle sound source [ m ] [m]FreeUnit Gert borders grenzt with an zwei two Raumflchenindoor surfacesGertist Unit mounted frei in der free Mitte in einer the middle Flcheof a surface2 4 8Direction RichtungsfaktorcoefficientFactory halls and swimming poolsFabrik- u. SchwimmhallenSchool classroomsResidential areas, offices, hotelReading rooms, TV studiosSchulrumeKrankenzimmer , kleine KirchenWohnrume, Bros, Hotelzimmer Konferenzrume, TheaterLesesle, FernsehstudiosRundfunkstudiosMusikzimmerRadio studiosa = 0,03α = 0,05α = 0,1α = 0,15α = 0,25α = 0,4800 m 3Large churchesHospital wards, small churchesConference rooms, theatresDepartment storesgroegroe KirchenKaufhuserConcert halls50 100 200 500 1000 2000 5000 10000 300005102050100200500100020005000Raumvolumen Room [ [m m 3 ]]Absorption factor αA wall surface that absorbs all sound waves that hit it has an absorptionfactor of a = 1. The above a m values represent the relationship between theactual and ideal absorption performance of a wall. They represent meanvalues.Absorption surface m2 (Sabin)This is the surface that completely absorbs all sound waves that hit it. It isnot identical to the entire room surface.Absorption Absorbtionsflche surface [ m [m 2 Sabin 2 Sabin] ]26 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitSamples for Capacity Definition1. Based on the room volume (800 m 3 ), an absorption surface of approx. 100 m 2 Sabinis estimated in accordance with the diagram Fig. 12“Homes, offices, hotel rooms, conferencerooms”.82 4Fig. 13: Direction coefficient2. The mean distance to the duct opening is assumed to be approx. 3 m and the directioncoefficient to be “2”, Fig. 13. The intersection of the dotted sample lines in the diagramFig. 12 mounts to the sound level difference: ΔL~12 dB.Direction coefficient 2(hemispherical radiation): unit is mounted free in the middle of a surfaceDirection coefficient 4(quarter-spherical radiation): unit borders with two room surfacesDirection coefficient 8(eight-spherical radiation): unit borders with three room surfacesSound level increase in dB1098765432112 3 4 5 6 8 10Number of unitsFig. 14: Sound level increase (dB)3. The anticipated A-rated sound pressurelevel L P for a unit is thus:L P = L W – ΔL = 49 dB(A) – 12 dB = 37 dB(A)Sound level in case of 2 discharge openings increases according to thediagram Fig. 14, by approx. 3 dB.Thus, the anticipated sound pressure level in the room amounts to:L Pges. = L P + 3 dB = 37 dB(A) + 3 dB = 40 dB(A)The approximate value for increased requirements (large office 45 dB (A) in table Fig.15) is thus fulfilled.Table „A-sound pressure level“ LP 1 as approximate value according to VDI 2081Room type A-sound level [dB(A)] Mean reverberation time [s]Apartment * **(Hotel room) night 35/30 30/25 0.5Residential rooms day 35 30 0.5AuditoriumsTV studio 30 25 1.5Concert halls 30 25 2.0Operas 30 25 1.5Theatre 35 30 1.0Cinema 40 30 1.0Lecture halls 40 35 1.0Reading rooms 40 35 1.0Seminar rooms 40 35 1.0Classrooms 40 35 1.0OfficesConference rooms 40 35 1.0Leisure rooms 40 35 0.5Break rooms 40 35 0.5Small offices 40 35 0.5Large offices 50 45 0.5Church 35 25 3.0Museums 40 35 1.5Service halls 45 40 1.5IT/Telecommunication room 55 40 1.5Laboratories 45 40 2.0Restaurants 40 to 55 2 1.0Kitchens 45 to 60 2 1.5Sales rooms 45 to 60 2 1.0Fig. 15* = Mimimum requirements** = Increased requirements1 Also refer to applicable building regulations, DIN standards and VDI guidelines (e.g. DIN 4109, DIN 1946, VDI 2058)2 Depending on applicationPR-2009-0015-GB • Subject to modifications • Status 10/2009 27


Installation SamplesOn-Demand Mounting of Intake and Discharge Side AccessoriesModular Version<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitCompact VersionFig. 16: Modular basic unit without accessoriesFig. 17: Compact basic unit without accessoriesFig. 18: Modular unit with air discharge boxFig. 19: Compact unit with air intake boxFig. 20: Air intake and discharge boxFig. 21: Air intake flexible connection + air intake soundattenuatorFig. 22: Intake flexible connection + discharge sound attenuator+ discharge boxFig. 23: Air intake box + air intake sound attenuatorFig. 24: Air intake box + air intake sound attenuator + air discharge sound attenuator + discharge box28 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitDimensions of Basic UnitsFig. 25: Dimensions modular unit typeRecommended service opening for maintenance work onthe basic unit1: Condensate tray2: Service panel3: Filter behind cover strip*) Dimensions of basic unit and service openingFig. 26Fig. 27: Dimensions compact unit typeDimensionsSizeb[mm]b max[mm]B[mm]1 682 1060 12602 982 1360 15603 1282 1660 18604 1432 1810 2010Please consider that possibly further or larger openingsmust be provided if accessories are mounted.PR-2009-0015-GB • Subject to modifications • Status 10/2009 29


Dimensions of Basic Units<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitMinimum mounting clearancesFig. 28Medium connections (warm/chilled water)Medium connections (warm/chilled water)212-pipe system heatexchanger CS1 and CS2Connections: 1/2" internalthreadSize Capacity stage1 2A 190 1654-pipe system heatexchanger with heatingand cooling circuitConnections: 1/2" internalthreadPos. 1: coolingPos. 2: heatingSize Capacity stage1 2A 215 215B 190 165C 30 30D 80 55E 205 230F 255 255Fig. 29 Fig. 30Unit weight and water charge of heat exchangerSizeModular typeWeight 1)[kg]Compacttype2-pipeWater charge [l]Cooling circuit4-pipeHeating circuitCS 1 CS 2 CS 1 CS 2 CS 1 CS 21 37 46 1.64 2.10 1.32 1.64 0.32 0.432 45 54 2.26 3.01 1.82 2.26 0.44 0.603 55 66 2.88 3.84 2.31 2.88 0.57 0.764 61 76 3.19 4.25 2.56 3.19 0.63 0.851) Max. basic unit weight without accessories30 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitAccessory SizesFig. 31Fig. 32Fig. 33Fig. 34Size 1Size 2Size 3Size 4Spare filter hoses (1 set = 5 pieces)Quality class G2, G3 (EN 779); regenerative filtermediumSize Order-Nr. Filter quality Filter lengthG2 G3 L1 ZGM.1A823 ZGM.1A833 approx. 7002 ZGM.2A823 ZGM.2A833 approx. 10003 ZGM.3A823 ZGM.3A833 approx. 13004 ZGM.4A823 ZGM.4A833 approx. 1450Air intake flexible connector (material class B1)Size Order-Nr. Weight [kg]1 ZGM.1A111 2.92 ZGM.2A111 3.73 ZGM.3A111 4.54 ZGM.4A111 5.4Air discharge flexible connector(material class B1)Size Order-Nr. Weight [kg]1 ZGM.1A112 2.92 ZGM.2A112 3.73 ZGM.3A112 4.54 ZGM.4A112 5.4Air intake box with round connector,insulated (galvanized steel)Size Order-Nr. Weight [kg]1 ZGM.1A041 5.82 ZGM.2A041 7.83 ZGM.3A041 9.94 ZGM.4A041 10.9Air discharge box with round connector,insulated (galvanized steel)Size Order-Nr. Weight [kg]1 ZGM.1A042 5.82 ZGM.2A042 7.83 ZGM.3A042 9.94 ZGM.4A042 10.9Cover cap for all sizes(galvanized sheet steel, not insulated)Size Order-Nr. WeightAir intake Air discharge [kg]1-4 ZGM.0A711 ZGM.0A712 0.3Air intake sound attenuator (galvanized sheet steelwith internal acoustic and thermal insulation)Size Order-Nr. Weight [kg]1 ZGM.1A211 16.22 ZGM.2A211 21.63 ZGM.3A211 26.94 ZGM.4A211 30.2Air discharge sound attenuator (galvanized sheetsteel with internal acoustic and thermal insulation))Size Order-Nr. Weight [kg]1 ZGM.1A212 16.22 ZGM.2A212 21.63 ZGM.3A212 26.94 ZGM.4A212 30.2Size 1 2 3 4b [mm] 682 982 1282 1482Octave centre frequency [Hz] Sum level approx. Δ L W [dB]63 125 250 500 1000 2000 4000 8000 Air intake side 10Acoustic insulation [dB] 3 3 8.0 16 21 25 17 13 Air discharge side 12PR-2009-0015-GB • Subject to modifications • Status 10/2009 31


Accessory Sizes<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitInstallation sample:Suspension rail with threadedrods M8+minor partsMountinglength[mm]Order-Nr.Weight[kg]950 ZGM.0A613 2.41550 ZGM.0A623 4.02150 ZGM.0A633 5.5Mounting with suspension railand mounting adapter on oneside and threaded rods on theother side.Fig. 35Suspension rail 950 mmCross section of suspension railand mounting adapterRail length enough for amaximum 1 basic unit and 1 airintake and discharge box.Fig. 36Suspension rail 1550 mmRail length enough for a maximum1 basic unit, 1 sound attenuatorand 1 air intake anddischarge box.Fig. 37Suspension rail 2150 mmRail length enough for a maximum1 basic unit, 1 intake anddischarge sound attenuator, 2sound attenuators and 1 air intakeand discharge box.Fig. 38In order to minimize the remaining structure borne sound it recommended to use standard spring elements.32 PR-2009-0015-GB • Subject to modifications • Status 10/2009


AB ABAB ABAB ABAB ABAB ABAB AB<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitOverview of ValvesSelection Table!The following selection table presents all available valvesmodels with main features and compatible control equipment.The following symbols are used:„•“ = Valve type compatible with the corresponding controlpanel or electric equipment.„–“ = Valve type not compatible with the corresponding controlpanel or electrical equipment.Valve typeFunctiontypeControltypeVoltage Compatible control equipment Controls byMATRIX500MATRIX2000MATRIX3000MATRIX4000ThermostatswitchothersR3 point(modulating)230 V~ – – (only 2-pipesystem)NC3 point(modulating)24 V~ – (only 2-pipesystem;transformerby othersnecessary)230 V~ – 3 point(modulating)(Transformerbyothers necessary)(Transformerbyothers necessary)– – T(2 floatingauxiliaryswitches)2 point(modulating)(only 2-pipesystem)230 V~ • Q2 point(modulating)24 V~ – – S(Transformerbyothers necessary)continuous24 V~(analoguesignal0..10 V)(Transformerby othersnecessary)(Transformerbyothers necessary)– – – – – PR-2009-0015-GB • Subject to modifications • Status 10/2009 33


Overview of Valve Actuators<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitModulating Actuator 230 V AC / 3-point Operation / opt. 2 Floating Auxiliary Switches /Modulating Actuator 24 V AC and 0-10 V/24 V AC / Thermoelectric Actuator 230 V AC and 24 V ACContinuous virtually continuous actuatorsPlastic motor casingC BAFloating auxiliary switch:Switch S1 (valve signal 100% open)Switch S2 (valve signal setting settable 0..100%)Technical data:Function R C N SControl mode 3-point 3-point 3-point continuousOrder-Nr. actuator(loose)OperatingvoltagePowerconsumption308 173 312 370 311 947 311 948230 V AC50/60 Hz230 V AC50/60 Hz24 V AC50/60 Hz0-10 V/24 V AC50/60Hz7 VA 7 VA 0.7 VA 1.4 VAProtection IP43 IP43 IP43 IP43Run time 120 s/50 Hz 150 s/50 Hz 120 s/50 Hz 120s/50 HzFig. 39: For dimensions of continuous and virtually continuous valveactuators refer to tableOperatingforce [N]Controlstroke [mm]Max. allowedambienttemp.180 180 180 1806.5 6.5 6.5 6.560 °C 60 °C 60 °C 60 °CCable [m] 2.7 2.7 2.7 2.7LoadcapacityAuxiliaryswitch-max. 5 (1) A/250 Vmax. 100 mA/24 V- -Rated dimensions [mm]A 100 109 100 100B 61 85 61 61C 49 49 49 49Thermoelectric valve actuatorsPlastic actuator casingTechnical data:Function T QControl mode 2-point 2-pointOrder-Nr. actuator 240 5072 240 5073Operating voltage230 V AC50/60 Hz24 V AC50/60 HzPower consumption [W] 3 3Heat up current [A] 0.6 0.7Rated current [A] 0.014 0.1Protection type IP44 IP44Run time (approx.) [min] 2.5 4Operating force [N] 90 N 90 NFig. 40: Dimensions of thermoelectric valve actuators in mmControl stroke [mm] 4 4Max. ambient temp. 50 °C 50 °CConnecting cable [m] 1 134 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitOverview of Valve BodiesTwo and Three-WayTwo and three-way valves– Brass or red brass valve body– Stainless steel spindle and coneTechnical data:Rated pressure16 barmax. medium temperature 120 °Cmax. glycol concentration 50 %Rated dimensions[mm]Stroke 2,5mma b c d eG 1/2" AG 3/4" A5666404034.536.655Stroke 6,5mmG 1/2" AG 3/4" A5666404032341818Fig. 41: Dimensions of two and three-way valvesThree-way valvesValve body with spindle stroke 2,5 mm:DNk VS A-AB[m 3 /h]k VS B-AB[m 3 /h]Valve externalthreadDp max[kPa]Order-Nr.(loose)15 1.6 1.0 G 1/2" A 200 240 507020 4.0 2.5 G 3/4" A 100 240 5078For suitable thermoelectric valve actuator refer to page 34Valve body with spindle stroke 6,5 mm:Pressure drop Δp [kPa]DNk VS A-AB[m 3 /h]k VS B-AB[m 3 /h]Valve externalthreadDp max[kPa]Order-Nr.(loose)15 0.25 0.16 G 1/2" A 600 240 506115 0.40 0.25 G 1/2" A 600 240 506215 0.63 0.40 G 1/2" A 600 240 506315 1.00 0.63 G 1/2" A 600 240 506420 1.60 1.00 G 1/2" A 300 240 506520 2.50 1.60 G 3/4" A 150 240 506620 4.00 2.50 G 3/4" A 50 240 5067For suitable virtually continuous/continuous valve actuators refer topage 34•Water flow rate V [l/h]Fig. 42: k VS -values for valves with spindle hub 6,5 mmTwo-way valvesValve body with spindle stroke 2,5 mm:DNk VS A-AB[m 3 /h]Valve external threadDp max[kPa]Order-Nr.(loose)15 1.6 G 1/2" A 300 240 506820 4.0 G 3/4" A 100 240 5141Pressure drop Δp [kPa]For suitable thermoelectric valve actuator refer to page 34Valve body with spindle stroke 6,5 mm:DNk VS A-AB[m 3 /h]Valve external threadDp max[kPa]Order-Nr.(loose)15 0.25 G 1/2" A 600 240 505415 0.40 G 1/2" A 600 240 505515 0.63 G 1/2" A 600 240 505615 1.00 G 1/2" A 600 240 505720 1.60 G 1/2" A 300 240 505820 2.50 G 3/4" A 150 240 5059•Water flow rate V [l/h]Fig. 43: k VS -values for valves with spindle stroke 2,5 mm20 4.00 G 3/4" A 50 240 5060For suitable virtually continuous/continuous valve actuators refer topage 34PR-2009-0015-GB • Subject to modifications • Status 10/2009 35


Overview of ValvesShut-off Valves<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil Unitk vs -value 1,45SW19All <strong>GEA</strong> valves can be optionally supplied withshut-off valves at the outlet.32These valves are used for shutting-off the coolingor heating medium as well as for adjusting andequalizing medium flow rate.3/4"MNG3/4"Depending on rated size of the control valve, shutoffvalves are used with k vs -value of 1,45 or k vs -value 2,20.k vs -value 2,2051SW24Technical data:Rated pressure:10 barMax. water inlet temperature: 130 °CpH-value: 8 - 9,533As medium water with a max. 50% glycol rate isallowed.Connection3/4"663/4"Depending on the valve equipment the shut-offvalves are supplied with outer thread connection(designation number „4“ in on page 51) or withconnecting nut and solder fitting (designationnumber „5“, refer to Product type code onpage 51).3/4"15Control valveShut-off valvek vs -valuesConnectionthreadk vs -valuesConnectionthreadSolder fittingCu pipe180.25-1,60 G 1/2" A 1.45 G 3/4" A Ø 152.50-4,00 G 3/4" A 2.20 G 3/4" A Ø 15Fig. 44The setting of the necessary medium flow rate is carried out on the basis of the following diagrams. The pre-settingcorresponds to the number of rotations to the left of the setting/adjustment screw starting from the right stop position(valve closed).k vs -value 1,45Pre-settingk vs -value 2,20Pre-setting1/4 1/2 1 1 1/2 2 3 4 5 6 71/2 1 11/2 2 21/2 3 4550508404030302020Pressure drop Δp [kPa]109876543Pressure drop Δp [kPa]109876543221102030405060708090100200300Water flow rate m W [kg/h]400500600700800900100012030405060708090100200300400500Water flow rate m W [kg/h]600700800900100015002000Pre-setting 1/4 1/2 1 1 1/2 2 3 4 5 6 7 8kv-values 0.07 0.13 0.22 0.32 0.43 0.65 0.85 1.10 1.25 1.40 1.45Pre-setting 1/2 1 1 1/2 2 2 1/2 3 4 5kv-values 0.2 0.4 0.6 1.0 1.5 1.7 2.0 2.236 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitOverview of ValvesBall Traps263/4“27 36SW 273/4“All <strong>GEA</strong> valves can be optionally supplied with balltraps.These are necessary to shut-off cooling or heatingmedium.Materials:Valve casing:Ball:Gasket:BrassBrass, groundRubber63Technical data:Rated pressure:10 barMax. water inlet temperature: 110 °Ck vs -value6,70 m³/hAs a medium water and water/glycol is allowed.3/4“15Depending on the valve equipment ball traps aresupplied with outer thread connection (designations2 and 4, see Product Type Code on page 51)or with connecting nut and solder fitting (designations3 and 5, see Product Type Code onpage 51).18k vs -valueBall trapConnection threadSolder fitting for Cupipe6.70 G 3/4" A Ø 15Fig. 45The servicing of the ball cock is performed via a flat-bladed screwdriver.2015Pressure drop Δp [kPa]109,08,07,06,05,04,54,03,53,02,52,01,51,00,90,80,70,60,55006007008009001000110012001300140015001600170018001900200025003000•Water flow rate m W [kg/h]PR-2009-0015-GB • Subject to modifications • Status 10/2009 37


Control via Thermostat / Speed Switches, Controls by Others<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitTerminal box with connections for <strong>Geko</strong> unitsTerminal boxSheet steel electricswitch boxOrder code basic unitGMxx.xxxx.AxxxxGMxx.xxxx.BxxxxGMxx.xxxx.CxxxxGMxx.xxxx.ExxxxGMxx.xxxx.HxxxxGMxx.xxxx.KxxxxGMxx.xxxx.LxxxxGMxx.xxxx.MxxxxGMxx.xxxx.OxxxxGMxx.xxxx.RxxxxIn order to carry out connection to the control system all componentslike fan(s) and valve(s) are wired in the terminal box.Depending on the selected unit configuration and valve equipment, theterminal box is either made of plastic or sheet steel. The selection isperformed using the product type code, as illustrated.Using thermostat and speed switches of series C easy control is provided for fan coil units. Switches are supplied loose.Unit mounting is not possible.The switches can be used with: Valve type Switch type Return airsensorOrder symbolCoolingandHeatingCoolingorHeatingHeatingCooling4-pipe system chilledand warm water2-pipe system chilled orwarm water2-pipe system warmwater2-pipe system chilledwaterCMT (= 983 861) 0 QCET (= MCR2000)CMT with flow thermostat (flowthermostat to be ordered separatelyusing order number 902 035)CET with flow sensor (flow sensorincluded in package)without 0with 5without 1with 6R0 QCMT 0 QCETwithout 0with 5R––– ––– CMS (= 983 860) 0 PCMT 0 QCETwithout 0with 5R––– ––– CMS 0 PRAlternatively to a return air sensor, a room temperature sensor can be connected to a CET type switch. If a return airsensor is used, the fan mustbe operating in a continuous mode.Please consider:In connection with thermostat / speed switches only on/off valve actuators can be used (T).Relay kitis necessary if up to four fan coil units areswitched in parallel. The mixing of different<strong>Geko</strong> types and sizes is allowed - refer tonote!With kit 2Withoutkit0Slave unit with relay kitOrder codeD 0 • 1 • AOrder code D 0 • 2 0 1 • Z DNOTE!Only one unit with CMT/CMS switch may be operated without a relay kit. Unitsthat are operated with CET switch must be equipped with a relay kit.38 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitControl via Thermostat / Speed Switches, Controls by OthersOperation of thermostat and speed switchesSwitch typeFunctionsCMS – On/off switch– Fan speed selection switch 1-2-3CMT – On/off switch– Fan speed selection switch 1-2-3– Setpoint setting indoor temperature 5 ... 35 °C (mechanical setting limitation)– Thermostat with neutral zoneCET – On/standby switch– Fan speed selection switch 1-2-3– Setpoint setting indoor temperature 5 ... 35 °C (mechanical setting limitation)– Thermostat with settable neutral zone– Enable input via potential free floating contact by others– Room frost protection– Connection possibilities for external room or return air sensor and flow sensor– Integrated indoor temperature sensorSensorsIndoor temperaturesensor903 414Flow sensor903 434Return air sensor903 474FunctionsThermistor sensor for on-wall mounting– NTC-sensor element; resistance coefficient at 25 °C = 10 kΩ– Plastic casing: white, similar to RAL 9010– Protection class IP 20; dimensions in mm (W x H x D): 84 x 84 x 22Thermistor sensor with tightening strap for mounting at inlet line– NTC-sensor element; resistance coefficient at 25 °C = 10 kΩ– Max. ambient temperature 100 °C– Protection class 2; cable length 2 mThermistor sensor for mounting in unit– NTC-sensor element; resistance coefficient at 25 °C = 10 kΩ– Protection class IP 43; casing dimensions (D x L): 6 x 100 mm; cable length 1,5 m– Max. ambient temperature 100 °CFlow thermostat902 035Flow thermostat for change-over between heating or cooling mode– Capillary length 1000 mm; switching points 19 °C/25 °C ± 1 K– Operating voltage 250 VAC 50/60 Hz– Dimensions in mm (W x H x D): 85 x 53 x 65– Flow thermostat in enclosed casing for wall mounting, the measuring capillaries aremounted on the water inlet.Additional sensors which are supplied loose and wired on-site by others should be ordered optionally (not in connection with the above-mentionedswitch types CMT and CMS).NOTE!Flow and return air sensor are integrated in the relevant controls packages and donot have to be selected separately if ordered using the package number.PR-2009-0015-GB • Subject to modifications • Status 10/2009 39


onfuncsend%Control System <strong>GEA</strong> MATRIXRecirculating Air Unit, Sizes 1-4<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil Unit<strong>GEA</strong> MATRIX ® 500/2000System features:– Assigning of temperature 10... 30 °C– Assigning of fan speed– Limitable setting range– Change-over between normal / economy mode on controlpanel– Room temperature measurement via control panel– External room temperature sensor can be connected*– Valve control (2-point)– Temperature control via fan on/off and/or valve(s)– Status signals via LED– Group control– Group switch-off in event of malfunctionAdditional features with MATRIX 2000:– Extended temperature setpoint assignment.: 7...40 °C(default 10..30 °C)– Temperature control via fan speed switch and valves– Network capability* if required with add-on moduleMATRIX OP4CControl panel for MATRIX 500 control system– Pure white casing, IP20 protection type– Setpoint temperature setting– Fan speed selection switch 0 - A (continuous) - 1-2-3– Economy mode switch– LEDs for operation / malfunction / ext. control– Integrated room temperature sensorMATRIX OP5CControl panel for MATRIX 500,like OP4C, but with:– Economy mode buttonMATRIX OP20CControl panel for MATRIX 2000,like OP5C, but with:– Fan speed selection switch 0-A (Auto)-1-2-3MATRIX OP21CControl panel for MATRIX 2000,like OP20C, but with:– Economy mode buttonSTUA<strong>GEA</strong> MATRIX 3000System features:– Assigning of temp. 7 ... 40 °C (default 10... 30 °C)– Assigning of fan speed– Limitable setting range– Change-over between normal / economy mode on controlpanel– Input for change-over between normal / economy mode orunit OFF with frost protection– Room temperature measurement via control panel– External room temperature sensor can be connected– Valve control (2-point)– Temperature control via fan and/or valve(s)– Room frost protection function– Status signals via LED– Operating and error messaging viapotential free change-over contacts– Stand alone unit or group control– Stand alone unit switch-off in event of malfunction– Network capabilityMATRIX OP30CControl panel for MATRIX 3000/4000 control system– Pure white casing, IP20 protection type– Setpoint temperature setting– Fan speed selection switch 0 - A (auto) - 1-2-3– LEDs for operation / malfunction / ext. control– Integrated room temperature sensorMATRIX OP31CAs OP30C control panel, but also includes:– Normal / economy mode switchMATRIX OP44CAs OP31C control panel, but also includes switches for:– Change-over between heating / cooling / automaticoperation– Change over between recirculating and mixed air modeBCDMATRIX OP50CControl panel for MATRIX 3000/4000 control system– Pure white casing, IP20 protection type– Menu-assisted operation via rotating switch– LCD display with plain text display– Status messages via pictograms– Integrated room temperature sensorMATRIX OP51CAs OP50C control panel, but also includes:– Integrated weekly clock timer with programme forholiday and special switching daysEFMATRIX.IRInfrared remote control for MATRIX 3000/4000control system– Black casing, similar to RAL 9004– LCD display approx. 45x30mm– Functions such as OP44C (without operation,malfunction and ext. control messaging, no integr. roomtemperature sensor)– Max. range 20moff- +N40 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitControl System <strong>GEA</strong> MATRIXRecirculating Air Unit, Sizes 1-4MasterunitSlaveunits:MATRIX 500: 1-3MATRIX 2000: 1-15With controller type:D0 = 7x2x0,8 J-Y(ST)YD2 = max. 5x2x0,8 J-Y(ST)YWith controller type:D0 = 7x2x0,8 J-Y(ST)YD2 = max. 5x2x0,8 J-Y(ST)Y3x1,5 mm 2 NYM3x1,5 mm 2 NYM3x1,5 mm 2 NYM230 V ~50 HzMATRIX 2000CoolingKHeatingH0Heating or cooling HoK 1Heating and cooling HuK 2Flow sensor (only with HoC units)with connecting cableMATRIX500 HoCMATRIX 500 H,C, HaC/MATRIX 2000w/o return sensor * 1 0with return sensor * 6 5Cooling/heating mediumControl panelOrder code MATRIX 500D 0 • 5 1 • AD 0 • 5 0 1 • Z DOrder code MATRIX 2000D 2 • 1 • AD 2 • 0 1 • Z DMasterunitSlave units1-15e. g. 2x2x0,5 HelukabelWith controller type:D2 = 4x2x0,8 J-Y(ST)YD3/4 = e. g. 1x2x0,5 Helukabel3x1,5 mm 2 NYM3x1,5 mm 2 NYM3x1,5 mm 2 NYM230 V ~50 Hz2x2x0,8Flow sensor (only with HoC units)with connecting cableCooling/heating mediumSpeedsIndividual unit controlwith operation- anderror messagingGroup controlwith operation anderror messagingInput unit OFF withroom frost protectionInput economymode contactSupply air temp.limitationSilentvalve controlContact cooling andheating requestConnection forexternal sensor• • 3 1 2 0 1up to3-speedup to5-speed• • 3 2 2 0 1• • 3 1 3 1• • 3 2 3 2• • • 3 3 3 3• • • 3 4 3 4• • • • • • 4 5 4 5• • • • • • • 4 6 4 6CoolingHeating0Cooling or heating 1Cooling and heating 2w/o return sensor * 0with return sensor * 5Control panelOrder codeD • • A D • • Z D* Alternative room temperature sensor (refer to page 46) / with MATRIX.IR return or indoor sensor absolutely necessary!PR-2009-0015-GB • Subject to modifications • Status 10/2009 41


<strong>GEA</strong> MATRIX Control SystemSystem Description<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitOverviewNormal/economy modebuttonsSpeed stageselection switchValve actuator type2 point (modulating)••••LEDs foroperation/fault/ext.controlSetpointtemperatureMATRIX 500MATRIX 500 control system supports all basic functions (heating/cooling) of recirculatingair fan coil unit. The controller can be used in the following unit types:– 2-pipe units „only heating“– 2-pipe units „only cooling“– 2-pipe units „cooing or heating“ (change over)– 4-pipe unit „cooling and heating“The speed can be set manually and the unit switched off via the control panel. Valveswith on/off or modulating control behaviour and a supply voltage of 230 V AC can beactivated to control the heating and/or cooling capacity. Additionally, the MATRIX 500enables monitoring of the fan motor via thermal contacts with external leads as wellas the condensate water level for cooling units with a condensate pump. The connectedsensors are monitored as well.The OP4/OP5 control panel enables the setpoint values to be set quickly and easilywithout extensive prior experience. Mechanical limit stops can be used to limit the settingrange for the setpoint temperature and speed stage. Room temperature is measuredvia a sensor integrated in the control panel. If the control panel is positioned inan unfavourable location (such as by the door), an external temperature sensor or returnair sensor can be connected (not possible on changeover systems). Systemfaults are signalled centrally via the red “malfunction” LED and output using a changeovercontact. If economy mode is activated, it is displayed via the yellow LED integratedinto the button. In addition to protection type IP20 (OP4 C/OP5 C), an IP54 controlpanel model (OP5 I) is available for moist areas.The connection in the unit is made via plug-in cage clamps. Electronics, fans andvalves (230V) are fused separately via two backup fuses on the power supply. A fuseof B 10A type must be supplied to provide the necessary circuit protection.The MATRIX 500 can be used for controlling individual circulating air units and recirculatingair unit groups as well.Valve actuator2 point 3 point•• •• •• •MATRIX 2000The MATRIX 2000 control system is based on features incorporated in the MATRIX500 system but also provides additional functions that can be summarized as follows:– Along with manual speed selection the fan control can be also carried out in a 3speed mode based on the deviation of actual temperature from the setpoint.– With 2-pipe units 3-point modulating valve actuators can be controlled as well.– Besides, the control of valve actuators using 24V AC supply voltage is alsopossible (transformer by others).The direct connection of an external room temperature sensor is not possible withchange over units, but can be performed via a Global Module. A fault message canalso be received using a Global Module. Direct tapping is not possible.42 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil Unit<strong>GEA</strong> MATRIX Control SystemSystem DescriptionNormal/economy modebuttonsSpeed stageselection switchLEDs foroperation/fault/ext.controlSetpointtemperatureswitchThe OP20/OP21 control panel enables the setpoint values to be set quickly and easilywithout extensive prior experience. Mechanical limit stops can be used to limit the settingrange for the setpoint temperature and speed stage. Room temperature is measuredvia a sensor integrated in the control panel. If the control panel is positioned in anunfavourable location (such as by the door), an external temperature sensor or returnair sensor can be connected (not possible on change over systems please use a GlobalModule). System faults are signalled centrally via the red “malfunction” LED. Ifeconomy mode is activated, it is displayed via the yellow LED integrated into thebutton.In addition to protection type IP20 (OP20 C/OP21 C), an IP54 control panel model(OP21 I) is available for moist areas.The connection in the unit is made via plug-in cage clamps. Electronics, fans andvalves (230V) are fused separately via two microfuses on the power supply. A backupfuse B 10A must be supplied to provide the necessary circuit protection.The MATRIX 2000 can be used for controlling individual recirculation air units and alsorecirculation air unit groups. The integrated MATRIX.Net bus system enables integrationof up to 16 several groups to one network. The combination with MATRIX 3000controllers and connection of Global Modules and communication interfaces is alsopossible./5Valve actuator2 point 3 point• •• •• •• •MATRIX 3000The Matrix 3000 control system is based on the MATRIX 2000 system and providesadditional functions that can summarized are as follows:3-point valves with modulating control behaviour can be applied on 4-pipe systems.Mixed operation is also possible (2-point cooling valve / modulating heating valve ormodulating cooling valve / 2-point heating valve).Operation and fault signals are output via two change-over contacts on the unit. Themaximum load on the contacts at 230 V AC is 4 A ohmic / 2 A inductive.The supply air temperature can be limited for heating and cooling. Fixed and slidinglimits can be defined.An external temperature sensor or return air sensor can be connected to all systemtypes.An additional control input enables the following operating modes that can be setexternally:– Normal/economy operation or– Unit OFF with frost protectionVarious types of control panels are available. The range varies from a simple variantwith setpoint temperature and fan operating mode selection using infrared remotecontrol to a control panel with display. The display unit can also be supplied with anintegrated weekly timer.MATRIX 4000The Matrix 4000 control system is based on the MATRIX 2000/3000 system and providesadditional functions that can summarized are as follows:In order to provide improved selection of heating/cooling capacity a five speed fancontrol is enabled.For applications with highest comfort requirements electronic control elements provideabsolutely silent valve control.Four additional control inputs enable external assignment of the following operatingmodes:– Normal mode– Economy mode– Free mode– Unit OFF with frost protection– Compulsory setting of a fan speedA connection possibility for an outdoor sensor makes it possible to activate summercompensation. Outdoor air temperature value is automatically transmitted to all unitsconnected within the MATRIX.Net.PR-2009-0015-GB • Subject to modifications • Status 10/2009 43


<strong>GEA</strong> MATRIX Control SystemOverview of Features<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitDescription of features MATRIX500MATRIX2000MATRIX3000MATRIX4000Unit type 2-pipe systems: „only heating“, „only cooling“; „heating or cooling“ 4-pipe system heating and cooling Fan mode up to 3 speeds up to 5 speeds Temperature related fan speed switching Minimum speed 1 Motor monitoring with external thermal contacts Valve control 2 and 4-pipe system: on/off actuators 2-pipe system: 3-point modulating actuator 4-pipe system: 3-point modulating actuators Silent control (semiconductor relay)External heating valve with cooling unit with fan switch off Electric heating 1-speed 2-speedFrost protection Room frost protection Unit frost protectionSummer/winter compensation * * Supply air temperature limitationMin/Max limitation heating Min/Max limitation cooling Control inputs Economy mode Economy mode or door or window contact * Economy mode and door or window contact and unit OFF and free operatingmode* * Measuring outdoor temperaturevia local sensor connectionusing MATRIX.AI Measuring inlet temperature via local sensor connection Measuring return air temperaturevia local sensor connection ** Measuring supply air temperaturevia local sensor connectionMessages/signals Alarm condensate level too high with unit switch off Heating and/or cooling request * * Status signal via change-over contact * Fault signal via change-over contact * Mixed air damper control Open/close or continuous Exhaust fan control 1 speed via relay output via power unit / exhaust air controllerChiller control up to 2 speeds via MATRIX.RF module Control modes Indoor temperature control Supply air temperature control MATRIX.Net bus system can be extended by: MATRIX.DI MATRIX.AI MATRIX.DO MATRIX.RF MATRIX.Clock MATRIX.EMMATRIX.LON Service tools MATRIX.PDA MATRIX.PC Control panels MATRIX OP4C/MATRIX OP5x MATRIX OP20C/MATRIX OP21xMATRIX OP30x MATRIX OP31x MATRIX OP44x MATRIX OP50x/51x * with additional module only**not with heating or cooling units44 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil Unit<strong>GEA</strong> MATRIX Control SystemMounting Control PanelsAs the control panel is split into two units, the control panel cover only needs to besnapped on the mounting plate during commissioning. This provides optimumprotection against dirt and damage for the control panels during the constructionphase.The cable connection is established via cage clamps. This enables quick and easy useof solid and flexible cores.To mount the control panel in a standard in-wall socket, corresponding drill holes needto be provided in the mounting plate.The control panel can also be fitted directly on the wall (cable laid under plaster or incavity wall).IP54 control panels for moisture proof applications are available on request.To prevent dirt accumulation or accidental operation, control panel covers areavailable as accessories (refer to Fig. 49 on page 46).PR-2009-0015-GB • Subject to modifications • Status 10/2009 45


<strong>GEA</strong> MATRIX Control SystemSensors/Accessories<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitFig. 46Fig. 47Indoor sensor, order-Nr. 903.414Thermistor sensor for on-wall mounting– NTC sensor element– Plastic casing: white, similar to RAL 9010– Resistance coefficient at 25 °C = 10 kΩ– Protection type IP20– Dimensions in mm (W x H x D): 84 x 84 x 22The 903.414 indoor sensor replaces indoor sensor in theMATRIX OP XXC control panels. The additional sensormust be fitted if the control panel is mounted in a locationthat is unsuitable for accurate temperaturemeasurement.External sensor order-nr. 903.454Thermistor sensor for measuring ambient temperaturee.g. for summer/winter compensation (according to DIN1946 part 2/3)– NTC sensor element– Impact resistant white plastic casing– for outdoor wall mounting– PG bolts– Resistance coefficient at 25 °C = 10 kΩ– Protection type IP 54– Dimensions in mm (W x H x D): 65 x 50 x 37.5Flow sensor order-nr. 903.434Thermistor sensor for mounting at inlet line– NTC sensor element– Sensor on basic plate; white plastic casing;RAL 9010– Mounted with tightening strap at inlet line– Max. ambient temperature 100 °C– Dimensions in mm (W x H x D): 85 x 53 x 65– Resistance coefficient at 25 °C = 10 kΩ– Protection type IP 43Fig. 48Unit capwhite order nr. OPD.C(for OP21C / OP30C / OP31C / OP44C)Light grey order-nr. OPD.I(for OP21I / OP30I / OP31I / OP44I)For covering operating elements of control panelThe control panel cover is hung into the guide slots of thecontrol panel and protects the control panel from dirtaccumulation and accidental operation.Fig. 4946 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitControls System <strong>GEA</strong> MATRIXGlobal ModulesThe global modules of the MATRIX control system are designated for input and outputof MATRIX system signals. The global modules enable the transmission of messagesand operation statuses to external units as well as control via these external units. Themodules can be integrated at any location within the MATRIX network. The networkmay contain and simultaneously operate a maximum of 2 MATRIX modules of thesame type (DI,DO,AI) or 16 modules (LON).The modules are supplied with the default factory configuration. Configurations withother settings can be adjusted using the MATRIX.PC software..Technical data:Power supply 24 V DC ± 15 %Protection type IP 20Operation temperature 0 up to +45 °CFusing10 A TMountingMounting railMATRIX.DI max. current consumption 0,1 AMATRIX.DI dimensions106 mm x 90 mm x 58 mmMATRIX.DO max. current consumption 0,14 AMATRIX.DO contact assignment 250 V/5 A (ohmic); 2 A (inductive)MATRIX.DO dimensions160 mm x 90 mm x 58 mmMATRIX.AI nominal current consumption 0,03 AMATRIX.AI dimensions160 mm x 90 mm x 58 mmMATRIX.LON nominal current0,045 AconsumptionMATRIX.LON dimensions106 mm x 90 mm x 58 mmDigital input module MATRIX.DIThe digital input module MATRIX.DI is used to receive 8 independent digital controlsignals.Factory configuration:Input valid for Closed contact results in1 all groups HVAC Heating Mode2 all groups HVAC Cooling Mode3 all groups Normal mode4 all groups Economy mode5 Group 0 Fan in speed 36 Group 0 Secondary air damper close7 Group 0 Secondary air damper open8 Group 0 Mixed air operation 100 %Digital output module MATRIX.DOThe module has 8 digital outputs with potential free change over contacts.Factory configuration:Output valid for Energized relay signals1 all groups Operation2 Group 0 Fault message3 Group 0 Frost message4 Group 1 Fault message5 Group 1 Frost message6 Group 2 Fault message7 Group 2 Frost message8 all groups Fault messagePR-2009-0015-GB • Subject to modifications • Status 10/2009 47


Controls System <strong>GEA</strong> MATRIX<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitAnalogue input module MATRIX.AIThe module has 8 analogue inputs that are controlled using 0…10 V/2..10 V signals orcan be supplied with NTC sensors (10 k Ohm/25 °C).Factory configuration:Input valid for Parameter Type Filtervalue1 all groups OutsidetemperatureNTC 0 –Measurementrange2 all groups Inlet temperature NTC 0 –3 Group 0 Room setpoint 0 ... 10 V 0 10 – 30 °C4 Group 1 Room setpoint 0 ... 10 V 0 10 – 30 °C5 Group 2 Room setpoint 0 ... 10 V 0 10 – 30 °C6 Group 1 Outside air ratio 0 ... 10 V 0 0 ... 100 %7 Group 2 Outside air ratio 0 ... 10 V 0 0 ... 100 %8 Group 3 Outside air ratio 0 ... 10 V 0 0 ... 100 %MATRIX.LON moduleThe MATRIX.LON communication module is part of the global modules of the <strong>GEA</strong>MATRIX control system and is used for connecting the MATRIX control system to anetwork structure in accordance with the LON WORKS standard. It enables the connectionof air treatment components to a building management system or other facilitymanagement systems. It also enables external systems such as dampers or lightingsystems to be controlled via the MATRIX OP50/51 control panel. The module can beintegrated into the MATRIX network at any point.Gruppe 2Gruppe 4 Gruppe 16Gruppe 3 Gruppe 1MATRIX.Clock timer moduleThe MATRIX.Clock timer module is intended for use as a central weekly timer. Themodule can be integrated into the MATRIX network at any point and supports up to 16groups in a network. The groups can be assigned individually to six weeklyprogrammes, special switching days and the holiday programme. In each weeklyprogramme, up to four switching times (2 x on / 2 x off) can be defined. Additionally, upto six special switching days with up to four switching times (2 x on / 2 x off) per specialswitching day can be defined. Holiday periods can be defined via the holiday days thatcan be programmed for the whole calendar year. Input is carried out via astraightforward “push&turn” control. Ease of user navigation is ensured by means ofstructured menus, plain text messages and pictograms. The current status of theindividual programmes is displayed via a menu.The timer module can be toggled between six different languages online. The switchbetween summer and winter time is done automatically. If required, a blockingprotection e.g. for pumps can be activated (once a week). Additionally, the time formatcan be selected between 12 and 24 hour display.Power to the clock timer is supplied via the MATRIX controller’s power unit..There are two different variants available:– MATRIX.Clock C with IP 20 protection type; colour – white (similar to RAL 9016)– MATRIX.Clock I with IP 54 protection type; colour – light grey (similar to RAL 7035)48 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitControls System <strong>GEA</strong> MATRIXMATRIX.OP71 control panel for all groupsThe MATRIX.OP71 control panel is designed to be operated from one central point. Itcan integrated at any location within the MATRIX network and can simultaneouslyserve up to 16 groups.Up to 16 unit groups can be assigned to one cluster:– One unit group per each cluster– Each cluster with up to 16 unit groups.Clear text menus and "push&turn" function enable easy handling during operation orconfiguration. A maximum of 16 unit groups can be induvidually grouped to clusters.Using the control panel the wanted setpoints for temperature, fan speed, etc. can beassigned for each cluster. Thanks to control panel features comprising all groups, thenecessary room or return air sensors are located in the respective groups (grouplocations).Local control panels (OP2xx, OP3xx, OP4xx, OP5x) can be additionally integrated inindividual groups. Their functional scope can be defined and adjusted using the controlpanel for all groups. Thus, a relative daily setpoint can be entered via a local controlpanel, whereas the OP71C setpoint is assigned as standard.The integrated clock timer enables to assign 8 weekly programmes to clusters at anysequence. Each weekly programme enables to enter four switching times per day(2 x On/2 x Off), that can also be set to be valid for the whole day. Besides, it is possibleto set 8 special switching days with up to four switching times (2 x On/2 x Off) perspecial switching day. Holidays / bank holidays can be set using the calendar annualprogramme.During holidays the unit can be set to operate in "unit off" or economy mode.The summer / winter time switch over is performed automatically.The control unit is currently supplied with 7 selectable languages:– German– English– French– Polish– Czech and– Hungarian.Two different variants are available:– MATRIX.OP71C with IP 20 protection type; colour – white (similar to RAL 9016)– MATRIXOP71I with IP 54 protection type; colour – light grey (similar to RAL 7035)PR-2009-0015-GB • Subject to modifications • Status 10/2009 49


Controls System <strong>GEA</strong> MATRIX<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitService toolsMATRIX.PDAThe MATRIX.PDA service tool is used for setting parameters of the MATRIX controlsystem and makes the commissioning and maintenance of systems considerablyeasier. The service tool can be connected via the service interface that is integratedinto all control panels, controllers, global modules, the clock timer and thecommunication modules. Input is carried out via a straightforward “push&turn” control.The following main functions are available:– Automatic network scanning with display of detected users– Plain text error display– Modification of parameters such as temperature limits, times or control type– Display of actual values– Display of current unit status such as HVAC mode or valve position– Manual control of actuators such as fans and valves– Reading out, saving and writing of configuration dataThe service tool can be toggled between six different languages online. The unit is protectedfrom damage during transit and use via a rubber guard.Service software MATRIX.PCBased on the functions of the MATRIX.PDA service tool, the MATRIX.PC servicesoftware provides further comprehensive functions in the field of parameterization,commissioning and data recording of the <strong>GEA</strong> MATRIX controller system.The service software can be connected via the service interface that is integrated intoall control panels, controllers, global modules, the timer and the communicationmodules. A USB interface is required on the PC. The enclosed adaptor establishes thenecessary connection between the PC and the service interface.In addition to the functions of the MATRIX.PDA, the following main functions are alsoavailable:– Online display of module, status and network data– Recording and saving of temperature developments and switching states of theactuators with adjustable sample rate– Offline parameterization– Programming of inputs and outputs provided for this purpose(controllers, global modules)– Output of messages and network data– Parameterisation of controller and control panel functions– Input of sensor correction factorsPC system requirements:– PC with 233 MHz clock speed or higher– 20 MB of free hard drive space– Minimum screen resolution of 800x600 pixels– USB interface for CAN adaptorThe software can be run on the following operating systems:Windows 98 Second Edition; Windows 2000; Windows XPIn addition to the program CD, the installation instructions and interface module forconnection to the USB port of the PC are also provided.50 PR-2009-0015-GB • Subject to modifications • Status 10/2009


<strong>GEA</strong> <strong>MPower</strong>-<strong>Geko</strong> Fan Coil UnitProduct Type CodeUnit type code Controls package Valve codeG M 1 1 . U 0 W 3 . A 0 0 G 2 D 2 . 0 0 1 . B A V G M . R 3 1 6 R 2 2 5 . 1 LCooling/heatingHeating circuitSize1 = Size 12 = Size 23 = Size 34 = Size 4Capacity stage1 = Capacity stage 12 = Capacity stage 2Air flow functionU = Circulating airMedium related functionHeating only0W = Warm water pumpCooling onlyW0 = Chilled water pumpCooling or heatingWC = WWP - CWPCooling and heatingWarm= WWP - CWPwaterMedium connection *Ceiling3 = left4 = rightSpeed stagesTerminal box with terminal stripA = Speed 1, 2, 3B = Speed 2, 3, 4C = Speed 3, 4, 5E = Speed 1, 3, 5H = Speed 1, 2, 3, 4, 5Sheet steel electric switch box with terminalstrip or for integrated controlsK = Speed 1, 2, 3L = Speed 2, 3, 4M = Speed 3, 4, 5O = Speed 1, 3, 5R = Speed 1, 2, 3, 4, 5Controller type0 = Terminal box/Matrix 5002 = MATRIX 20003 = MATRIX 30004 = MATRIX 4000Controls package Nr.control panelA = MATRIX OP21CB = MATRIX OP30CC = MATRIX OP31CD = MATRIX OP44CE = MATRIX OP50CF = MATRIX OP51CN = MATRIX.IRP = CMS = 983 860Q = CMT = 983 861R = CET = MCR 2000S = MATRIX OP4CT = MATRIX OP5CU = MATRIX OP20CZ = without control panelUnit typeMaster unit, control panelA = Single/master unit, controlpanel suppliedC = Master unit without controlpanelD = Slave unit without controlpanelFunction typeR = 3-point 230 VT = 2-point 230 VN = 3-point 24 VQ = 2-point 24 VS = 0-10 V, 24 VC = 3-point 230 V + 2 contactsValve body2 = 2-way3 = 3-wayK vs -value03 = K vs 0,25 (R, N, S, C)04 = K vs 0,40 (R, N, S, C)06 = K vs 0,63 (R, N, S, C)10 = K vs 1,0 (R, N, S, C)16 = K vs 0,40 (R, N, S, C, T, Q)25 = K vs 2,5 (R, N, S, C)40 = K vs 4,0 (R, N, S, C, T, Q)Connection/shut-off0 = Inlet/outlet with external thread1 = Inlet/outlet with solder fitting2 = Inlet/outlet + ball trap with external thread3 = Inlet/outlet + ball trap with solder fitting4 = Inlet + ball trap/outlet + shut-off valve with externalthread5 = Inlet + ball trap/outlet + shut-off valve with solder fittingMedium connectionL = leftR = rightThermal contact0 = with integrated thermal contacts1 = with external (led out) thermal contactsCondensate pump0 = with condensate drain1 = with condensate pump **DesignG = Basic unit for modular designM = Compact unit with integrated discharge connectorFilter2 = G2 mat filter3 = G3 mat filter* Front connection side, facing discharge** Steel sheet electrical switch box necessaryPR-2009-0015-GB • Subject to modifications • Status 10/2009 51


Customer proximity, sales structuresReachable always and everywhere!ABBGBIHBYCHCZCZDD<strong>GEA</strong> KlimatechnikGmbH & Co KGA-4673 GaspoltshofenTel. +43 / 7735 / 8000-0<strong>GEA</strong> Happel Belgium N. V.B-1130 BrusselsTel. +32 / 2 / 2406161EVISS Ltd.BG-7000 RousseTel . +359 / 82 / 81000<strong>GEA</strong> KlimatechnikGmbH & Co KGRS-11070 Novi BeogradTel. +381 / 11 / 3193955<strong>GEA</strong> Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060ATC Klimatec Schweiz AGCH-3065 Bolligen-StationTel. +41 / 31 / 9171919<strong>GEA</strong> LVZ, a.s.CZ-46312 LiberecTel. +420 / 48 / 5225-111<strong>GEA</strong> Klimatizace spol. s r.o.CZ-46312 LiberecTel. +420 / 48 / 5225-303<strong>GEA</strong> HappelKlimatechnik GmbHD-44625 HerneTel. +49 / 2325 / 468-00<strong>GEA</strong> HappelWieland GmbHD-44625 HerneTel. +49 / 2325 / 468-754DDDKEESTFFFINGB<strong>GEA</strong> DelbagLufttechnik GmbHD-44625 HerneTel. +49 / 2325 / 468-700<strong>GEA</strong> Delbag-LuftfilterVertriebsgesellschaft mbHD-10709 BerlinTel. +49 / 30 / 43592-3<strong>GEA</strong> Klimateknik ApSDK-2610 RødovreTel . +45 / 38 / 887070<strong>GEA</strong> Air TreatmentMarketing Services Int.GmbH – oficina EspañaE-28036 MadridTel. +34 / 91 / 3837701<strong>GEA</strong> Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060<strong>GEA</strong> DelbagFiltration d l‘airF-77450 MontryTel. +33 / 1 / 60043355<strong>GEA</strong> Happel France sarlF-59436 Roncq CedexTel. +33 / 3 / 20689020OY TEKNOCALOR ABFIN-01300 VantaaTel. + 358 / 9 / 82546020<strong>GEA</strong> Denco Ltd.UK-HR4 8DS HerefordTel. +44 / 1432 / 277 277HHRIEISLLTLVMWENNL<strong>GEA</strong> Klimatechnika KftH-1037 BudapestTel. +36 / 1 / 4393200<strong>GEA</strong> Klima-rashladnatehnika d.o.o.HR-10000 ZagrebTel. +385 / 1 / 6064900Aspect Environmental Ltd.Ardee, Co. Louth IrelandTel. +353 / 41 / 6858983Rafn JenssonIS-110 ReykjavikTel. +354 / 56 / 780-30<strong>GEA</strong> Happel LuxembourgL-4940 BascharageTel. +352 / 26 / 502970<strong>GEA</strong> Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060<strong>GEA</strong> Klimatechnik UABLT-01141 VilniusTel. +370 / 5 / 2106060<strong>GEA</strong> KlimatechnikGmbH & Co KGRS-110 70 Novi BeogradTel. +381 / 11 / 3193955<strong>GEA</strong> Klimaprodukter ASN-0484 OsloTel. +47 / 220 / 27990<strong>GEA</strong> Happel Nederland B.V.NL-2909 LLCapelle a/d IjsselTel. +31 / 10 / 2350606PPLRORUSSSKSLOSRBTRUANónio, Lda.P-1269-090 LisboaTel. +351 / 21 / 3826160<strong>GEA</strong> Klimatyzacja Sp. z o.o.PL-54610 WroclawTel. +48 / 71 / 3737952<strong>GEA</strong> Klimatechnik s.r.l.RO-300222 TimisoaraTel. +40 / 356 / 423703<strong>GEA</strong> KlimatechnikGmbH & Co KGRU-105094 MoskvaTel. +7 / 495 / 9566674<strong>GEA</strong> EXOS Ventilation ABS-74528 EnköpingTel. +46 / 171 / 85530<strong>GEA</strong> Klimatizácia s.r.o.SK-83104 BratislavaTel. +421 / 7 / 44457917<strong>GEA</strong> KlimatizacijskaTehnika d.o.o.SI-1000 LjubljanaTel. +386 / 1 / 2573850<strong>GEA</strong> KlimatechnikGmbH & Co KGRS-11070 Novi BeogradTel. +381 / 11 / 3193955<strong>GEA</strong> ISISANTR-80700Balmumcu IstanbulTel. +90 / 212 / 2757171<strong>GEA</strong> Ukraina t.o.v.UA-01135 KyivTel. +38 / 044 / 4619356The complete addresses are available on theInternet under: www.gea-air-eco2nomy.com.moJOMMVJMMNRJd_=•=pìÄàÉÅí=íç=ãçÇáÑáÅ~íáçåëPR - xxxx -xxxx - xxx • Subject to modificationpí~íìë=NMLOMMV=•=`çéóêáÖÜí=db^=^áê=qêÉ~íãÉåíIssue xx/ xxxx • Copyright <strong>GEA</strong> Air Treatmentwww.gea-air-eco2nomy.com