Air conditioning of swimming pools with <strong>com</strong>fort units<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Air conditioning of swimming pools | Data & Facts<br />

<strong>GEA</strong> Heat Exchangers / HVAC Systems


Table of Contents<br />

Copyright note<br />

Disclosing, copying, distributing or taking any action in reliance on the contents of this document is strictly<br />

prohibited without express prior consent. Violations entail liability for any damages or other liability arising.<br />

All rights in relation to patents, utility patents or design patents are reserved.<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Air Recirculating Dehumidifier with Heat Pump, Type CAU<br />

Functional Description .......................................................................................... 3<br />

System and Controls Scheme .............................................................................. 3<br />

Components ......................................................................................................... 4<br />

Technical Data ..................................................................................................... 6<br />

Accessories .......................................................................................................... 6<br />

Air Mixing Dehumidifier with Heat Pump, Type CMU<br />

Functional Description ........................................................................................... 7<br />

System and Controls Scheme .............................................................................. 8<br />

Components ......................................................................................................... 8<br />

Technical Data ................................................................................................... 13<br />

Air Mixing Dehumidifier with Heat Pump, Type CAM<br />

Functional Description ........................................................................................ 14<br />

System and Controls Scheme ............................................................................ 15<br />

Components ....................................................................................................... 15<br />

Technical Data ................................................................................................... 20<br />

Air Mixing Dehumidifier with Heat Pump, Type CMP<br />

Functional Description ........................................................................................ 22<br />

System and Controls Scheme ............................................................................ 23<br />

Components ....................................................................................................... 23<br />

Technical Data ................................................................................................... 28<br />

Air Mixing Dehumidifier, Type CWR<br />

Functional Description ........................................................................................ 29<br />

System and Controls Scheme ............................................................................ 30<br />

Components........................................................................................................ 30<br />

Technical Data ................................................................................................... 34<br />

Air Mixing Dehumidifier, Type CWP<br />

Functional Description ........................................................................................ 36<br />

System and Controls Scheme ............................................................................ 37<br />

Komponenten ..................................................................................................... 37<br />

Technische Daten .............................................................................................. 42<br />

Compact <strong>GEA</strong> Fricostar Micro units<br />

Air Mixing Dehumidifier, Type CAC<br />

Functional Description ........................................................................................ 43<br />

System and Controls Scheme ............................................................................ 44<br />

Components ....................................................................................................... 44<br />

Technical Data ................................................................................................... 48<br />

Air Mixing Dehumidifier with Heat Pump Type CWC<br />

Functional Description ........................................................................................ 49<br />

System and Controls Scheme ............................................................................ 50<br />

Components ....................................................................................................... 50<br />

Technical Data ................................................................................................... 53<br />

Electric Integration, Overview of Cable Connections<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong> air mixing units .................................................................... 54<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong> air recirculating units ........................................................... 55<br />

Unit Selection as Relates to Water Surface<br />

Unit Model Range as Relates to Water Surface, Unit Type: Standard .............. 56<br />

Unit Model Range as Relates to Water Surface, Unit Type: Performance ........ 56<br />

Configuration Variants and Accessories<br />

Configuration Variants ........................................................................................ 57<br />

Accessories (Component Version only for DDC-Controller) .............................. 58<br />

2 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidifier with Air Recirculating and Heat Pump Function<br />

Type CAU<br />

Functional description of the unit<br />

The <strong>GEA</strong> <strong>CAIRfricostar</strong> CAU is mainly designed for private swimming pools and can<br />

be delivered in 4 sizes. The unit's function is to dehumidify and heat air in swimming<br />

pools in circulating air mode. The unit is supplied with a fully electronic control system<br />

that automatically regulates system functions.<br />

Operation mode with dehumidification demand<br />

In circulating air mode without dehumidification the air is recirculated in the swimming<br />

pool. The multifunction humidistat that is installed in the swimming pool switches the<br />

unit into dehumidification mode as soon as the humidity setpoint has been exceeded.<br />

At this point the fan is switched into speed 2 and the refrigeration circuit is activated.<br />

The dehumidification process is carried out until the setpoint is reached. After that the<br />

fan is switched into speed 1 and the circuit <strong>com</strong>pressor is stopped. Using an optional<br />

pool water condenser a certain amount of excess energy produced by the heat pump<br />

cycle can be fed back into swimming pool water or similar circuit system.<br />

Air recirculating dehumidifier CAU<br />

Supply air fan runs at high speed. The necessary transmission heat is provided by the reheater coil. Using<br />

an optional pool water condenser a certain amount of excess energy can be fed back into swimming<br />

pool water.<br />

System and controls scheme<br />

M<br />

M<br />

M<br />

M1<br />

M<br />

p<br />

P<br />

P<br />

M<br />

M<br />

p<br />

DI<br />

AI<br />

DO<br />

AO<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 3


Dehumidifier with Air Recirculating and Heat Pump Function<br />

Type CAU<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Components<br />

Casing:<br />

Heat pump for<br />

dehumidification:<br />

Indoor installation<br />

– 50 mm panels, inside and outside skins are painted; (corresponds to RAL 9002),<br />

the series includes casing frame and service door in casing panel thickness together<br />

with a full profile rubber gasket in EPDM quality. All outside and inside surfaces<br />

are <strong>com</strong>pletely smooth.<br />

– Leak tightness class G II according to VDI 3803. Thermal and sound bridges are<br />

minimized.<br />

– Non <strong>com</strong>bustible insulation (fire classification A1 according to DIN 4102; Ö-Norm<br />

B3800; CFC-free)<br />

– Heat transfer coefficient k = 0,57 W/m2 K<br />

– Sound insulation performance Rw = 44 dB according to DIN 52210/T4<br />

– Casing features according to EN1886<br />

– Filter bypass leakage F9<br />

– Leak tightness class according to prEN 1886 (10/2005) L1<br />

– Casing leakage B<br />

– Mechanical stability 1A<br />

– Thermal insulation T2<br />

– Thermal bridging factor TB2 (in risk areas)<br />

– Frame profiles AlMgSi 0,5<br />

– Flexible connector with potential equalisation, temperature resistant from -30 °C to<br />

+120 °C<br />

– Duct connection using 30 mm frame with 4 hole bolt connection<br />

– Interior installation parts for swimming pool mode with special corrosion protection<br />

– Direct evaporator according to VDI 6022: heat exchanger as Cu/Alu model for<br />

R 407c refrigerant, fins made of aluminium, frame elements made of AlMg3, pipes<br />

made of oxygen-free copper.<br />

– Condensate water tray in bottom panel for evaporator and heat recovery system,<br />

with a slope in the direction of condensate drain, made of stainless steel V4A powder<br />

coated, including drain tray, conform with VDI 6022<br />

– Air-cooled condenser according to VDI 6022: heat exchanger as Cu/Alu model for<br />

R 407c refrigerant, fins made of aluminium, frame elements made of AlMg3, pipes<br />

made of oxygen-free copper<br />

– Compressor unit: refrigeration circuit with a fully hermetic scroll <strong>com</strong>pressor<br />

– With optimized heat exchanger <strong>com</strong>bination for maximum COP values, mounted on<br />

anti-vibration mounts. Circuit includes filter drier, liquid collector, thermostatic<br />

expansion valve with MOP and external pressure equalisation, all necessary shutoff<br />

valves, monitoring and safety devices (pressostat, icing sensor, etc.)<br />

Droplet eliminator – Made of plastic with an aluminium frame at air velocities on supply and exhaust side<br />

exceeding 2,5 m/s is necessary<br />

Fan unit:<br />

<strong>GEA</strong> centrifugal fan „LESS ENERGY SYSTEM“<br />

– Optimized operating point, double side suction, coated surface model<br />

– Three phase motor, protection class IP55 , model type B3, <strong>com</strong>plete belt drive, easy<br />

service thanks to one bolt tensioning sled<br />

– Fan/motor unit mounted on anti-vibration mounts<br />

Filter for exhaust air: – Filter unit according to DIN<br />

– Including bag filter as of DIN/EN 779, synthetic fiber filter medium<br />

– All filters are fitted with a differential pressure switch for filter monitoring<br />

Heating section: – L.P.H.W. air heater, heat exchanger with copper pipes and drawn aluminium fins in<br />

aluminium frame AlMg3 (max. temp. 110°C, Pmax 16 bar) removable in accordance<br />

with VDI 6022<br />

4 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

<strong>GEA</strong> motor 3-way mixing<br />

valve:<br />

Control and regulation<br />

system<br />

The switch cabinet is<br />

supplied with the following<br />

main <strong>com</strong>ponents:<br />

Dehumidifier with Air Recirculating and Heat Pump Function<br />

Type CAU<br />

– Supplied loose for air reheating coil including actuator 230 V with an automatic step<br />

measurement system for fine adjustment of water flow rate<br />

– Supplied loose, installation by others<br />

– Consists of a separate switch cabinet for mounting on units with all necessary <strong>com</strong>ponents<br />

for control functions, wired according to VDE specifications.<br />

– Electrical connection (via plug or screw terminals) between control cabinet and unit<br />

using factory prepared and fully assembled lines.<br />

– Mains voltage for control of mixing valve and reheater pump (including controls)<br />

– Possible output for pool water pump<br />

– The switch cabinet is supplied loose, including fixing material for mounting on the<br />

unit<br />

– All electronic control and regulation <strong>com</strong>ponents can be easily replaced<br />

– Main isolating switch for all pole shut-down of the electrical unit<br />

– Group fuses for fan and <strong>com</strong>pressor<br />

Safety fuse for pump reheater circuit 230V<br />

Control fuse and control voltage supply unit 24V (safety extra-low voltage or SELV)<br />

Control of supply air fan using motor full protection device via PTC<br />

temperature sensor and electronic motor tripping device<br />

– Control of <strong>com</strong>pressor motor with thermal motor protection and interlock for safety<br />

chain and control card, control of icing protection, low and high pressure.<br />

– Electronic control card for <strong>com</strong>pressor regulation with minimum run and standstill<br />

time as clock protection, service reset button, status messages for timer control and<br />

light diode for faults of the refrigeration circuit.<br />

– Humidistat with remote control for mounting in the swimming pool, with status and<br />

fault lamp and operation switch.<br />

Operation with safety extra-low voltage.<br />

Setpoint setting 30-90 % r.h.<br />

Colour: white<br />

On-wall mounting<br />

Dimensions: W/H/D 145/80/30 (mm) supplied loose<br />

– Electronic three point PI-controller for exhaust air temperature control with setpoint<br />

setting on the switch cabinet including installed NTC exhaust air temperature sensor.<br />

– Output 230V for modulating 3-way valve motor in reheater circuit<br />

– If necessary <strong>GEA</strong> pool water temperature control for controlling pool water pump<br />

consisting of an integrated immersion thermostat, interlocking with <strong>com</strong>pressor<br />

operation and output for pool water pump 230V (only control output max. 2A) and<br />

time control for registration of actual values (only in <strong>com</strong>bination with pool water<br />

condenser)<br />

– Output for collective error message signal (floating change-over contact)<br />

– Control possibility of an exhaust fan by others, 2-speed, 230 V/max. 150 W<br />

Air recirculating dehumidifier CAU<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 5


Dehumidifier with Air Recirculating and Heat Pump Function<br />

Type CAU<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Technical data<br />

Unit series CAU…SU.. (standard model, maximum air velocity for supply and exhaust air approx. 2,8 m/s),<br />

fans in casing<br />

Type Unit dimensions Air volume flow<br />

Dehumidification<br />

capacity<br />

Heating capacity<br />

Pressure<br />

drop<br />

Motor rated power/<br />

current<br />

Current<br />

consumption<br />

CAU_SU<br />

Total width<br />

Total height<br />

Total length<br />

Minimum<br />

Maximum<br />

Rated (with dehumidification)<br />

Rated (with ventilation)<br />

Recirculatied air mode 1)<br />

[mm] [m3/h] [kg/h] [kW] [Pa] [kW/A] [A]<br />

015 760 1120 1680 750 750 500 3.1 7.0 4.6 2.3 5.9 400 0.4/1.4 1.5/2.9 4.3<br />

015 760 1120 1680 1842 1842 1228 1.4 8.0 6.0 2.0 9.4 400 1.7/3.8 1.5/2.9 6.7<br />

025 760 1360 1800 1842 1842 1228 4.2 13.0 10.6 2.5 11.1 400 0.8/2.1 2.4/4.6 6.7<br />

025 760 1360 1800 2755 2755 1836 3.3 13.8 11.3 2.1 14.1 400 1.7/3.8 2.4/4.6 8.4<br />

030 760 1360 1800 2755 2755 1836 4.3 16.2 13.3 2.6 14.1 400 1.7/3.8 2.8/5.5 9.3<br />

030 760 1360 1880 3355 3355 2236 3.6 16.6 13.9 2.5 15.8 400 3.0/6.7 2.8/5.5 12.2<br />

037 760 1600 1720 3354 3354 2236 4.9 19.8 16.3 3.3 18.3 400 1.7/3.8 3.7/7.5 11.3<br />

037 760 1600 1800 4129 4129 2752 3.9 20.1 17.0 3.1 20.5 400 3.0/6.7 3.7/7.5 14.2<br />

Air condenser, with inactive<br />

pool water condenser<br />

Air condenser, with active<br />

pool water condenser<br />

Pool water condenser (accessory)<br />

Reheater 2)<br />

Total external pressure<br />

Supply air fan, high speed,<br />

at rated volume flow<br />

Compressor, without<br />

pool water condenser<br />

Unit total 3)<br />

Tab. 1: Technical data <strong>CAIRfricostar</strong> CAU<br />

1) Swimming pool air condition 30 °C/54 %r.h.;<br />

2) Inlet/outlet temperature 70 °C/50 °C; maximum heating capacity; 2 rows<br />

3) plus controls/regulation/pumps etc.<br />

(All data are approximate values and summarize most important features.<br />

Subject to modifications. Exact data are available in the current Lplus design software)<br />

Accessories<br />

Valve final position switch for on demand controls of reheater pump 9349W20<br />

Pool water pump, self suction; industrial quality<br />

F8ZBP<br />

6 PR-2008-0327-GB • Subject to modifications • Status 05/2009


Option<br />

Option<br />

H<br />

Option<br />

H<br />

Option<br />

H<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidification unit with air mixing and heat pump function<br />

Type CMU<br />

Functional description of the unit<br />

The <strong>GEA</strong> <strong>CAIRfricostar</strong> CMU is designed for private and small public swimming pools.<br />

The series is available in 6 sizes. The unit's function is to dehumidify and heat air in<br />

swimming pools in air mixing mode. The unit is delivered with a DDC controls which<br />

regulates all functions of the system on a fully automated basis.<br />

When in idle mode without dehumidification the air is recirculated in the swimming pool.<br />

When the humidity setpoint has been exceeded the unit switches into dehumidification<br />

mode. At this point the supply air fan is switched into speed 2 and the exhaust air fan<br />

maintains air circulation at speed 1. The refrigeration unit is activated in order to start<br />

dehumidification. Using the bypass damper a certain part of return air is mixed without<br />

further treatment with dehumidified air that has passed through the refrigeration cycle.<br />

The dehumidification stage continues until the actual humidity value lies below that of<br />

the humidity setpoint. After that the fan is switched back into previous speed and the<br />

refrigeration cycle is stopped.<br />

When in active hours swimming pool mode the fresh and exhaust air dampers are<br />

opened, the bypass damper is closed. The dehumidification takes place via the activation<br />

of the refrigeration cycle with both fans switched into speed 2.<br />

Using an optional pool water condenser a certain amount of excess energy produced<br />

by the refrigeration cycle can be fed back into swimming pool water.<br />

Air mixing dehumidifier CMU<br />

Sample selection of operating modes:<br />

Idle mode without dehumidification<br />

demand<br />

Idle mode with dehumidification<br />

demand<br />

Active hours operation mode with<br />

dehumidification demand<br />

28°C<br />

H<br />

Bypass damper mode, exhaust air fan is deactivated,<br />

supply air fan runs at low speed.<br />

Bypass damper mode, exhaust air fan runs at<br />

low speed, supply air fan runs at high speed.<br />

The reheater provides the missing residual<br />

heat supply.<br />

Air mixing operation according to VDI, exhaust<br />

and supply air fans run at high speed.<br />

Compressor is switched on. The reheater<br />

provides the missing residual heat supply.<br />

Using a pool water condenser a certain<br />

amount of excess energy can be fed back<br />

into swimming pool water.<br />

Transition and summer mode with/without<br />

dehumidification demand<br />

Summer mode inactive period „free night cooling“<br />

In case of overheating of the swimming pool and high outdoor temperatures<br />

the heat pump is blocked. The unit operates for ventilation<br />

and dehumidification in air mixing or only outdoor/exhaust air mode.<br />

The fans run at high speed. In case of an optional bypass of the heat<br />

recovery system the latter is not used thanks to a damper system.<br />

If the swimming pool is overheated during the night time or idle period<br />

the unit ventilates only in outdoor/exhaust air mode. The fans run at<br />

high speed and provide cooling of the swimming pool to reach the<br />

setpoint temperature.<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 7


.<br />

Dehumidification unit with air mixing and heat pump function<br />

Type CMU<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

System and controls scheme<br />

M<br />

M<br />

M<br />

M1<br />

M<br />

M<br />

p<br />

M<br />

M<br />

MVS<br />

M2<br />

M<br />

M<br />

P<br />

P<br />

M<br />

M<br />

MVS<br />

p<br />

DI<br />

AI<br />

DO<br />

AO<br />

Components<br />

Casing:<br />

Indoor installation<br />

– 50 mm panels, inside and outside skins are painted; (corresponds to RAL 9002),<br />

the series includes casing frame and service door in casing panel thickness together<br />

with a full profile rubber gasket in EPDM quality. All outside and inside surfaces<br />

are <strong>com</strong>pletely smooth.<br />

– Leak tightness class G II according to VDI 3803. Thermal and sound bridges are<br />

minimized.<br />

– Non <strong>com</strong>bustible insulation (fire classification A1 according to DIN 4102; Ö-Norm<br />

B3800; CFC-free)<br />

– Heat transfer coefficient k = 0,57 W/m2 K<br />

– Sound insulation performance Rw = 44 dB according to DIN 52210/T4<br />

– Casing features according to EN1886<br />

– Filter bypass leakage F9<br />

– Leak tightness class according to prEN 1886 (10/2005) L1<br />

– Casing leakage B<br />

– Mechanical stability 1A<br />

– Thermal insulation T2<br />

– Thermal bridging factor TB2 (in risk areas)<br />

– Frame profiles AlMgSi 0,5<br />

– Flexible connection with potential equalisation, temperature resistant from -30 °C to<br />

120 °C<br />

– Duct connection using 30 mm frame with 4 hole bolt connection<br />

– Interior installation parts for swimming pool mode with special corrosion protection<br />

8 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidification unit with air mixing and heat pump function<br />

Type CMU<br />

Heat pump for<br />

dehumidification:<br />

– Direct evaporator according to VDI 6022: heat exchanger as Cu/Alu model for R<br />

407c refrigerant, fins made of aluminium, frame elements made of AlMg3, pipes<br />

made of oxygen-free copper.<br />

– Condensate water tray in bottom panel for evaporator and heat recovery system,<br />

with a slope in the direction of condensate drain, made of stainless steel V4A powder<br />

coated, including drain tray, conform with VDI 6022<br />

– Air-cooled condenser according to VDI 6022: heat exchanger as Cu/Alu model for<br />

R 407c refrigerant, fins made of aluminium, frame elements made of AlMg3, pipes<br />

made of oxygen-free copper<br />

– Compressor unit: refrigeration circuit with a fully hermetic scroll <strong>com</strong>pressor<br />

– With optimized heat exchanger <strong>com</strong>bination for maximum COP values, mounted on<br />

anti-vibration mounts, circuit includes filter drier, liquid collector, thermostatic<br />

expansion valve with MOP (maximum operating pressure) and external pressure<br />

equalisation, all necessary shut-off valves, monitoring and safety devices<br />

(pressostat, icing sensor, etc.)<br />

Droplet eliminator – Made of plastic with an aluminium frame at air velocities on supply and exhaust side<br />

exceeding 2,5 m/s is necessary<br />

Air mixing dehumidifier CMU<br />

Fan unit:<br />

Alternative fan unit:<br />

<strong>GEA</strong> centrifugal fan „LESS ENERGY SYSTEM“<br />

– Optimized operating point, double side suction, coated surface model<br />

– Three phase motor, protection class IP55 , model type B3, <strong>com</strong>plete belt drive, easy<br />

service thanks to one bolt tensioning sled<br />

– Fan/motor unit mounted on anti-vibration mounts<br />

<strong>GEA</strong> „OPTIVENT“ high performance fan impellers<br />

– Surface coated one side suction with backward curved blades that are directly connected<br />

to motor shaft; performance optimized three-phase motor, B3 model type,<br />

protection type IP55, insulation class F adjusted for operation with a frequency converter.<br />

Fan and motor unit including coated intake nozzle mounted on buckling<br />

resistant and coated base construction, motor and fan have sound attenuated<br />

bearings.<br />

– Continuous measurement of pressure effects<br />

– Statically and dynamically balanced according to DIN ISO 1940, part 1, G2,5).<br />

Continuous monitoring of operation using DDC. Frequency converter for each<br />

motor installed in or mounted on the unit, control via <strong>GEA</strong> DDC with a separate analogue<br />

signal for both motors. Frequency converters are adjusted and set for both<br />

motors. Limit values for motor current and fan speed are set by the programme<br />

– Resonance frequency band/fade out set by factory<br />

– Automatic energy optimization for optimal energy use and efficiency rate<br />

– Multiple motor operation is possible<br />

– Voltage intermediate circuit converter without reduction of capacity<br />

– Continuous speed control<br />

– Operating hours counter<br />

– Min. and max. speed limitation, automatic ramp curve function UP/DOWN<br />

– Automatic motor adjustment<br />

– Motor tracing switch<br />

– DC break<br />

– Variable clock frequency<br />

– Motor protection<br />

– Short circuit and short circuit to earth safe<br />

– Under and over current protection<br />

– Phase fault monitoring<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 9


Dehumidification unit with air mixing and heat pump function<br />

Type CMU<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

– Motor coils for reducing speed of voltage rise du/dt (delta voltage/delta time)<br />

– Numerical display for queries and entering of different indicators on operating status:<br />

control setpoint, motor frequency, actual value and setpoint, motor current,<br />

motor torque and capacity, intermediate circuit voltage, thermal motor load, thermal<br />

frequency converter load, control and programmable display with copy function,<br />

production according to ISO 9001, CE Label, net and main shaft protection according<br />

to VDE 0160, radio interference shielding, codes and regulations on electromagnetic<br />

<strong>com</strong>patibility conform with EN 55011 Kl.B-1; EN 50082-2, electric<br />

insulation of control and power <strong>com</strong>ponents according to VDE 0106/0160 (the use<br />

of earth leakage circuit breaker / fuse with frequency converters NOT possible!),<br />

volume flow measuring device via ring measuring line and pressure measuring<br />

point in fan. Calculation and evaluation of volume flow via the <strong>GEA</strong> DDC. Continuous<br />

safety monitoring via safety chain in the unit. Display and settings via <strong>GEA</strong><br />

DDC.<br />

Air damper system: – Dampers with sealing lips, leakage volume flow 20 m3/h m2 (dp=100 Pa), for circulating<br />

air/bypass, for fresh and exhaust air. Circulating and fresh air rate 0-100%.<br />

– Coated Almg3 damper blades with flow efficient profile, operate in opposite directions.<br />

Driven by double sided, anti-static plastic gears PA6 as fiberglass reinforced<br />

model (resistant to chemicals) including special actuator for each damper<br />

– Control of the individual actuators using continuous DDC signals<br />

Filter for fresh and<br />

exhaust air:<br />

– Filter units conform with VDI 6022<br />

– Including bag filter as of DIN/EN 779, synthetic fiber filter medium<br />

– All filters are fitted with a differential pressure switch for filter monitoring via the DDC<br />

Heating section: – L.P.H.W. air heater, heat exchanger with copper pipes and drawn aluminium fins in<br />

aluminium frame AlMg3 (max. temp. 110°C, Pmax 16 bar) removable in accordance<br />

with VDI 6022;<br />

<strong>GEA</strong> motor 3-way mixing<br />

valve:<br />

– For air reheater, supplied loose including actuator 0-10 V with an automatic step<br />

measurement system for fine adjustment of water flow rate.<br />

– Supplied loose, installation by others<br />

Control and<br />

regulation<br />

system<br />

– Consists of a separate switch cabinet for mounting on units or separate installation<br />

(depending in unit size), with all necessary <strong>com</strong>ponents for control functions, wired<br />

according to VDE specifications. IP55 electrical connection (via plug or screw terminals)<br />

between control cabinet and unit using factory prepared and fully assembled<br />

lines. Electrical installation for voltage supply, valve mixing control, reheater<br />

pump, if necessary external sensor of the pool water pump and possibly other functions<br />

like remote control inputs by others. The cabinet is supplied loose depending<br />

on the unit size as a stand alone cabinet or for mounting on the unit.<br />

10 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidification unit with air mixing and heat pump function<br />

Type CMU<br />

The switch cabinet is<br />

supplied with the following<br />

main <strong>com</strong>ponents:<br />

– Main isolating switch for all pole shut-down of the electrical unit, lockable<br />

– Group fuses for fan and <strong>com</strong>pressor<br />

– Fuses for reheater and PWC pump<br />

230V/N/PE/50Hz (types 015-083)<br />

3 X 400V/NPE/50Hz (types 100-320)<br />

(if necessary - motor protection by others)<br />

– Control fuses, control transformer 230 V and control voltage supply unit 24V DC for<br />

the digital control<br />

– Control fuse and control voltage supply unit 24V AC for actuators<br />

– Automatic phase controller (option)<br />

– Indoor installation, frost free<br />

Digital control: – Modular automation station built into switch cabinet with deletion-proof software<br />

modules and digital and analogue inputs and outputs, equipped with all control<br />

functions for swimming pool dehumidifier, consisting of:<br />

– Control unit with 32 bit processor in network based, interdisciplinary, free programmable<br />

automation system<br />

– Watchdog function, data buffering (FLASH-ROM), hardware clock<br />

– Interfaces:<br />

1 x CAN (Controller Area Network) as central bus between control unit and I/O<br />

modules;<br />

1 x LIN (Local Interconnect Network) for auxiliary module monitoring and configuration<br />

functions;<br />

1 x CAN for external connection;<br />

2 x RS232/RS485, one RS232 has modem function;<br />

Optional - Ethernet; USB plug;<br />

Optional - various <strong>com</strong>munication functions can be carried out (e. g: OPC; LON;<br />

MODBUS; OSPA; BACnet®) As BACnet®-Building Controller (B-BC) the<br />

system can cost-efficiently intgerate or be integrated in any BACnet®<br />

third system.<br />

– In and output modules with an integrated microcontroller and memory for recording<br />

a programme specifically designed for the relevant module, status display for<br />

every input or output with CAN provided via top hat rail bus plug.<br />

– Comfortable intelligent control terminal for supporting display, control buttons and<br />

data transfer, installed in the door of the switch cabinet.<br />

– Alufront panel with front film<br />

– Keyboard connection via plug connector<br />

– Front side protection type IP 65<br />

– LCD-Display with 8 lines each with 40 symbols as clear text display, monochrome<br />

– 6 function buttons<br />

– Colour background lighting, adjustable, automatic lighting activation<br />

– Adjustable LCD contrast<br />

– System bus CAN<br />

– Alternative (option): as before, but:<br />

– with <strong>com</strong>fortable touch control terminal<br />

– LCD display with 16 colours<br />

– Graphical resolution 320 x 240 Pixel<br />

Air mixing dehumidifier CMU<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 11


Dehumidification unit with air mixing and heat pump function<br />

Type CMU<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Control and regulation<br />

functions:<br />

– Status and fault signals in clear text<br />

– Indication of all status and control parameters<br />

– Stepwise access authorization using code<br />

– Integrated clock timer<br />

– Automatic summer / winter time switch-over, activation of weekly programmes, holiday<br />

and special day programmes<br />

– Log for registration of faults with date and time<br />

– Operating hours counter, total operation and maintenance intervals<br />

– Data logging function for most important parameters, can be downloaded<br />

– Separate controls for supply and exhaust air fan motors<br />

– Air volume adjustment and display in m³/h, including monitoring for units with frequency<br />

converters<br />

– Fan motor monitoring using PTC resistor and motor protection relay<br />

– Filter monitoring<br />

– Compressor control (heat pump) with minimum run / standstill time<br />

– Regulation of air mixing dampers with selectable minimum fresh air rate and maximum<br />

limitation, automatic control depending on conditions of fresh air and swimming<br />

pool air<br />

– Control sequence with energy recovery, heater, <strong>com</strong>pressor (heat pump), bypass<br />

damper and air mixing damper system<br />

– Exhaust air temperature cascade control with min./max. limitation of supply air temperature<br />

– Cooling with outside air (night cooling)<br />

– Reheater-heat pump consumption control with blockage protection functions<br />

– Continuous humidity control<br />

– On demand - controls for automatic pool water pump with block up protection<br />

– Automatic switch-over between active/non-active hours operation<br />

– Continuous inactive/idle mode possible<br />

– Different languages can be selected<br />

– Commissioning function for air dampers<br />

– Inputs: external emergency switch off (e.g. fire protection damper or chlorine gas<br />

alarm)<br />

– Motor monitoring for NE pump can be switched, if required motor protection<br />

by others<br />

– Motor monitoring for pool water pump can be switched, if required motor protection<br />

by others<br />

– The necessary sensors and actuators are built into the unit or, if necessary, supplied<br />

loose with subsequent installation by others<br />

12 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidification unit with air mixing and heat pump function<br />

Type CMU<br />

Technical data<br />

Unit series CMU…SU. (standard model, maximum air velocity for supply and exhaust air approx. 2,8 m/s),<br />

plug fans, frequency converters<br />

Type Unit dimensions Air volume flow<br />

Dehumidification<br />

capacity<br />

Heating capacity<br />

Pressure<br />

drop Motor rated power/current Current<br />

consumption<br />

CMU_SU<br />

Total width<br />

Total height<br />

Total length<br />

Minimum<br />

Maximum<br />

Rated (with dehumidification)<br />

Rated (with ventilation)<br />

Active hours more (30% fresh air)/<br />

idle mode (circulating air) / VDI 2089 1)<br />

Air condenser, with inactive<br />

pool water condenser<br />

[mm] [m3/h] [kg/h] [kW] [Pa] [kW/A] [A]<br />

015 760 1120 2600 750 1843 1000 667 5/2/6 7.0 5.6 1.6 10.6 300 0.6/1.4 0.6/1.4 1.3/2.5 5.3<br />

025 760 1360 2700 1842 2756 2000 1333 10/4/13 13.0 11.5 1.5 11.7 300 0.8/1.7 0.8/1.7 2.1/4.3 7.7<br />

030 760 1360 2700 2755 3355 3000 2000 14/4/19 16.6 14.8 1.6 14.8 300 1.1/2.5 0.8/1.7 2.5/5.2 9.4<br />

037 760 1600 2740 3354 4129 4000 2667 18/5/25 21.0 18.1 2.1 20.2 300 1.5/3.4 1.1/2.5 3.4/7.1 13.0<br />

045 1080 1360 2760 4128 5032 5000 3333 21/4/32 24.2 20.2 2.1 36.0 300 2.2/4.7 2.2/4.7 3.3/7.0 16.4<br />

055 1080 1600 2800 5031 6193 6000 4000 26/6/38 30.0 26.3 2.6 46.4 300 2.2/4.7 1.5/3.4 4.2/8.9 17.0<br />

Air condenser, with active<br />

pool water condenser<br />

Pool water condenser (accessory)<br />

Reheater 2)<br />

Ext. fresh/supply air;<br />

exhaust/return air; each<br />

Supply air fan, high speed,<br />

at rated volume flow<br />

Exhaust air fan, high speed,<br />

at rated volume flow<br />

Compressor, without pool<br />

water condenser<br />

Unit total 3)<br />

Air mixing dehumidifier CMU<br />

Tab. 2: Technical data <strong>CAIRfricostar</strong> CMU_SU<br />

1) Swimming pool air condition 30 °C/54 %r.h.; Outdoor air condition 5 °C/85 %r.h.<br />

2) Inlet/outlet temperature 70 °C/50 °C; maximum heating capacity; 2 rows<br />

3) plus controls/regulation/pumps etc.<br />

(All data are approximate values and summarize most important features.<br />

Subject to modifications. Exact data are available in the current Lplus design software)<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 13


E<br />

A<br />

E<br />

Kompress or<br />

A<br />

ECOSTATPower Tube2<br />

E<br />

A<br />

E<br />

A<br />

Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CAM<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Functional description of the unit<br />

The <strong>GEA</strong> <strong>CAIRfricostar</strong> CAM is designed for various kinds of private and public swimming<br />

pools. The series can be supplied with air volume capacity between 750 up to<br />

45.000 m³/h. The unit's function is to dehumidify and heat air in swimming pools in air<br />

mixing mode. Together with the refrigeration unit (heat pump) this unit type is additionally<br />

equipped with an efficient heat recovery system. The unit is delivered with a DDC<br />

controls which regulates all functions of the system on a fully automated basis.<br />

Sample selection of operation mode:<br />

When in idle mode without dehumidification the air is recirculated in the swimming pool.<br />

When the humidity setpoint has been exceeded the unit switches into dehumidification<br />

mode. At this point the supply air fan is switched into speed 2 and the exhaust air fan<br />

maintains air circulation at speed 1. The refrigeration unit is activated in order to start<br />

dehumidification. Using the bypass damper a certain part of return air is mixed without<br />

further treatment with dehumidified air that has passed through the refrigeration cycle.<br />

The dehumidification stage continues until the actual humidity value is reduced below<br />

that of the humidity setpoint. After that the fan is switched back into previous speed and<br />

the refrigeration cycle is stopped.<br />

When in active hours swimming pool mode the fresh and exhaust air dampers are<br />

opened, the bypass damper is closed. The dehumidification takes place via the activation<br />

of the refrigeration cycle with both fans switched into speed 2.<br />

Using an optional pool water condenser a certain amount of excess energy produced<br />

by the refrigeration cycle can be fed back into swimming pool water.<br />

Idle mode without dehumidification<br />

demand<br />

Idle mode with dehumidification<br />

request<br />

Active hours swimming pool mode<br />

with humidification request and pool<br />

water condenser<br />

+<br />

+<br />

+<br />

+ +<br />

+<br />

+ +<br />

-<br />

-<br />

-<br />

-<br />

Bypass damper mode, exhaust air fan is deactivated,<br />

supply air fan runs at low speed.<br />

Bypass damper mode, exhaust air fan runs at<br />

low speed, supply air fan runs at large speed.<br />

Compressor is switched on. The reheater<br />

provides the missing residual heat supply.<br />

Air mixing operation according to VDI, exhaust<br />

and supply air fans run at high speed.<br />

Compressor is switched on. The reheater<br />

provides the missing residual heat supply.<br />

Using a pool water condenser a certain<br />

amount of excess energy can be fed back<br />

into swimming pool water.<br />

Transition and summer mode with/w/o dehumidification<br />

Summer mode inactive period „free night cooling“<br />

+<br />

+ +<br />

+<br />

+<br />

+ +<br />

+<br />

-<br />

-<br />

-<br />

-<br />

In case of overheating of the swimming pool and high outdoor temperatures<br />

the heat pump is blocked. The unit ventilates and dehumidifies<br />

in air mixing or only outdoor/exhaust air mode. The fans run at<br />

high speed. In case of an optional bypass of the heat recovery system<br />

the latter is not used thanks to a damper system and at the same<br />

time the air volume flow is increased ("free night cooling“ function).<br />

If the swimming pool is overheated during the night time or idle period<br />

the unit ventilates only in outdoor/exhaust air mode. The fans run at<br />

high speed and provide cooling of the swimming pool to reach the<br />

setpoint temperature. In case of an optimal bypass of the heat recovery<br />

system the heat recovery is not used thanks to a damper system<br />

and at the same time the air volume flow is increased.<br />

14 PR-2008-0327-GB • Subject to modifications • Status 05/2009


.<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CAM<br />

System and controls scheme<br />

M<br />

M<br />

M<br />

M<br />

M5<br />

M1<br />

M<br />

Ecostat<br />

L-Kondensator<br />

NE<br />

B26<br />

B2<br />

M<br />

p<br />

M<br />

Y1<br />

M<br />

MVS<br />

Ecostat<br />

M<br />

M<br />

P<br />

P<br />

M<br />

M<br />

MVS<br />

p<br />

Components<br />

Casing:<br />

DI<br />

AI<br />

DO<br />

AO<br />

Indoor installation<br />

– 50 mm panels, inside and outside skins are painted; (corresponds to RAL 9002),<br />

the series includes casing frame and service door in casing panel thickness together<br />

with a full profile rubber gasket in EPDM quality. All outside and inside surfaces<br />

are <strong>com</strong>pletely smooth.<br />

– Leak tightness class G II according to VDI 3803. Thermal and sound bridges are<br />

minimized.<br />

– Non <strong>com</strong>bustible insulation (fire classification A1 according to DIN 4102; Ö-Norm<br />

B3800; CFC-free)<br />

– Heat transfer coefficient k = 0,57 W/m2 K<br />

– Sound insulation performance Rw = 44 dB according to DIN 52210/T4<br />

– Casing features according to EN1886<br />

– Filter bypass leakage F9<br />

– Leak tightness class according to prEN 1886 (10/2005) L1<br />

– Casing leakage B<br />

– Mechanical stability 1A<br />

– Thermal insulation T2<br />

– Thermal bridging factor TB2 (in risk areas)<br />

– Frame profiles AlMgSi 0,5<br />

– Flexible connector with potential equalisation, temperature resistant from -30 °C to<br />

+120 °C<br />

– Duct connection using 30 mm frame with 4 hole bolt connection<br />

– Interior installation parts for swimming pool mode with special corrosion protection<br />

Air mixing dehumidifier CAM<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 15


Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CAM<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Heat pump for<br />

dehumidification:<br />

– Direct evaporator according to VDI 6022: heat exchanger as Cu/Alu model for<br />

R 407c refrigerant, fins made of aluminium, frame elements made of AlMg3, pipes<br />

made of oxygen-free copper.<br />

– Condensate water tray in bottom panel for evaporator and heat recovery system,<br />

with a slope in the direction of condensate drain, made of stainless steel V4A powder<br />

coated, including drain tray, conform with VDI 6022<br />

– Air-cooled condenser according to VDI 6022: heat exchanger as Cu/Alu model for<br />

R 407c refrigerant, fins made of aluminium, frame elements made of AlMg3, pipes<br />

made of oxygen-free copper<br />

– Compressor unit: refrigeration circuit with a fully hermetic scroll <strong>com</strong>pressor<br />

– With optimized heat exchanger <strong>com</strong>bination for maximum COP values, mounted on<br />

anti-vibration mounts, circuit includes filter drier, liquid collector, thermostatic<br />

expansion valve with MOP and external pressure equalisation, all necessary shutoff<br />

valves, monitoring and safety devices (pressostat, icing sensor, etc.)<br />

Droplet eliminator – Made of plastic with an aluminium frame at air velocities on supply and exhaust side<br />

exceeding 2,5 m/s is necessary<br />

Fan unit:<br />

Alternative fan unit:<br />

<strong>GEA</strong> centrifugal fan „LESS ENERGY SYSTEM“<br />

– Optimized operating point, double inlet double width fan, coated surface model<br />

– Three phase motor, protection class IP55 , model type B3, <strong>com</strong>plete belt drive, easy<br />

service thanks to one bolt tensioning sled<br />

– Fan/motor unit mounted on anti-vibration mounts<br />

<strong>GEA</strong> „OPTIVENT“ high performance fan impellers<br />

– Surface coated one side suction with backward curved blades that are directly connected<br />

to motor shaft; performance optimized three-phase motor, B3 model type,<br />

protection type IP55, insulation class F adjusted for operation with a frequency converter.<br />

Fan and motor unit including coated intake nozzle mounted on buckling<br />

resistant and coated base construction, motor and fan have sound attenuated<br />

bearings<br />

– Continuous measurement of pressure effects<br />

– Statically and dynamically balanced according to DIN ISO 1940, part 1, G2,5). Continuous<br />

monitoring of operation using DDC. Frequency converter for each motor<br />

installed in or mounted on the unit, control via <strong>GEA</strong> DDC with a separate analogue<br />

signal for both motors. Frequency converters are adjusted and set for both motors.<br />

Limit values for motor current and fan speed are set by the programme<br />

– Resonance frequency band/fade out set by factory<br />

– Automatic energy optimization for optimal energy use and efficiency rate<br />

– Multiple motor operation is possible<br />

– Voltage intermediate circuit converter without reduction of capacity<br />

– Continuous speed control<br />

– Operating hours counter<br />

– Min. and max. speed limitation, automatic ramp curve function UP/DOWN<br />

– Automatic motor adjustment<br />

– Motor tracing switch<br />

– DC break<br />

– Variable clock frequency<br />

– Motor protection<br />

– Short circuit and short circuit to earth safe<br />

– Under and over current protection<br />

– Phase fault monitoring<br />

16 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CAM<br />

– Motor coils for reducing speed of voltage rise du/dt (delta voltage/delta time)<br />

– Numerical display for queries and entering of different indicators on operating status:<br />

control setpoint, motor frequency, actual value and setpoint, motor current,<br />

motor torque and capacity, intermediate circuit voltage, thermal motor load, thermal<br />

frequency converter load, control and programmable display with copy function,<br />

production according to ISO 9001, CE Label, net and main shaft protection according<br />

to VDE 0160, radio interference shielding, codes and regulations on electromagnetic<br />

<strong>com</strong>patibility conform with EN 55011 Kl.B-1; EN 50082-2, electric<br />

insulation of control and power <strong>com</strong>ponents according to VDE 0106/0160 (the use<br />

of earth leakage circuit breaker / fuse with frequency converters NOT possible!),<br />

volume flow measuring device via ring measuring line and pressure measuring<br />

point in fan.<br />

Calculation and evaluation of volume flow via the <strong>GEA</strong> DDC. The settings for entire<br />

unit are done at the factory. Continuous safety monitoring via safety chain in the<br />

unit. Display and settings via <strong>GEA</strong> DDC.<br />

Air damper system – Dampers with sealing lips, leakage volume flow 20 m3/h m2 (dp=100 Pa), for circulating<br />

air/bypass, for fresh and exhaust air. Circulating and fresh air rate 0-100%<br />

– Coated Almg3 damper blades with flow efficient profile, operate in opposite directions.<br />

Driven by double sided, anti-static plastic gears PA6 as fiberglass reinforced<br />

model (resistant to chemicals) including special actuator for each damper<br />

– Control of the individual actuators using continuous DDC signals<br />

Filter for fresh and<br />

exhaust air:<br />

– Filter units conform with VDI 6022<br />

– Including bag filter as of DIN/EN 779, synthetic fiber filter medium<br />

– All filters are fitted with a differential pressure switch for filter-monitoring via the<br />

DDC<br />

Air mixing dehumidifier CAM<br />

Heat recovery system: <strong>GEA</strong> „ECOSTAT2 POWER TUBE“:<br />

– Recuperative heat recovery using <strong>GEA</strong> heat pipe technology, heat exchanger<br />

made of Cu/Al. Aluminium fins, frame elements made of AlMg3, tubes made of oxygen-free<br />

copper charged with R134a CFC-free refrigerant for energy transfer.<br />

– Non-<strong>com</strong>bustible according to fire protection regulation<br />

Heating section: – L.P.H.W. air heater, heat exchanger with copper pipes and drawn aluminium fins in<br />

aluminium frame AlMg3 (max. temp. 110°C, Pmax 16 bar) removable in accordance<br />

with VDI6022;<br />

<strong>GEA</strong> motor 3-way mixing<br />

valve:<br />

Control and regulation<br />

system<br />

– For air reheater, supplied loose including actuator 0-10 V with an automatic step<br />

measurement system for fine adjustment of water flow rate<br />

– Supplied loose, installation by others<br />

– Consists of a separate switch cabinet for mounting on units or separate installation<br />

(depending on unit size), with all necessary <strong>com</strong>ponents for control functions, wired<br />

according to VDE specifications. IP55 electrical connection (via plug or screw terminals)<br />

between control cabinet and unit using factory prepared and fully assembled<br />

lines. Electrical installation for voltage supply, valve mixing control, reheater<br />

pump, if necessary external sensor of the pool water pump and possibly other functions<br />

like remote control inputs by others. The cabinet is supplied loose depending<br />

on the unit size as a stand alone cabinet or for mounting on the unit;<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 17


Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CAM<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

The switch cabinet is<br />

supplied with the following<br />

main <strong>com</strong>ponents:<br />

– Main isolating switch for all pole shut-down of the electrical unit, lockable<br />

– Group fuses for fan and <strong>com</strong>pressor<br />

– Fuses for reheater and PWC pump<br />

230V/N/PE/50Hz (types 015-083)<br />

3 X 400V/NPE/50Hz (types 100-320) (if necessary - motor protection by others)<br />

– Control fuses, control transformer 230 V and control voltage supply unit 24V DC for<br />

the digital control<br />

– Control fuse and control voltage supply unit 24V AC for actuators<br />

– Automatic phase controller (option)<br />

– Indoor installation, frost free<br />

Digital control: – Modular automation station built into switch cabinet with deletion-proof software<br />

modules and digital and analogue inputs and outputs, equipped with all control<br />

functions for swimming pool dehumidifier, consisting of:<br />

– Control unit with 32 bit processor in network based, interdisciplinary, free programmable<br />

automation system<br />

– Watchdog function, data buffering (FLASH-ROM), hardware clock<br />

– Interfaces:<br />

1 x CAN (Controller Area Network) as central bus between control unit and I/O<br />

modules;<br />

1 x LIN (Local Interconnect Network) for auxiliary module monitoring and configuration<br />

functions;<br />

1 x CAN for external connection;<br />

2 x RS232/RS485, one RS232 has modem function;<br />

Optional - Ethernet; USB plug;<br />

Optional - various <strong>com</strong>munication functions can be carried out (e. g: OPC; LON;<br />

MODBUS; OSPA; BACnet ® ) As BACnet ® -Building Controller (B-BC) the system<br />

can cost efficiently intgerate or be integrated in any BACnet ® third system.<br />

– In and output modules with an integrated microcontroller and memory for recording<br />

a programme specifically designed for the relevant module, status display for<br />

every input or output with CAN provided via top hat rail bus plug.<br />

– Comfortable intelligent control terminal for supporting display, control buttons and<br />

data transfer, installed in the door of the switch cabinet<br />

– Alufront panel with front film<br />

– Keyboard connection via plug connector<br />

– Front side protection type IP 65<br />

– LCD-Display with 8 lines each with 40 symbols as clear text display, monochrome<br />

– 6 function buttons<br />

– Colour background lighting, adjustable, automatic lighting activation<br />

– Adjustable LCD contrast<br />

– System bus CAN<br />

– Alternative (option): as before, but:<br />

– with <strong>com</strong>fortable touch control terminal<br />

– LCD display with 16 colours<br />

– Graphical resolution 320 x 240 Pixel<br />

18 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Control and regulation<br />

functions:<br />

Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CAM<br />

– Status and fault signals in clear text<br />

– Indication of all status and control parameters<br />

– Stepwise access authorization using code<br />

– Integrated clock timer<br />

– Automatic summer / winter time switch-over, activation of weekly programmes, holiday<br />

and special day programmes<br />

– Log for registration of faults with date and time<br />

– Operating hours counter, total operation and maintenance intervals<br />

– Data logging function for most important parameters, can be downloaded<br />

– Separate controls for supply and exhaust air fan motors<br />

– Air volume adjustment and display in m³/h, including monitoring for units with frequency<br />

converters<br />

– Fan motor monitoring using PTC resistor and motor protection relay<br />

– Filter monitoring<br />

– Compressor control (heat pump) with minimum run / standstill time<br />

– Control of air mixig dampers with selectable min. fresh air rate and max. limitation,<br />

automatic control depending on conditions of fresh air and swimming pool air<br />

– Control sequence with energy recovery, heater, <strong>com</strong>pressor (heat pump), bypass<br />

damper and air mixing damper system<br />

– Exhaust air temperature cascade control with min./max. limitation<br />

of supply air temperature<br />

– Cooling with outside air (night cooling)<br />

– Reheater-heat pump consumption control with blockage protection functions<br />

– Continuous humidity control<br />

– On demand - controls for automatic pool water pump with block up protection<br />

– Automatic switch-over between active/non-active hours operation<br />

– Continuous inactive/idle mode possible<br />

– Different languages can be selected<br />

– Commissioning function for air dampers<br />

– Inputs: external emergency switch off<br />

(e.g. fire protection damper or chlorine gas alarm)<br />

– Motor monitoring for reheater pump can be switched, if required motor protection<br />

by others<br />

– Motor monitoring for pool water pump can be switched, if required motor protection<br />

by others<br />

– The necessary sensors and actuators are built into the unit or, if necessary,<br />

supplied loose with subsequent installation by others<br />

Air mixing dehumidifier CAM<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 19


Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CAM<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Technical data<br />

Type<br />

Unit series CAM…SU. (standard model, maximum air velocity for supply and exhaust air approx. 2,8 m/s),<br />

plug fans, frequency converters<br />

Air volume flow<br />

Unit dimensions<br />

Dehumidification<br />

capacity<br />

Heating capacity<br />

Pressure<br />

drop<br />

Motor rated power/current<br />

Current<br />

consumption<br />

CAM_SU<br />

Total width<br />

Total height<br />

Total length<br />

Minimum<br />

Maximum<br />

Rated (with dehumidification)<br />

Rated (with ventilation)<br />

Active hours more (30 % F.A.)/<br />

idle mode (circulating air)/ VDI 2089 1)<br />

Air condenser, with inactive<br />

pool water condenser<br />

Air condenser, with active pool<br />

water condenser<br />

[mm] [m3/h] [kg/h] [kW] [Pa] [kW/A] [A]<br />

015 760 1120 3000 750 1843 1000 667 6/3/6 5.4 3.0 2.4 3.0 9.9 300 0.6/1.4 0.6/1.4 1.3/2.5 5.3<br />

025 760 1360 3200 1842 2756 2000 1333 12/5/13 9.3 6.7 2.8 5.9 16.3 300 0.8/1.7 0.8/1.7 1.8/3.5 6.9<br />

030 760 1360 3300 2755 3355 3000 2000 16/5/19 10.7 7.9 3.0 6.9 20.6 300 2.2/4.6 1.5/3.3 2.2/4.2 12.1<br />

037 760 1600 3300 3354 4129 4000 2667 19/5/25 13.1 10.8 2.5 8.9 28.0 300 3.0/6.1 2.2/4.6 2.3/4.5 15.2<br />

045 1080 1360 3300 4128 5032 5000 3333 26/9/32 17.3 14.5 2.6 12.2 35.9 300 3.0/6.1 3.0/6.1 2.7/5.4 17.6<br />

055 1080 1600 3400 5031 6193 6000 4000 31/11/38 21.3 18.7 2.5 15.0 43.9 300 4.0/8.2 3.0/6.1 3.5/7.2 21.5<br />

083 1080 2240 4000 6192 9290 9000 6000 43/12/57 26.9 22.5 4.3 22.0 66.5 300 4.0/8.2 4.0/8.2 4.7/9.4 25.8<br />

100 1400 2240 4000 9289 12386 12000 8000 57/17/76 35.6 30.7 5.2 30.6 88.8 300 5.5/11.4 5.5/11.4 6.1/13.3 36.1<br />

110 1720 2240 4000 12385 15483 15000 10000 72/21/95 42.4 39.0 4.6 39.3 110.0 300 7.5/15.2 5.5/11.4 6.5/13.4 40.0<br />

130 2000 2320 4000 15482 18192 18000 12000 86/24/115 53.1 45.6 6.5 45.4 135.9 300 7.5/15.2 7.5/15.2 8.6/15.7 46.1<br />

150 1720 2880 4400 18191 20644 20000 13333 98/31/127 62.6 55.7 8.2 50.8 147.3 300 11.0/24.5 7.5/15.2 10.5/19.3 59.0<br />

170 2000 2960 4600 20643 24257 24000 16000 117/37/153 72.9 63.2 10.2 61.8 180.1 300 11.0/24.5 11.0/24.5 12.3/24.4 73.4<br />

200 2320 2960 4600 24256 28385 27000 18000 135/45/172 87.8 77.1 10.2 72.5 188.2 300 11.0/24.5 11.0/24.5 13.7/24.5 73.5<br />

230 2640 2960 4800 28384 32514 32500 21667 158/48/207 99.4 86.6 13.5 85.8 232.4 300 15.0/29.5 15.0/29.5 15.6/29.7 88.7<br />

250 2320 3600 5000 32513 35482 34000 22667 169/58/216 108.1 95.4 14.2 91.6 237.6 300 15.0/29.5 11.0/24.5 17.5/31.7 85.7<br />

320 2920 3600 5300 40642 45128 45000 30000 219/79/286 135.1 118.5 15.7 120.0 327.3 300 18.5/36.5 18.5/36.5 20.7/38.1 111.1<br />

Tab. 3: Technical data <strong>CAIRfricostar</strong> CAM_SU<br />

Pool water condenser (accessory)<br />

Heat recovery system<br />

Reheater 2)<br />

Ext. fresh/supply air;<br />

exhaust/return air; each<br />

Supply air fan, high speed,<br />

at rated volume flow<br />

Exhaust air fan, high speed,<br />

at rated volume flow<br />

Compressor, without pool<br />

water condenser<br />

Unit total 3)<br />

1) Swimming pool air condition 30 °C/54 %r.F.; Outdoor air condition 5 °C/85 %r.h.<br />

2) Inlet/outlet temperature 70 °C/50 °C; maximum heating capacity; 2 rows<br />

3) plus controls/regulation/pumps etc.<br />

(All data are approximate values and summarize most important features.<br />

Subject to modifications. Exact data are available in the current Lplus design software)<br />

20 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CAM<br />

Unit series CAM…PU. (performance model, maximum air velocity for supply and exhaust air from 2,5 m/s to 2,0 m/s),<br />

plug fans, frequency converters<br />

Type Unit dimensions<br />

Air volume flow<br />

Dehumidification<br />

capacity<br />

Heating capacity<br />

Pressure<br />

drop<br />

Motor rated power/current<br />

Current<br />

consumption<br />

CAM_PU<br />

Total width<br />

Total height<br />

Total length<br />

Minimum<br />

Maximum<br />

Rated (with dehumidification)<br />

Rated (with ventilation)<br />

Active hours more (30 % F.A.)/<br />

idle mode (circulating air)/ VDI 2089 1)<br />

Air condenser, with inactive<br />

pool water condenser<br />

Air condenser, with active<br />

pool water condenser<br />

[mm] [m3/h] [kg/h] [kW] [Pa] [kW/A] [A]<br />

015 760 1120 3000 750 1500 1000 667 6/4/6 5.6 3.5 2.3 3.5 9.5 300 0.6/1.4 0.6/1.4 1.2/2.3 5.1<br />

025 760 1360 3200 1500 2500 2000 1333 11/5/13 7.4 5.3 2.1 7.0 15.3 300 1.1/2.4 0.8/1.7 1.3/2.5 6.6<br />

030 760 1360 3300 2500 2995 2900 1933 16/6/18 10.8 7.9 3.3 8.7 20.0 300 2.2/4.6 2.2/4.6 2.3/4.3 13.5<br />

037 760 1600 3300 2994 3686 3600 2400 19/7/23 12.9 10.1 2.9 10.9 24.7 300 3.0/6.1 2.2/4.7 2.5/4.7 15.4<br />

045 1080 1360 3300 3685 4493 4400 2933 25/10/28 16.8 14.0 3.1 14.1 30.8 300 2.2/4.6 2.2/4.8 2.9/5.6 14.8<br />

055 1080 1600 3400 4492 5530 5500 3667 31/12/35 20.6 17.9 3.1 17.7 38.8 300 3.0/6.1 3.0/6.1 3.6/7.4 19.6<br />

083 1080 2240 4000 5529 8294 7500 5000 39/14/48 23.7 19.6 4.4 24.3 56.3 300 4.0/8.2 3.0/6.1 4.2/7.6 21.9<br />

100 1400 2240 4000 8293 9953 9900 6600 53/19/63 30.9 26.2 5.1 33.5 72.7 300 4.0/8.2 4.0/8.2 5.1/11.2 27.6<br />

110 1720 2240 4000 9952 11059 11000 7333 62/25/70 36.4 31.8 4.9 39.8 86.9 300 4.0/8.2 4.0/8.2 5.9/13.2 29.6<br />

130 2000 2320 4000 11058 12995 12500 8333 70/29/80 43.1 35.8 7.5 45.2 98.6 300 4.0/8.2 4.0/8.2 6.8/13.7 30.1<br />

150 1720 2880 4400 12994 14746 14500 9667 82/36/92 52.3 44.5 8.6 52.1 115.5 300 5.5/11.4 5.5/11.4 9.0/16.2 39.0<br />

170 2000 2960 4600 14745 17326 17000 11333 94/37/108 54.1 46.6 9.0 61.3 132.7 300 5.5/11.4 5.5/11.4 8.5/15.6 38.4<br />

200 2320 2960 4600 17325 20275 20000 13333 112/45/127 67.4 57.6 9.6 73.2 158.9 300 7.5/17.0 7.5/17.0 10.4/18.9 52.9<br />

230 2640 2960 4800 20274 23224 23000 15333 130/54/146 77.3 65.2 13.7 85.6 185.2 300 7.5/17.0 7.5/17.0 12.0/24.1 58.1<br />

250 2320 3600 5000 23223 25344 25000 16667 138/49/159 79.8 66.2 12.3 92.0 199.3 300 11.0/25.0 7.5/17.0 11.9/24.0 66.0<br />

320 2920 3600 5300 29029 32256 32000 21333 177/63/204 101.4 86.4 15.6 118.1 288.2 300 11.0/25.0 11.0/25.0 15.3/29.3 79.3<br />

Tab. 4: Technical data <strong>CAIRfricostar</strong> CAM_PU<br />

1) Swimming pool air condition 30 °C/54 %r.F.; Outdoor air condition 5 °C/85 %r.h.<br />

2) Inlet/outlet temperature 70 °C/50 °C; maximum heating capacity; 2 rows<br />

3) plus controls/regulation/pumps etc.<br />

(All data are approximate values and summarize most important features.<br />

Subject to modifications. Exact data are available in the current Lplus design software)<br />

Pool water condenser (accessory)<br />

Heat recovery system<br />

Reheater 2)<br />

Ext. fresh/supply air;<br />

exhaust/return air; each<br />

Supply air fan, high speed,<br />

at rated volume flow<br />

Exhaust air fan, high speed,<br />

at rated volume flow<br />

Compressor, without pool<br />

water condenser<br />

Unit total 3)<br />

Air mixing dehumidifier CAM<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 21


F6<br />

F6<br />

F7<br />

F7<br />

F6<br />

F6<br />

F7<br />

F7<br />

F6<br />

F6<br />

F7<br />

F7<br />

Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CMP<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Functional description of the unit<br />

The <strong>GEA</strong> <strong>CAIRfricostar</strong> CMP is designed for various kinds High Performance private<br />

and public swimming pools. The series can be supplied with air volume capacity<br />

between 750 up to 37,500 m³/h. The unit's function is to dehumidify and heat air in<br />

swimming pools in air mixing mode. Together with a (heat pump) this unit type is additionally<br />

equipped with an efficient heat recovery system using a double plate heat<br />

exchanger. The unit is delivered with a DDC controls which regulates all functions of<br />

the system on a fully automated basis.<br />

Sample selection of operation mode:<br />

When in idle mode without dehumidification the air is recirculated in the swimming pool.<br />

When the humidity setpoint has been exceeded the unit switches into dehumidification<br />

mode. At this point the supply air fan is activated and the exhaust air fan maintains the<br />

air circulation. The refrigeration unit is activated in order to start dehumidification. The<br />

dehumidification stage continues until the actual humidity value is reduced below that<br />

of the humidity setpoint. After that the fan is switched back into previous speed and the<br />

dehumidification cycle is stopped.<br />

In active hours mode the fresh and exhaust air dampers are opened, the refrigeration<br />

cycle is activated and both fans are switched into high speed.<br />

Using an optional pool water condenser a certain amount of excess energy produced<br />

by the refrigeration cycle can be fed back into swimming pool water. In case of overheating<br />

of the swimming pool the refrigeration unit is deactivated and the bypass<br />

dampers are permanently open in order to avoid heat recovery system.<br />

Idle mode without dehumidification<br />

demand<br />

Idle mode with dehumidification<br />

demand<br />

Active hours operation mode with<br />

dehumidification demand<br />

Bypass damper mode, exhaust air fan is deactivated,<br />

supply air fan runs at low speed.<br />

Bypass damper mode, exhaust air fan runs at<br />

low speed, supply air fan runs at high speed.<br />

Compressor is switched on. Residual heat<br />

supply is provided by the reheater coil.<br />

Operation with air mixing damper, exhaust<br />

and supply air fans run at high speed. Compressor<br />

is switched on. Compressor is<br />

switched on.<br />

Active hours operation mode with<br />

dehumidification demand at high<br />

outdoor temperatures<br />

Active hours operation mode with<br />

dehumidification demand at high<br />

outdoor temperatures<br />

Idle mode in summer and at high<br />

outdoor temperatures<br />

Operation with air mixing damper, exhaust<br />

and supply air fans run at high speed. Compressor<br />

is blocked. Regulated heat recovery<br />

using open bypass dampers for avoiding heat<br />

recovery system.<br />

Operation with air mixing damper, exhaust<br />

and supply air fans run at high speed. Compressor<br />

is blocked. Regulated heat recovery<br />

using open bypass dampers for avoiding heat<br />

recovery system.<br />

Outdoor air operation for reaching nominal air<br />

temperature. Compressor is blocked. Double<br />

plate heat exchanger is blocked.<br />

22 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CMP<br />

System and controls scheme<br />

M<br />

<br />

M<br />

<br />

M<br />

p<br />

<br />

<br />

M<br />

M<br />

p<br />

Y8<br />

M<br />

+<br />

+<br />

M<br />

M<br />

p<br />

<br />

<br />

p<br />

M3<br />

p<br />

M<br />

p<br />

M<br />

p<br />

M<br />

M<br />

M<br />

DI<br />

AI<br />

DO<br />

AO<br />

Components<br />

Casing:<br />

Heat pump for<br />

dehumidification:<br />

Indoor installation<br />

– 50 mm panels, inside and outside skins are painted; (corresponds to RAL 9002),<br />

the series includes casing frame and service door in casing panel thickness together<br />

with a full profile rubber gasket in EPDM quality. All outside and inside surfaces<br />

are <strong>com</strong>pletely smooth.<br />

– Leak tightness class G II according to VDI 3803. Thermal and sound bridges are<br />

minimized.<br />

– Non <strong>com</strong>bustible insulation (fire classification A1 according to DIN 4102; Ö-Norm<br />

B3800; CFC-free)<br />

– Heat transfer coefficient k = 0,57 W/m2 K<br />

– Sound insulation performance Rw = 44 dB according to DIN 52210/T4<br />

– Casing features according to EN1886<br />

– Filter bypass leakage F9<br />

– Leak tightness class according to prEN 1886 (10/2005) L1<br />

– Casing leakage B<br />

– Mechanical stability 1A<br />

– Thermal insulation T2<br />

– Thermal bridging factor TB2 (in risk areas)<br />

– Frame profiles AlMgSi 0,5<br />

– Flexible connector with potential equalisation, temperature resistant from<br />

-30 °C to +120 °C<br />

– Duct connection using 30 mm frame with 4 hole bolt connection<br />

– Interior installation parts for swimming pool mode with special corrosion protection<br />

– Direct evaporator according to VDI 6022: heat exchanger as Cu/Alu model for<br />

R 407c refrigerant, fins made of aluminium, frame elements made of AlMg3, pipes<br />

made of oxygen-free copper.<br />

– Condensate water tray in bottom panel for evaporator and heat recovery system,<br />

with a slope in the direction of condensate drain, made of stainless steel V4A powder<br />

coated, including drain tray, conform with VDI 6022<br />

– Air-cooled condenser according to VDI 6022: heat exchanger as Cu/Alu model for<br />

R 407c refrigerant, fins made of aluminium, frame elements made of AlMg3, pipes<br />

made of oxygen-free copper<br />

– Compressor unit: refrigeration circuit with a fully hermetic scroll <strong>com</strong>pressor<br />

Air mixing dehumidifier CMP<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 23


Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CMP<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

– With optimized heat exchanger <strong>com</strong>bination for maximum COP values, mounted on<br />

anti-vibration mounts, circuit includes filter drier, liquid collector, thermostatic<br />

expansion valve with MOP (maximum operating pressure) and external pressure<br />

equalisation, all necessary shut-off valves, monitoring and safety devices<br />

(pressostat, icing sensor, etc.)<br />

Droplet eliminator – Made of plastic with an aluminium frame at air velocities on supply and exhaust side<br />

exceeding 2,5 m/s is necessary<br />

Fan unit:<br />

<strong>GEA</strong> „OPTIVENT“<br />

– High performance fan impellers with coated backward curved blades, one side suction<br />

and blades directly connected to motor shaft; Performance<br />

– Optimized high value three-phase motor, B3 model type, protection type IP55, insulation<br />

class F adjusted for operation with a frequency converter. Fan and motor unit<br />

including coated intake nozzle mounted on buckling resistant and coated base construction,<br />

motor and fan have sound attenuated bearings<br />

– Continuous measurement of pressure effects<br />

– Statically and dynamically balanced according to DIN ISO 1940, part 1, G2,5). Continuous<br />

monitoring of operation using DDC. Frequency converter for each motor<br />

installed in or mounted on the unit, control via <strong>GEA</strong> DDC with a separate analogue<br />

signal for both motors. Frequency converters are adjusted and set for both motors.<br />

Limit values for motor current and fan speed are set by the programme<br />

– Resonance frequency band/fade out set by factory<br />

– Automatic energy optimization for optimal energy use and efficiency rate<br />

– Multiple motor operation is possible<br />

– Voltage intermediate circuit converter without reduction of capacity<br />

– Continuous speed control<br />

– Operating hours counter<br />

– Min. and max. speed limitation, automatic ramp curve function UP/DOWN<br />

– Automatic motor adjustment<br />

– Motor tracing switch<br />

– DC break<br />

– Variable clock frequency<br />

– Motor protection<br />

– Short circuit and short circuit to earth safe<br />

– Under and over current protection<br />

– Phase fault monitoring<br />

– Motor coils for reducing speed of voltage rise du/dt (delta voltage/delta time)<br />

– Numerical display for queries and entering of different indicators on operating status:<br />

control setpoint, motor frequency, actual value and setpoint, motor current,<br />

motor torque and capacity, intermediate circuit voltage, thermal motor load, thermal<br />

frequency converter load, control and programmable display with copy function,<br />

production according to ISO 9001, CE Label, net and main shaft protection<br />

according to VDE 0160, radio interference shielding, codes and regulations on electromagnetic<br />

<strong>com</strong>patibility conform with EN 55011 Kl.B-1; EN 50082-2, electric insulation<br />

of control and power <strong>com</strong>ponents according to VDE 0106/0160 (The use of<br />

earth leakage circuit breaker / fuse with frequency converters NOT possible!), volume<br />

flow measuring device via ring measuring line and pressure measuring point<br />

in fan. Calculation and evaluation of volume flow via the <strong>GEA</strong> DDC. The settings for<br />

entire unit are done at the factory. Continuous safety monitoring via safety chain in<br />

the unit. Display and settings via <strong>GEA</strong> DDC.<br />

24 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CMP<br />

Air damper system: – Dampers with sealing lips, leakage volume flow 20 m3/h m2 (dp=100 Pa), for circulating<br />

air/bypass, for fresh and exhaust air. Circulating and fresh air rate 0-100%<br />

– Coated Almg3 damper blades with flow efficient profile, operate in opposite directions.<br />

Driven by double sided, anti-static plastic gears PA6 as fiberglass reinforced<br />

model (resistant to chemicals) including special actuator for each damper<br />

– Control of the individual actuators using continuous DDC signals<br />

Filter for fresh and<br />

exhaust air:<br />

– Filter units conform with VDI 6022<br />

– Including bag filter as of DIN/EN 779, synthetic fiber filter medium<br />

– All filters are fitted with a differential pressure switch for filter monitoring via the DDC<br />

Heat recovery system:<br />

<strong>GEA</strong> „ECOPLAT2 POWER PLATE“<br />

– 2 symmetric high performance plate heat exchangers, recuperative heat recovery<br />

by using two cross flow aluminium plate heat exchangers (corrosion protected Al99<br />

with best temperature coefficient) in row switch. Surface is additionally coated with<br />

thermoplastic material. Largest possible heat exchange surface using entire unit<br />

depth with minimum pressure losses. Optimal selection with consideration of operation<br />

conditions. Best efficiency rates within entire outdoor temperature range,<br />

especially resistant to corrosion and wear. Swimming pool configuration.<br />

– „Upside Down“ installation for smaller internal pressure drops.<br />

– AlMg3 ventilation tray<br />

– Technical data checked according to EUROVENT<br />

– Conform with VDI 6022<br />

– Non-<strong>com</strong>bustible according to fire protection regulation<br />

Heating section: – L.P.H.W. air heater, heat exchanger with copper pipes and drawn aluminium fins in<br />

aluminium frame AlMg3 (max. temp. 110°C, Pmax 16 bar) removable in accordance<br />

with VDI 6022;<br />

<strong>GEA</strong> motor 3-way mixing<br />

valve:<br />

Control and regulation<br />

system<br />

– For air reheater, supplied loose including actuator 0-10 V with an automatic step<br />

measurement system for fine adjustment of water flow rate<br />

– Supplied loose, installation by others<br />

– Consists of a separate switch cabinet for mounting on units or separate installation<br />

(depending in unit size), with all necessary <strong>com</strong>ponents for control functions, wired<br />

according to VDE specifications. IP55 electrical connection (via plug or screw terminals)<br />

between control cabinet and unit using factory prepared and fully<br />

assembled lines. Electrical installation for voltage supply, valve mixing control,<br />

reheater pump, if necessary external sensor of the pool water pump and possibly<br />

other functions like remote control inputs by others. The cabinet is supplied loose<br />

depending on the unit size as a stand alone cabinet or for mounting on the unit<br />

Air mixing dehumidifier CMP<br />

The switch cabinet is<br />

supplied with the following<br />

main <strong>com</strong>ponents:<br />

– Main isolating switch for all pole shut-down of the electrical unit, lockable<br />

– Group fuses for fan and <strong>com</strong>pressor<br />

– Fuses for reheater and PWC pump<br />

230V/N/PE/50Hz (types 015-083)<br />

3 X 400V/NPE/50Hz (types 100-320)<br />

(if necessary - motor protection by others)<br />

– Control fuses, control transformer 230 V and control voltage supply unit 24V DC for<br />

the digital control<br />

– Control fuse and control voltage supply unit 24V AC for actuators<br />

– Automatic phase controller (option)<br />

– Indoor installation, frost free<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 25


Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CMP<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Digital control: – Modular automation station built into switch cabinet with deletion-proof software<br />

modules and digital and analogue inputs and outputs, equipped with all control<br />

functions for swimming pool dehumidifier, consisting of:<br />

– Control unit with 32 bit processor in network based, interdisciplinary, free programmable<br />

automation system<br />

– Watchdog function, data buffering (FLASH-ROM), hardware clock<br />

– Interfaces:<br />

1 x CAN (Controller Area Network) as central bus between control unit<br />

and I/O modules;<br />

1 x LIN (Local Interconnect Network) for auxiliary module monitoring and<br />

configuration functions;<br />

1 x CAN for external connection;<br />

2 x RS232/RS485, one RS232 has modem function;<br />

Optional - Ethernet; USB plug;<br />

Optional - various <strong>com</strong>munication functions can be carried out (e. g: OPC; LON;<br />

MODBUS; OSPA; BACnet®) As BACnet®-Building Controller (B-BC) the system<br />

can cost-efficiently intgerate or be integrated in any BACnet® third system.<br />

– In and output modules with an integrated microcontroller and memory for recording<br />

a programme specifically designed for the relevant module, status display for<br />

every input or output with CAN provided via top hat rail bus plug.<br />

– Comfortable intelligent control terminal for supporting display, control buttons and<br />

data transfer, integrated in the door of the switch cabinet<br />

– Alufront panel with front film<br />

– Keyboard connection via plug connector<br />

– Front side protection type IP 65<br />

– LCD-Display with 8 lines each with 40 symbols as clear text display, monochrome<br />

– 6 function buttons<br />

– Colour background lighting, adjustable, automatic lighting activation<br />

– Adjustable LCD contrast<br />

– System bus CAN<br />

– Alternative (option): as before, but:<br />

– with <strong>com</strong>fortable touch control terminal<br />

– LCD display with 16 colours<br />

– Graphical resolution 320 x 240 Pixel<br />

26 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Control and regulation<br />

functions:<br />

Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CMP<br />

– Status and fault signals in clear text<br />

– Indication of all status and control parameters<br />

– Stepwise access authorization using code<br />

– Integrated clock timer<br />

– Automatic summer / winter time switch-over, activation of weekly programmes,<br />

holiday and special day programmes<br />

– Log for registration of faults with date and time<br />

– Operating hours counter, total operation and maintenance intervals<br />

– Data logging function for most important parameters, can be downloaded<br />

– Separate controls for supply and exhaust air fan motors<br />

– Air volume adjustment and display in m³/h, including monitoring for units with frequency<br />

converters<br />

– Fan motor monitoring using PTC resistor and motor protection relay<br />

– Filter monitoring<br />

– Compressor control (heat pump) with minimum run / standstill time<br />

– Regulation of air mixing dampers with selectable minimum fresh air rate and maximum<br />

limitation, automatic control depending on conditions of fresh air and swimming<br />

pool air<br />

– Control sequence with energy recovery, heater, <strong>com</strong>pressor (heat pump), bypass<br />

damper and air mixing damper system<br />

– Exhaust air temperature cascade control with min./max. limitation of supply air temperature<br />

– Cooling with outside air (night cooling)<br />

– Reheater-heat pump consumption control with blockage protection functions<br />

– Continuous humidity control<br />

– On demand - controls for automatic pool water pump with block up protection<br />

– Automatic switch-over between active/non-active hours operation<br />

– Continuous inactive idle mode possible<br />

– Different languages can be selected<br />

– Commissioning function for air dampers<br />

– Inputs: external emergency switch off<br />

(e.g. fire protection damper or chlorine gas alarm)<br />

– Motor monitoring for reheater pump can be switched, if required motor protection<br />

by others<br />

– Motor monitoring for pool water pump can be switched, if required motor protection<br />

by others<br />

– The necessary sensors and actuators are built into the unit or, if necessary,<br />

supplied loose with subsequent installation by others<br />

Air mixing dehumidifier CMP<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 27


Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CMP<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Technical data<br />

Type<br />

Unit series CMP…PU. (performance model, maximum air velocity for supply and exhaust air from 2,5 m/s to 2,0 m/s),<br />

plug fans, frequency converters<br />

Unit<br />

dimensions<br />

Air volume flow<br />

Dehumidification<br />

capacity<br />

Heating capacity<br />

Pressure<br />

drop<br />

Motor rated power/current<br />

Current<br />

consumption<br />

CMP_PU<br />

Total width<br />

Total height<br />

Total length<br />

Minimum<br />

Maximum<br />

Rated (with dehumidification)<br />

Rated (with ventilation)<br />

Active hours more (30% fresh air)/<br />

idle mode (circulating air)/VDI 2089 1)<br />

Air condenser, with inactive<br />

pool water condenser<br />

Air condenser, with active<br />

pool water condenser<br />

[mm] [m3/h] [kg/h] [kW] [Pa] [kW/A] [A]<br />

015 760 1120 4240 750 1500 1000 667 6/4/6 5.0 2.6 2.6 3.6 8.4 300 0.6/1.4 0.6/1.4 1.2/2.3 5.1<br />

025 760 1360 4480 1500 2500 2000 1333 11/5/13 6.7 3.9 2.9 6.9 13.4 300 0.8/1.7 0.8/1.7 1.5/2.8 6.2<br />

037 760 1600 4840 2500 3686 3400 2267 18/8/22 10.7 7.7 3.2 11.3 21.2 300 1.5/3.3 1.5/3.3 2.1/4.1 10.7<br />

055 1080 1600 4880 3685 5530 5000 3333 27/13/32 15.9 12.1 3.8 16.6 31.6 300 2.2/4.7 2.2/4.7 3.1/5.9 15.3<br />

083 1080 2240 5480 5529 8294 7500 5000 40/17/48 22.4 17.6 5.4 25.6 48.9 300 3.0/6.4 3.0/6.4 4.4/7.9 20.7<br />

110 1720 2240 5720 8293 11059 11000 7333 58/25/70 30.7 25.2 5.6 37.5 77.8 300 4.0/8.2 4.0/8.2 5.0/11.2 27.6<br />

130 2000 2320 5920 11058 12995 12500 8333 68/31/80 36.9 29.0 8.1 44.2 90.9 300 5.5/11.4 4.0/8.2 6.2/13.4 33.0<br />

150 1720 2880 6600 12994 14746 14000 9333 77/37/90 42.1 32.9 8.5 51.8 98.1 300 5.5/11.4 5.5/11.4 7.0/13.9 36.7<br />

170 2000 2960 6800 14745 17326 17000 11333 94/46/108 51.5 39.9 12.2 63.0 120.7 300 7.5/17.0 7.5/17.0 9.0/16.2 50.2<br />

200 2320 2960 7080 17325 20275 20000 13333 112/57/127 61.9 50.0 12.7 74.5 139.3 300 7.5/17.0 7.5/17.0 10.8/19.6 53.6<br />

250 2320 3600 7360 20274 25344 25000 16667 134/61/159 75.7 59.9 16.2 84.2 180.4 300 11.0/25.0 7.5/17.0 12.4/24.6 66.6<br />

320 2920 3600 8120 29029 32256 32000 21333 175/84/204 99.4 75.6 21.9 111.4 234.6 300 11.0/25.0 11.0/25.0 16.3/30.6 80.6<br />

Tab. 5: Technical data <strong>CAIRfricostar</strong> CMP_PU<br />

Pool water condenser (accessory)<br />

Heat recovery system<br />

Reheater 2)<br />

Ext. fresh/supply air;<br />

exhaust/return air; each<br />

Supply air fan, high speed,<br />

at rated volume flow<br />

Exhaust air fan, high speed,<br />

at rated volume flow<br />

Compressor, without<br />

pool water condenser<br />

Unit total 3)<br />

1) Swimming pool air condition 30 °C/54 %r.h.; Outdoor air condition 5 °C/85 %r.h.<br />

2) Inlet/outlet temperature 70 °C/50 °C; maximum heating capacity; 2 rows<br />

3) plus controls/regulation/pumps etc.<br />

(All data are approximate values and summarize most important features.<br />

Subject to modifications. Exact data are available in the current Lplus design software)<br />

28 PR-2008-0327-GB • Subject to modifications • Status 05/2009


130<br />

130<br />

130<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidifier with Air Mixing Function<br />

Type CWR<br />

Functional description of the unit<br />

The <strong>GEA</strong> <strong>CAIRfricostar</strong> CWR is designed for various kinds of private and public swimming<br />

pools. The series can be supplied with air volume capacity between 750 up to<br />

45,000 m³/h. The unit's function is to dehumidify and heat air in swimming pools in air<br />

mixing mode. This unit type is additionally equipped with an efficient heat recovery system.<br />

The unit is delivered with a DDC controls which regulates all functions of the system<br />

on a fully automated basis.<br />

Sample selection of operating modes:<br />

When in idle mode without dehumidification the air is recirculated in the swimming pool.<br />

When the humidity setpoint has been exceeded the unit switches into dehumidification<br />

mode. For this purpose the supply and exhaust air fans are activated to run at high<br />

speed with continuous mixing of outdoor air. The dehumidification stage continues until<br />

the actual humidity value is reduced below that of the humidity setpoint. After that the<br />

fans are deactivated.<br />

Idle mode without dehumidification<br />

demand<br />

Active hours operation mode with<br />

dehumidification demand<br />

Idle mode with dehumidification<br />

request<br />

+<br />

+<br />

+<br />

-<br />

-<br />

-<br />

Bypass damper mode, exhaust air fan is<br />

deactivated,<br />

supply air fan runs at low speed.<br />

Active hours operation mode with high<br />

dehumidification demand<br />

Air mixing operation according to VDI,<br />

exhaust and supply air fans run at high<br />

speed. The reheater provides the missing<br />

residual heat supply.<br />

Air mixing mode with a minimum fresh air rate<br />

Active hours/summer operation mode<br />

Air mixing dehumidifier CWR<br />

+<br />

+<br />

-<br />

-<br />

130<br />

130<br />

Air mixing operation according to VDI, exhaust and supply air fans<br />

run at high speed. The reheater provides the missing residual heat<br />

supply. Outdoor air temperature is increased.<br />

Fresh air mode, exhaust and supply air fans run at high speed.<br />

Heat recovery is not used thanks to a damper system.<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 29


.<br />

Dehumidifier with Air Mixing Function<br />

Type CWR<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

System and controls scheme<br />

M<br />

M<br />

M<br />

M<br />

M<br />

p<br />

Y2<br />

M<br />

MVS<br />

M<br />

M<br />

M<br />

MVS<br />

p<br />

DI<br />

AI<br />

DO<br />

AO<br />

Components<br />

Casing:<br />

Fan unit:<br />

Indoor installation<br />

– 50 mm panels, inside and outside skins are painted; (corresponds to RAL 9002),<br />

the series includes casing frame and service door in casing panel thickness together<br />

with a full profile rubber gasket in EPDM quality. All outside and inside surfaces<br />

are <strong>com</strong>pletely smooth.<br />

– Leak tightness class G II according to VDI 3803. Thermal and sound bridges are<br />

minimized.<br />

– Non <strong>com</strong>bustible insulation (fire classification A1 according to DIN 4102; Ö-Norm<br />

B3800; CFC-free)<br />

– Heat transfer coefficient k = 0,57 W/m2 K<br />

– Sound insulation performance Rw = 44 dB according to DIN 52210/T4<br />

– Casing features according to EN1886<br />

– Filter bypass leakage F9<br />

– Leak tightness class according to prEN 1886 (10/2005) L1<br />

– Casing leakage B<br />

– Mechanical stability 1A<br />

– Thermal insulation T2<br />

– Thermal bridging factor TB2 (in risk areas)<br />

– Frame profiles AlMgSi 0,5<br />

– Flexible connector with potential equalisation, temperature resistant from -30 °C to<br />

+120 °C<br />

– Duct connection using 30 mm frame with 4 hole bolt connection<br />

– Interior installation parts for swimming pool mode with special corrosion protection<br />

<strong>GEA</strong> centrifugal fan „LESS ENERGY SYSTEM“<br />

– Optimized operating point, double side suction, coated surface model<br />

– Three phase motor, protection class IP55 , model type B3, <strong>com</strong>plete belt drive, easy<br />

service thanks to one bolt tensioning sled<br />

– Fan/motor unit mounted on anti-vibration mounts<br />

30 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Alternative fan unit:<br />

Dehumidifier with Air Mixing Function<br />

Type CWR<br />

<strong>GEA</strong> „OPTIVENT“ high performance fan impellers<br />

– Surface coated one side suction with backward curved blades that are directly connected<br />

to motor shaft; performance optimized three-phase motor, B3 model type,<br />

protection type IP55, insulation class F adjusted for operation with a frequency converter.<br />

Fan and motor unit including coated intake nozzle mounted on buckling<br />

resistant and coated base construction, motor and fan have sound attenuated bearings<br />

– Continuous measurement of pressure effects<br />

– Statically and dynamically balanced according to DIN ISO 1940, part 1, G2,5). Continuous<br />

pressure monitoring using DDC. Frequency converter for each motor<br />

installed in or mounted on the unit, control via <strong>GEA</strong> DDC with a separate analogue<br />

signal for each motor. Frequency converters are adjusted and set for both motors.<br />

Limit values for motor current and fan speed are set by the programme<br />

– Resonance frequency band/fade out set by factory<br />

– automatic energy optimization for optimal energy use and efficiency rate<br />

– Multiple motor operation is possible<br />

– Voltage intermediate circuit converter without reduction of capacity<br />

– continuous speed control<br />

– Operating hours counter<br />

– Min. and max. speed limitation, automatic ramp curve function UP/DOWN<br />

– Automatic motor adjustment<br />

– Motor tracing switch<br />

– DC break<br />

– Variable clock frequency<br />

– Motor protection<br />

– Short circuit and short circuit to earth safe<br />

– Under and overcurrent protection<br />

– Phase fault monitoring<br />

– Motor coils for reducing speed of voltage rise du/dt (delta voltage/delta time)<br />

– Numerical display for queries and entering of different indicators on operating status:<br />

control setpoint, motor frequency, actual value and setpoint, motor current,<br />

motor torque and capacity, intermediate circuit voltage, thermal motor load, thermal<br />

frequency converter load, control and programmable display with copy function,<br />

production according to ISO 9001, CE Label, net and main shaft protection according<br />

to VDE 0160, radio interference shielding, codes and regulations on electromagnetic<br />

<strong>com</strong>patibility conform with EN 55011 Kl.B-1; EN 50082-2, electric<br />

insulation of control and power <strong>com</strong>ponents according to VDE 0106/0160 (The use<br />

of earth leakage circuit breaker / fuse with frequency converters NOT possible!),<br />

volume flow measuring device via ring measuring line and pressure measuring<br />

point in fan. Calculation and evaluation of volume flow via the <strong>GEA</strong> DDC. The settings<br />

for entire unit are done at the factory. Continuous safety monitoring via safety<br />

chain in the unit. Display and settings via <strong>GEA</strong> DDC.<br />

Air mixing dehumidifier CWR<br />

Air damper system: – Dampers with sealing lips, leakage volume flow 20 m3/h m2 (dp=100 Pa), for circulating<br />

air/bypass, for fresh and exhaust air. Circulating and fresh air rate 0-100%<br />

– Coated Almg3 damper blades with flow efficient profile, operate in opposite<br />

directions. Driven by double sided, anti-static plastic gears PA6 as fiberglass<br />

reinforced model (resistant to chemicals) including special actuator for<br />

each damper<br />

– Control of the individual actuators using continuous DDC signals<br />

Filter for fresh and<br />

exhaust air:<br />

– Filter units conform with VDI 6022<br />

– Including bag filter as of DIN/EN 779, synthetic fiber filter medium<br />

– All filters are fitted with a differential pressure switch for filter monitoring via the DDC<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 31


Dehumidifier with Air Mixing Function<br />

Type CWR<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Heat recovery system: <strong>GEA</strong> „ECOSTAT2 POWER TUBE“:<br />

– Recuperative heat recovery using <strong>GEA</strong> heat pipe technology, heat exchanger<br />

made of Cu/Al. Aluminium fins, frame elements made of AlMg3, tubes made of oxygen-free<br />

copper charged with R134a CFC-free refrigerant for energy transfer.<br />

– Non-<strong>com</strong>bustible according to fire protection regulation<br />

Heating section: – L.P.H.W. air heater, heat exchanger with copper pipes and drawn aluminium fins in<br />

aluminium frame AlMg3 (max. temp. 110°C, Pmax 16 bar) removable in accordance<br />

with VDI 6022;<br />

<strong>GEA</strong> motor 3-way mixing<br />

valve:<br />

Control and regulation<br />

system<br />

The switch cabinet is<br />

supplied with the following<br />

main <strong>com</strong>ponents:<br />

– For air reheater, supplied loose including actuator 0-10 V with an automatic step<br />

measurement system for fine adjustment of water flow rate<br />

– supplied loose, installation by others<br />

– Consists of a separate switch cabinet for mounting on units or separate installation<br />

(depending in unit size), with all necessary <strong>com</strong>ponents for control functions, wired<br />

according to VDE specifications. IP55 electrical connection (via plug or screw terminals)<br />

between control cabinet and unit using factory prepared and fully assembled<br />

lines. Electrical installation for voltage supply, valve mixing control, reheater<br />

pump, if necessary external sensor and possibly other functions like remote control<br />

inputs by others. The cabinet is supplied loose depending on the unit size as a<br />

stand alone cabinet or for mounting on the unit<br />

– Main isolating switch for all pole shut-down of the electrical unit, lockable<br />

– Group fuses for fans<br />

– Fuses for reheater<br />

230V/N/PE/50Hz (types 015-083)<br />

3 X 400V/NPE/50Hz (types 100-320)<br />

(if necessary - motor protection by others)<br />

– Control fuses, control transformer 230 V and control voltage supply unit<br />

24V DC for the digital control<br />

– Control fuse and control voltage supply unit 24V AC for actuators<br />

– Automatic phase controller (option)<br />

– Indoor installation, frost free<br />

Digital control: – Modular automation station built into switch cabinet with deletion-proof software<br />

modules and digital and analogue inputs and outputs, equipped with all control<br />

functions for swimming pool dehumidifier, consisting of:<br />

– Control unit with 32 bit processor in network based, interdisciplinary, free programmable<br />

automation system<br />

– Watchdog function, data buffering (FLASH-ROM), hardware clock<br />

– Interfaces:<br />

1 x CAN (Controller Area Network) as central bus between control unit and I/O<br />

modules;<br />

1 x LIN (Local Interconnect Network) for auxiliary module monitoring and configuration<br />

functions;<br />

1 x CAN for external connection;<br />

2 x RS232/RS485, one RS232 has modem function;<br />

Optional - Ethernet; USB plug;<br />

Optional - various <strong>com</strong>munication functions can be carried out (e. g: OPC; LON;<br />

MODBUS; OSPA; BACnet®)<br />

As BACnet®-Building Controller (B-BC) the system can cost efficiently integrate<br />

or be integrated in any BACnet® third system.<br />

– In and output modules with an integrated microcontroller and memory for recording<br />

a programme specifically designed for the relevant module, status display for<br />

every input or output with CAN provided via top hat rail bus plug.<br />

– Comfortable intelligent control terminal for supporting display, control buttons and<br />

data transfer, installed in the door of the switch cabinet<br />

– Aluminium front panel with film, keyboard connection via plug connector<br />

– Front side protection type IP 65<br />

– LCD-Display with 8 lines each with 40 symbols as clear text display, monochrome<br />

32 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidifier with Air Mixing Function<br />

Type CWR<br />

Control and regulation<br />

functions:<br />

– 6 function buttons<br />

– Colour background lighting, adjustable, automatic lighting activation<br />

– Adjustable LCD contrast<br />

– System bus CAN<br />

– Alternative (option): as before, but:<br />

– with <strong>com</strong>fortable touch control terminal<br />

– LCD display with 16 colours<br />

– Graphical resolution 320 x 240 Pixel<br />

– Status and fault signals in clear text<br />

– Indication of all status and control parameters<br />

– Stepwise access authorization using code<br />

– Integrated clock timer<br />

– Automatic summer / winter time switch-over, activation of weekly programmes,<br />

holiday and special day programmes<br />

– Log for registration of faults with date and time<br />

– Operating hours counter, total operation and maintenance intervals<br />

– Data logging function for most important parameters, can be downloaded<br />

– Separate controls for supply and exhaust air fan motors<br />

– Air volume adjustment and display in m³/h, including monitoring for units with<br />

frequency converters<br />

– Fan motor monitoring using PTC resistor and motor protection relay<br />

– Filter monitoring<br />

– Regulation of air mixing dampers with selectable minimum fresh air rate and maximum<br />

limitation, automatic control depending on conditions of fresh air and swimming<br />

pool air<br />

– Control sequence with energy recovery, heater, bypass damper and air mixing<br />

damper system<br />

– Exhaust air temperature cascade control with min./max. limitation of supply air temperature<br />

– Cooling with outside air (night cooling)<br />

– Reheater-heat pump consumption control with blockage protection functions<br />

– Continuous humidity control<br />

– Automatic switch-over between active/non-active hours operation<br />

– Continuous inactive idle mode possible<br />

– Different languages can be selected<br />

– Commissioning function for air dampers<br />

– Inputs: external emergency switch off (e.g. fire protection damper or chlorine gas<br />

alarm)<br />

– Motor monitoring for reheater pump can be switched, if required motor protection<br />

by others<br />

– The necessary sensors and actuators are built into the unit or, if necessary,<br />

supplied loose with subsequent installation by others<br />

Air mixing dehumidifier CWR<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 33


Dehumidifier with Air Mixing Function<br />

Type CWR<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Technical data<br />

Unit series CWR…SU. (standard model, maximum air velocity for supply and exhaust air approx. 2,8 m/s),<br />

plug fans, frequency converters<br />

Type Unit dimensions Air volume flow<br />

Dehumidification<br />

capacity<br />

Heating<br />

capacity<br />

Pressure<br />

drop<br />

Motor rated<br />

power/current<br />

Current<br />

consumption<br />

CWR_SU<br />

Total width<br />

Total height<br />

Total length<br />

Minimum<br />

Maximum<br />

Rated (with dehumidification)<br />

Rated (with ventilation)<br />

[mm] [m3/h] [kg/h] [kW] [Pa] [kW/A] [A]<br />

015 760 1120 2520 750 2396 1500 1000 10 2.6 12.5 300 0.6/1.4 0.6/1.4 2.8<br />

025 760 1360 2560 2395 2756 2500 1667 16 4.6 19.1 300 1.1/2.4 1.1/2.4 4.8<br />

030 760 1360 2560 2755 3594 3000 2000 19 5.2 20.6 300 1.5/3.3 1.5/3.3 6.6<br />

037 760 1600 2680 3593 4424 4000 2667 25 6.9 28.9 300 2.2/4.6 2.2/4.6 9.2<br />

045 1080 1360 2680 4423 5391 4800 3200 31 8.7 34.8 300 2.2/4.6 2.2/4.6 9.2<br />

055 1080 1600 2720 5390 6636 6000 4000 38 10.9 43.9 300 3.0/6.4 3.0/6.4 11.0<br />

083 1080 2240 3320 6635 9953 9000 6000 57 16.6 66.5 300 4.0/8.2 4.0/8.2 16.4<br />

100 1400 2240 3360 9952 13271 12000 8000 76 22.5 88.8 300 5.5/11.4 4.0/8.2 19.6<br />

110 1720 2240 3480 13270 16589 15000 10000 95 28.5 110.0 300 5.5/11.4 5.5/11.4 22.8<br />

130 2000 2320 3520 16588 19492 17500 11667 111 32.9 133.2 300 7.5/17.0 7.5/17.0 34.0<br />

150 1720 2880 3840 19491 22118 20000 13333 127 37.3 147.3 300 7.5/17.0 7.5/17.0 34.0<br />

170 2000 2960 3800 22117 25989 23500 15667 150 44.3 177.4 300 11.0/25.0 7.5/17.0 42.0<br />

200 2320 2960 3880 25988 30413 27000 18000 172 51.5 188.2 300 11.0/25.0 11.0/25.0 50.0<br />

230 2640 2960 3880 30412 34836 31500 21000 200 60.2 227.1 300 15.0/29.5 15.0/29.5 59.0<br />

250 2320 3600 4200 34835 38016 35000 23333 223 66.5 242.6 300 15.0/29.5 11.0/25.0 54.5<br />

320 2920 3600 4320 43545 48384 44000 29333 280 84.3 321.9 300 15.0/29.5 15.0/29.5 59.0<br />

Tab. 6: <strong>CAIRfricostar</strong> CWR_SU<br />

conform with VDI 2089,<br />

at rated air flow 1)<br />

Heat recovery system<br />

Reheater 2)<br />

Ext. fresh/supply air;<br />

exhaust/return air; each<br />

Supply air fan, high speed,<br />

at rated volume flow<br />

Exhaust air fan, high speed,<br />

at rated volume flow<br />

Unit total 3)<br />

1) Swimming pool air condition 30 °C/54 %r.h.; Outdoor air condition 5 °C/85 %r.h.<br />

2) Inlet/outlet temperature 70 °C/50 °C; maximum heating capacity; 2 rows<br />

3) plus controls/regulation/pumps etc.<br />

(All data are approximate values and summarize most important features.<br />

Subject to modifications. Exact data are available in the current Lplus design software)<br />

34 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidifier with Air Mixing Function<br />

Type CWR<br />

Unit series CWR…PU. (performance model, maximum air velocity for supply and exhaust air from 2,3 m/s to 2,0 m/s),<br />

plug fans, frequency converters<br />

Type Unit dimensions Air volume flow<br />

Dehumidification<br />

capacity<br />

Heating<br />

capacity<br />

Pressure<br />

drop<br />

Motor rated<br />

power/current<br />

Current<br />

consumption<br />

CWR_PU<br />

Total width<br />

Total height<br />

Total length<br />

Minimum<br />

1) Swimming pool air condition 30 °C/54 %r.h.; Outdoor air condition 5 °C/85 %r.h.<br />

2) Inlet/outlet temperature 70 °C/50 °C; maximum heating capacity; 2 rows<br />

3) plus controls/regulation/pumps etc.<br />

(All data are approximate values and summarize most important features.<br />

Subject to modifications. Exact data are available in the current Lplus design software)<br />

Maximum<br />

Rated (with dehumidification)<br />

Rated (with ventilation)<br />

[mm] [m3/h] [kg/h] [kW] [Pa] [kW/A] (A)<br />

015 760 1120 2520 750 1500 1500 1000 10 2.9 11.9 300 0.6/1.4 0.6/1.4 2.8<br />

025 760 1360 2700 1500 2500 2500 1667 16 5.2 18.0 300 1.1/2.4 1.1/2.4 4.8<br />

030 760 1360 2700 2500 2995 2800 1867 18 5.7 19.5 300 1.5/3.3 1.5/3.3 6.6<br />

037 760 1600 2700 2994 3686 3300 2200 21 6.8 23.2 300 2.2/4.6 1.5/3.3 7.9<br />

045 1080 1360 2800 3685 4493 4200 2800 27 8.8 29.7 300 2.2/4.6 2.2/4.6 9.2<br />

055 1080 1600 2800 4492 5530 5000 3333 32 8.9 36.0 300 2.2/4.6 2.2/4.6 9.2<br />

083 1080 2240 3300 5529 8294 7500 5000 48 15.8 56.3 300 3.0/6.4 3.0/6.4 12.8<br />

100 1400 2240 3500 8293 9953 9900 6600 63 21.2 72.7 300 4.0/8.2 4.0/8.2 16.4<br />

110 1720 2240 3500 9952 11059 11000 7333 70 23.9 86.9 300 4.0/8.2 4.0/8.2 16.4<br />

130 2000 2320 3600 11058 12995 12800 8533 81 27.8 100.4 300 4.0/8.2 4.0/8.2 16.4<br />

150 1720 2880 3600 12994 14746 14500 9667 92 31.4 115.5 300 5.5/11.4 5.5/11.4 22.8<br />

170 2000 2960 3800 14745 17326 17000 11333 108 37.0 132.7 300 5.5/11.4 5.5/11.4 22.8<br />

200 2320 2960 4000 17325 20275 20000 13333 127 43.6 158.9 300 7.5/17.0 5.5/11.4 28.4<br />

230 2640 2960 4000 20274 23224 23000 15333 146 50.2 185.2 300 7.5/17.0 7.5/17.0 34.0<br />

250 2320 3600 4200 23223 25344 25000 16667 159 54.6 199.3 300 7.5/17.0 7.5/17.0 34.0<br />

320 2920 3600 4500 29029 32256 32000 21333 204 70.1 238.2 300 11.0/25.0 11.0/25.0 50.0<br />

Tab. 7: <strong>CAIRfricostar</strong> CWR_PU<br />

Conform with VDI 2089,<br />

at rated air flow 1)<br />

Heat recovery system<br />

Reheater 2)<br />

Ext. fresh/supply air;<br />

exhaust/return air; each<br />

Supply air fan, high speed,<br />

at rated volume flow<br />

Exhaust air fan, high speed,<br />

at rated volume flow<br />

Unit total 3)<br />

Air mixing dehumidifier CWR<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 35


F6<br />

F6<br />

F7<br />

F6<br />

F7<br />

F6<br />

F7<br />

Dehumidifier with Air Mixing Function<br />

Type CWP<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Functional description of the unit<br />

The <strong>GEA</strong> <strong>CAIRfricostar</strong> CWP is designed for various kinds High Performance private<br />

and public swimming pools. The series can be supplied with air volume capacity<br />

between 750 up to 37,500 m³/h. The unit's function is to dehumidify and heat air in<br />

swimming pools in air mixing mode. This unit type is additionally equipped with an efficient<br />

heat recovery system. The unit is delivered with a DDC controls which regulates<br />

all functions of the system on a fully automated basis.<br />

Sample selection of operating modes:<br />

When in idle mode without dehumidification the air is recirculated in the swimming pool.<br />

When the humidity setpoint has been exceeded the unit switches into dehumidification<br />

mode. For this purpose the supply and exhaust air fans are activated to run at high<br />

speed with continuous mixing of outdoor air. The dehumidification stage continues until<br />

the actual humidity value is reduced below that of the humidity setpoint. After that the<br />

fans are deactivated.<br />

In case of overheating of the swimming pool the refrigeration unit is deactivated and<br />

the bypass dampers are permanently open in order to avoid heat recovery system.<br />

Idle mode without dehumidification<br />

demand<br />

Inactive/active mode with low<br />

dehumidification<br />

Active hours operation mode with<br />

dehumidification demand at high<br />

outdoor temperatures<br />

Bypass damper mode, exhaust air fan is deactivated,<br />

supply air fan runs at low speed.<br />

Operation with air mixing damper, exhaust<br />

and supply air fans run at high speed. Compressor<br />

is switched on.<br />

Operation with air mixing damper, exhaust<br />

and supply air fans run at high speed. Regulated<br />

heat recovery using open bypass<br />

dampers for avoiding heat recovery system.<br />

Active hours operation mode with dehumidification<br />

request at high outdoor temperatures<br />

Idle mode in summer and at high outdoor temperatures<br />

F7<br />

F7<br />

F6<br />

Operation with air mixing damper, exhaust and supply air fans run at<br />

high speed. Regulated heat recovery using open bypass dampers for<br />

avoiding heat recovery system.<br />

Outdoor air operation for reaching nominal air temperature.<br />

Double plate heat exchanger is blocked.<br />

36 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidifier with Air Mixing Function<br />

Type CWP<br />

System and controls scheme<br />

M<br />

<br />

M<br />

M<br />

M<br />

p<br />

FU<br />

<br />

<br />

p<br />

+<br />

M<br />

M<br />

p<br />

M<br />

p<br />

FU<br />

p<br />

NE<br />

M<br />

<br />

<br />

M<br />

M<br />

DI<br />

AI<br />

DO<br />

AO<br />

Components<br />

Casing:<br />

Indoor installation<br />

– 50 mm panels, inside and outside skins are painted; (corresponds to RAL 9002),<br />

the series includes casing frame and service door in casing panel thickness together<br />

with a full profile rubber gasket in EPDM quality. All outside and inside surfaces<br />

are <strong>com</strong>pletely smooth.<br />

– Leak tightness class G II according to VDI 3803. Thermal and sound bridges are<br />

minimized.<br />

– Non <strong>com</strong>bustible insulation (fire classification A1 according to DIN 4102; Ö-Norm<br />

B3800; CFC-free)<br />

– Heat transfer coefficient k = 0,57 W/m2 K<br />

– Sound insulation performance Rw = 44 dB according to DIN 52210/T4<br />

– Casing features according to EN1886<br />

– Filter bypass leakage F9<br />

– Leak tightness class according to prEN 1886 (10/2005) L1<br />

– Casing leakage B<br />

– Mechanical stability 1A<br />

– Thermal insulation T2<br />

– Thermal bridging factor TB2 (in risk areas)<br />

– Frame profiles AlMgSi 0,5<br />

– Flexible connector with potential equalisation, temperature resistant from -30 °C to<br />

+120 °C<br />

– Duct connection using 30 mm frame with 4 hole bolt connection<br />

– Interior installation parts for swimming pool mode with special corrosion protection<br />

Air mixing dehumidifier CWP<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 37


Dehumidifier with Air Mixing Function<br />

Type CWP<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Alternative fan unit:<br />

<strong>GEA</strong> „OPTIVENT“ high performance fan impellers<br />

– Surface coated one side suction with backward curved blades that are directly connected<br />

to motor shaft; performance optimized three-phase motor, B3 model type,<br />

protection type IP55, insulation class F adjusted for operation with a frequency converter.<br />

Fan and motor unit including coated intake nozzle mounted on buckling<br />

resistant and coated base construction, motor and fan have sound attenuated bearings.<br />

– Continuous measurement of pressure effects<br />

– Statically and dynamically balanced according to DIN ISO 1940, part 1, G2,5). Continuous<br />

monitoring of operation using DDC. Frequency converter for each motor<br />

installed in or mounted on the unit, control via <strong>GEA</strong> DDC with a separate analogue<br />

signal for both motors. Frequency converters are adjusted and set for both motors.<br />

Limit values for motor current and fan speed are set by the programme<br />

– Resonance frequency band/fade out set by factory<br />

– Automatic energy optimization for optimal energy use and efficiency rate<br />

– Multiple motor operation is possible<br />

– Voltage intermediate circuit converter without reduction of capacity<br />

– Continuous speed control<br />

– Operating hours counter<br />

– Min. and max. speed limitation, automatic ramp curve function UP/DOWN<br />

– Automatic motor adjustment<br />

– Motor tracing switch<br />

– DC break<br />

– Variable clock frequency<br />

– Motor protection<br />

– Short circuit and short circuit to earth safe<br />

– Under and over current protection<br />

– Phase fault monitoring<br />

– Motor coils for reducing speed of voltage rise du/dt (delta voltage/delta time)<br />

– Numerical display for queries and entering of different indicators on operating status:<br />

control setpoint, motor frequency, actual value and setpoint, motor current,<br />

motor torque and capacity, intermediate circuit voltage, thermal motor load, thermal<br />

frequency converter load, control and programmable display with copy function,<br />

production according to ISO 9001, CE Label, net and main shaft protection according<br />

to VDE 0160, radio interference shielding, codes and regulations on electromagnetic<br />

<strong>com</strong>patibility conform with EN 55011 Kl.B-1; EN 50082-2, electric<br />

insulation of control and power <strong>com</strong>ponents according to VDE 0106/0160 (The use<br />

of earth leakage circuit breaker / fuse with frequency converters NOT possible!),<br />

volume flow measuring device via ring measuring line and pressure measuring<br />

point in fan. Calculation and evaluation of volume flow via the <strong>GEA</strong> DDC. The settings<br />

for entire unit are done at the factory. Continuous safety monitoring via safety<br />

chain in the unit. Display and settings via <strong>GEA</strong> DDC.<br />

Air damper system: – Dampers with sealing lips, leakage volume flow 20 m3/h m2 (dp=100 Pa), for circulating<br />

air/bypass, for fresh and exhaust air. Circulating and fresh air rate 0-100%<br />

– Coated AlMg3 damper blades with flow efficient profile, operate in opposite directions.<br />

Driven by double sided, anti-static plastic gears PA6 as fiberglass reinforced<br />

model (resistant to chemicals) including special actuator for each damper<br />

– Control of the individual actuators using continuous DDC signals<br />

Filter for fresh and<br />

exhaust air:<br />

– Filter units conform with VDI 6022<br />

– Including bag filter as of DIN/EN 779, synthetic fiber filter medium<br />

– All filters are fitted with a differential pressure switch for filter monitoring via the DDC<br />

38 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Heat recovery system:<br />

Heating section:<br />

<strong>GEA</strong> motor 3-way mixing<br />

valve:<br />

Control and regulation<br />

system<br />

The switch cabinet is<br />

supplied with the following<br />

main <strong>com</strong>ponents:<br />

Dehumidifier with Air Mixing Function<br />

Type CWP<br />

<strong>GEA</strong> „ECOPLAT2 POWER PLATE“<br />

– 2 symmetric high performance plate heat exchangers for recuperative heat<br />

recovery<br />

2 cross flow aluminium plate heat exchangers (corrosion protected Al99 with best<br />

temperature coefficient) in row switch. Surface is additionally coated with thermoplastic<br />

material. Largest possible heat exchange surface using entire unit depth<br />

with minimum pressure losses. Optimal selection with consideration of operation<br />

conditions. Best efficiency rates within entire outdoor temperature range, especially<br />

resistant to corrosion and wear. Swimming pool configuration.<br />

– „Upside Down“ installation for smaller internal pressure drops.<br />

– AlMg3 ventilation tray<br />

– Technical data checked according to EUROVENT<br />

– Conform with VDI 6022<br />

– Non-<strong>com</strong>bustible according to fire protection regulation<br />

L.P.H.W. air heater, heat exchanger with copper pipes and drawn aluminium fins in<br />

aluminium frame AlMg3 (max. temp. 110°C, Pmax 16 bar) removable in accordance<br />

with VDI 6022;<br />

– For air reheater, supplied loose including actuator 0-10 V with an automatic step<br />

measurement system for fine adjustment of water flow rate<br />

– Supplied loose, installation by others<br />

– Consists of a separate switch cabinet for mounting on units or separate installation<br />

(depending in unit size), with all necessary <strong>com</strong>ponents for control functions, wired<br />

according to VDE specifications. IP55 electrical connection (via plug or screw terminals)<br />

between control cabinet and unit using factory prepared and fully assembled<br />

lines. Electrical installation for voltage supply, valve mixing control, reheater<br />

pump, if necessary external sensor and possibly other functions like remote control<br />

inputs by others. The cabinet is supplied loose depending on the unit size as a<br />

stand alone cabinet or for mounting on the unit<br />

– Main isolating switch for all pole shut-down of the electrical unit, lockable<br />

– Group fuses for fan and <strong>com</strong>pressor<br />

– Fuses for reheater 230V/N/PE/50Hz (types 015-083)<br />

3 X 400V/NPE/50Hz (types 100-320)<br />

(if necessary - motor protection by others)<br />

– Control fuses, control transformer 230 V and control voltage supply<br />

unit 24V DC for the digital control<br />

– Control fuse and control voltage supply unit 24V AC for actuators<br />

– Automatic phase controller (option)<br />

– Indoor installation, frost free<br />

Air mixing dehumidifier CWP<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 39


Dehumidifier with Air Mixing Function<br />

Type CWP<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Digital control: – Modular automation station built into switch cabinet with deletion-proof software<br />

modules and digital and analogue inputs and outputs, equipped with all control<br />

functions for swimming pool dehumidifier, consisting of:<br />

– Control unit with 32 bit processor in network based, interdisciplinary, free programmable<br />

automation system<br />

– Watchdog function, data buffering (FLASH-ROM), hardware clock<br />

– Interfaces:<br />

1 x CAN (Controller Area Network) as central bus between control unit and I/O<br />

modules;<br />

1 x LIN (Local Interconnect Network) for auxiliary module monitoring and configuration<br />

functions;<br />

1 x CAN for external connection;<br />

2 x RS232/RS485, one RS232 has modem function;<br />

Optional - Ethernet; USB plug;<br />

Optional - various <strong>com</strong>munication functions can be carried out (e. g: OPC; LON;<br />

MODBUS; OSPA; BACnet®) As BACnet®-Building Controller (B-BC) the system<br />

can cost efficiently intgerate or be integrated in any BACnet® third system.<br />

– In and output modules with an integrated microcontroller and memory for recording<br />

a programme specifically designed for the relevant module, status display for<br />

every input or output with CAN provided via top hat rail bus plug.<br />

– Comfortable intelligent control terminal for supporting display, control buttons and<br />

data transfer, installed in the door of the switch cabinet<br />

– Alufront panel with front film<br />

– Keyboard connection via plug connector<br />

– Front side protection type IP 65<br />

– LCD-Display with 8 lines each with 40 symbols as clear text display, monochrome<br />

– 6 function buttons<br />

– Colour background lighting, adjustable, automatic lighting activation<br />

– Adjustable LCD contrast<br />

– System bus CAN<br />

– Alternative (option): as before, but:<br />

– with <strong>com</strong>fortable touch control terminal<br />

– LCD display with 16 colours<br />

– Graphical resolution 320 x 240 Pixel<br />

40 PR-2008-0327-GB • Subject to modifications • Status 05/2009


Air mixing dehumidifier CWP<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Control and regulation<br />

functions:<br />

Dehumidifier with Air Mixing Function<br />

Type CWP<br />

– Status and fault signals in clear text<br />

– Indication of all status and control parameters<br />

– Stepwise access authorization using code<br />

– Integrated clock timer<br />

– Automatic summer / winter time switch-over, activation of weekly programmes,<br />

holiday and special day programmes<br />

– Log for registration of faults with date and time<br />

– Operating hours counter, total operation and maintenance intervals<br />

– Data logging function for most important parameters, can be downloaded<br />

– Separate controls for supply and exhaust air fan motors<br />

– Air volume adjustment and display in m³/h, including monitoring for units with frequency<br />

converters<br />

– Fan motor monitoring using PTC resistor and motor protection relay<br />

– Filter monitoring<br />

– Regulation of air mixing dampers with selectable minimum fresh air rate and maximum<br />

limitation, automatic control depending on conditions of fresh air and swimming<br />

pool air<br />

– Control sequence with energy recovery, heater, bypass damper and air mixing<br />

damper system<br />

– Exhaust air temperature cascade control with min./max. limitation of supply air temperature<br />

– Cooling with outside air (night cooling)<br />

– Reheater-heat pump consumption control with blockage protection functions<br />

– Continuous humidity control<br />

– Automatic switch-over between active/non-active hours operation<br />

– Continuous inactive idle mode possible<br />

– Different languages can be selected<br />

– Commissioning function for air dampers<br />

– Inputs: external emergency switch off (e.g. fire protection damper or chlorine gas<br />

alarm)<br />

– Motor monitoring for reheater pump can be switched, if required motor protection<br />

by others<br />

– The necessary sensors and actuators are built into the unit or, if necessary, supplied<br />

loose with subsequent installation by others<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 41


Dehumidifier with Air Mixing Function<br />

Type CWP<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Technical data<br />

Unitz series CWP…VU. (performance model, maximum air velocity for supply and exhaust air from 2,5 m/s to 2,0 m/s),<br />

plug fans, frequency converters<br />

Type Unit dimensions Air volume flow<br />

Dehumidification<br />

capacity<br />

Heating<br />

capacity<br />

Pressure<br />

drop<br />

Motor rated<br />

power/current<br />

Current consumption<br />

CWP_VU<br />

Total width<br />

Total height<br />

Total length<br />

Minimum<br />

Maximum<br />

Rated (with dehumidification)<br />

Rated (with ventilation)<br />

Conform with VDI 2089,<br />

at rated air flow 1)<br />

[mm] [m3/h] [kg/h] [kW] [Pa] [kW/A] [A]<br />

015 760 1120 3600 750 1500 1000 667 6 2.1 8.4 300 0.6/1.4 0.6/1.4 2.8<br />

025 760 1360 3800 1500 2500 2500 1667 16 5.1 15.4 300 1.1/2.4 1.1/2.4 4.8<br />

037 760 1600 4100 2500 3686 3400 2267 22 6.8 21.2 300 1.5/3.4 1.1/2.4 5.8<br />

055 1080 1600 4200 3685 5530 5000 3333 32 10.1 31.6 300 2.2/4.7 1.5/3.4 8.1<br />

083 1080 2240 5700 5529 8294 7500 5000 48 15.3 48.9 300 3.0/6.4 3.0/6.4 12.8<br />

110 1720 2240 5700 8293 11059 11000 7333 70 25.3 78.9 300 4.0/8.2 3.0/6.4 14.6<br />

130 2000 2320 6000 11058 12995 12500 8333 80 26.1 90.9 300 4.0/8.2 4.0/8.2 16.4<br />

150 1720 2880 6600 12994 14746 14000 9333 89 30.0 98.1 300 5.5/11.4 5.5/11.4 22.8<br />

170 2000 2960 6800 14745 17326 17000 11333 108 36.4 120.7 300 7.5/17.0 5.5/11.4 28.4<br />

230 2320 2960 7100 17325 20275 20000 13333 127 42.8 139.3 300 7.5/17.0 7.5/17.0 34.0<br />

250 2320 3600 7400 20274 25344 25000 16667 159 49.9 180.4 300 7.5/17.0 7.5/17.0 34.0<br />

320 2920 3600 8200 29029 32256 32000 21333 204 65.0 234.5 300 11.0/25.0 11.0/25.0 50.0<br />

Tab. 8: Technical data <strong>CAIRfricostar</strong> CWP_VU<br />

Heat recovery system<br />

Reheater 2)<br />

Ext. fresh/supply air;<br />

exhaust/return air; each<br />

Supply air fan, high speed,<br />

at rated volume flow<br />

Exhaust air fan, high speed,<br />

at rated volume flow<br />

Unit total 3)<br />

1) Swimming pool air condition 30 °C/54 %r.h.; Outdoor air condition 5 °C/85 %r.h.<br />

2) Inlet/outlet temperature 70 °C/50 °C; maximum heating capacity; 2 rows<br />

3) plus controls/regulation/pumps etc.<br />

(All data are approximate values and summarize most important features.<br />

Subject to modifications. Exact data are available in the current Lplus design software)<br />

42 PR-2008-0327-GB • Subject to modifications • Status 05/2009


Air mixing dehumidifier CAC<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidification Unit with Air Mixing Function<br />

Type CAC<br />

Functional description of the unit<br />

The <strong>GEA</strong> <strong>CAIRfricostar</strong> CAC is designed for private and small public swimming pools.<br />

The series is available in 2 model and 3 capacity sizes. The unit's function is to dehumidify<br />

and heat air in swimming pools in air mixing mode. The unit is delivered with a<br />

DDC controls which regulates all functions of the system on a fully automated basis.<br />

When in idle mode without dehumidification the air is recirculated in the swimming pool.<br />

When the humidity setpoint has been exceeded the unit switches into dehumidification<br />

mode. At this point the supply air fan is switched into speed 2 with the exhaust air fan<br />

maintaining air circulation at speed 1. The refrigeration unit is activated in order to start<br />

dehumidification. Using the bypass damper a certain part of return air is mixed without<br />

further treatment with dehumidified air that has passed through the refrigeration cycle.<br />

The dehumidification stage continues until the actual humidity value lies below that of<br />

the humidity setpoint. Then fans and refrigeration unit are deactivated.<br />

When in active hours swimming pool mode the fresh and exhaust air dampers are<br />

opened, the bypass damper is closed. The dehumidification takes place via the<br />

activation of the refrigeration cycle with both fans switched into speed 2.<br />

Using an optional pool water condenser a certain amount of excess energy produced<br />

by the refrigeration cycle can be fed back into swimming pool water.<br />

Sample selection of operation modes:<br />

Idle mode without dehumidification<br />

demand<br />

Idle mode with dehumidification<br />

demand<br />

Active hours swimming pool mode<br />

with humidification demand and pool<br />

water condenser<br />

Bypass damper mode, exhaust air fan is deactivated,<br />

supply air fan runs at low speed.<br />

Bypass damper mode, exhaust air fan runs at<br />

low speed, supply air fan runs at high speed.<br />

Compressor is switched on. The reheater<br />

provides the missing residual heat supply.<br />

Air mixing operation according to VDI,<br />

exhaust and supply air fans run at high<br />

speed. Compressor is switched on. The reheater<br />

provides the missing residual heat<br />

supply. Using a pool water condenser a certain<br />

amount of excess energy can be fed<br />

back into swimming pool water.<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 43


Dehumidification Unit with Air Mixing Function<br />

Type CAC<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Transition/summer mode with/without dehum demand<br />

Summer mode inactive period „free night cooling“<br />

In case of overheating of the swimming pool and high outdoor temperatures<br />

the heat pump is blocked. The unit operates for ventilation<br />

and dehumidification in air mixing or only outdoor/exhaust air mode.<br />

The fans run at high speed. In case of an optional bypass of the heat<br />

recovery system the heat recovery is not used thanks to a damper<br />

system and at the same time the air volume flow is increased.<br />

If the swimming pool is overheated during the night time or idle period<br />

the unit ventilates only in outdoor/exhaust air mode. The fans run at<br />

high speed and provide cooling of the swimming pool to reach the<br />

setpoint temperature. In case of an optional bypass of the heat recovery<br />

system the heat recovery is not used thanks to a damper system<br />

and at the same time the air volume flow is increased.<br />

System and controls scheme<br />

Components<br />

Casing:<br />

Indoor installation<br />

– 50 mm panels, inside and outside skins are painted; (corresponds to RAL 9002),<br />

the series includes casing frame and service door in casing panel thickness together<br />

with a full profile rubber gasket in EPDM quality. All outside and inside surfaces<br />

are <strong>com</strong>pletely smooth.<br />

– Leak tightness class G II according to VDI 3803. Thermal and sound bridges are<br />

minimized.<br />

– Non <strong>com</strong>bustible insulation (fire classification A1 according to DIN 4102; Ö-Norm<br />

B3800; CFC-free)<br />

– Heat transfer coefficient k = 0,57 W/m2 K<br />

– Sound insulation performance Rw = 44 dB according to DIN 52210/T4<br />

– Casing features according to EN1886<br />

– Filter bypass leakage F9<br />

– Leak tightness class according to prEN 1886 (10/2005) L1<br />

– Casing leakage B<br />

– Mechanical stability 1A<br />

– Thermal insulation T2<br />

– Thermal bridging factor TB2 (in risk areas)<br />

44 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidification Unit with Air Mixing Function<br />

Type CAC<br />

– Frame profiles AlMgSi 0,5<br />

– Flexible connector with potential equalisation, temperature resistant from -30 °C to<br />

+120 °C<br />

– Duct connection using 30 mm frame with 4 hole bolt connection<br />

– Interior installation parts for swimming pool mode with special corrosion protection<br />

Heat pump for<br />

dehumidification:<br />

– Direct evaporator according to VDI 6022: heat exchanger as Cu/Alu model for R<br />

407c refrigerant, fins made of aluminium, frame elements made of AlMg3, pipes<br />

made of oxygen-free copper.<br />

– Condensate water tray in bottom panel for evaporator and heat recovery system,<br />

with a slope in the direction of condensate drain, made of stainless steel V4A<br />

powder coated, including drain tray, conform with VDI 6022<br />

– Air-cooled condenser according to VDI 6022: heat exchanger as Cu/Alu model for<br />

R 407c refrigerant, fins made of aluminium, frame elements made of AlMg3, pipes<br />

made of oxygen-free copper<br />

– Compressor unit: refrigeration circuit with a fully hermetic scroll <strong>com</strong>pressor<br />

– with optimized heat exchanger <strong>com</strong>bination for maximum COP values, mounted on<br />

anti-vibration mounts, circuit includes filter drier, liquid collector, thermostatic<br />

expansion valve with MOP and external pressure equalisation, all necessary<br />

shut-off valves, monitoring and safety devices (pressostat, icing sensor, etc.)<br />

Droplet eliminator – made of plastic with an aluminium frame at air velocities on supply and exhaust side<br />

exceeding 2,5 m/s is necessary<br />

Fan unit:<br />

<strong>GEA</strong> centrifugal fan „LESS ENERGY SYSTEM“<br />

– Optimized operating point, double side suction, coated surface model<br />

– Three phase motor, protection class IP55 , model type B3, <strong>com</strong>plete belt drive, easy<br />

service thanks to one bolt tensioning sled<br />

– Fan/motor unit mounted on anti-vibration mounts<br />

Air damper system: – Dampers with sealing lips, leakage volume flow 20 m 3 /h m2 (dp=100 Pa), for circulating<br />

air/bypass, for fresh and exhaust air. Circulating and fresh air rate 0-100%<br />

– Coated Almg3 damper blades with flow efficient profile, operate in opposite directions.<br />

Driven by double sided, anti-static plastic gears PA6 as fiberglass reinforced<br />

model (resistant to chemicals) including special actuator for each damper<br />

– Control of the individual actuators using continuous DDC signals<br />

Filter for fresh and<br />

exhaust air:<br />

– Filter units conform with VDI 6022<br />

– including bag filter as of DIN/EN 779, synthetic fiber filter medium<br />

– All filters are fitted with a differential pressure switch for filter monitoring via the DDC<br />

Heat recovery system:<br />

<strong>GEA</strong> „ECOPLAT POWER PLATE“<br />

– symmetric high performance plate heat exchangers, recuperative heat recovery by<br />

using two cross-flow aluminium plate heat exchangers (corrosion protected Al99<br />

with best temperature coefficient). Surface is additionally coated with thermoplastic<br />

material. Largest possible heat exchange surface using entire unit depth with minimum<br />

pressure losses. Optimal selection with consideration of operation conditions.<br />

Best efficiency rates within entire outdoor temperature range, especially resistant to<br />

corrosion and wear. Swimming pool configuration.<br />

– AlMg3 ventilation tray<br />

– technical data checked according to EUROVENT<br />

– conform with VDI 6022<br />

– Non-<strong>com</strong>bustible according to fire protection regulation<br />

Heating section: – L.P.H.W. air heater, heat exchanger with copper pipes and drawn aluminium fins in<br />

aluminium frame AlMg3 (max. temp. 110°C, Pmax 16bar) removable in accordance<br />

with VDI6022;<br />

Air mixing dehumidifier CAC<br />

<strong>GEA</strong> motor -3-way mixing<br />

valve:<br />

– For air reheater, supplied loose including actuator 0-10 V with an automatic step<br />

measurement system for fine adjustment of water flow rate<br />

– supplied loose, installation by others<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 45


Dehumidification Unit with Air Mixing Function<br />

Type CAC<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Control and regulation system:<br />

The switch cabinet is<br />

supplied with the following<br />

main <strong>com</strong>ponents:<br />

– Consists of a separate switch cabinet for mounting on units or separate installation<br />

(depending in unit size), with all necessary <strong>com</strong>ponents for control functions, wired<br />

according to VDE specifications. IP55. Electrical connection (via plug or screw<br />

terminals) between control cabinet and unit using factory prepared lines. Electrical<br />

installation for voltage supply, valve mixing control, reheater pump, if necessary<br />

external sensor for the pool water pump and possibly other functions like remote<br />

control inputs to be installed by others. The cabinet is supplied loose depending on<br />

the unit size as a stand alone cabinet or for mounting on the unit;<br />

– Main isolating switch for all pole shut-down of the electrical unit, lockable<br />

– Group fuses for fan and <strong>com</strong>pressor<br />

– Fuses for reheater and PWC pump 230V/N/PE/50Hz (types 015-083) (if necessary<br />

- motor protection by others)<br />

– Control fuses, control transformer 230 V and control voltage supply unit 24V DC for<br />

the digital control<br />

– Control fuse and control supply voltage unit 24V AC for actuators<br />

– Automatic phase controller (option)<br />

– Indoor installation, frost free<br />

Digital control: – Modular automation station built into switch cabinet with deletion-proof software<br />

modules and digital and analogue inputs and outputs, equipped with all control<br />

functions for swimming pool dehumidifier, consisting of:<br />

– Control unit with 32 bit processor in network based, interdisciplinary, free programmable<br />

automation system<br />

– Watchdog function, data buffering (FLASH-ROM), hardware clock<br />

– Interface:1 x CAN (Controller Area Network) as a central bus between control<br />

unit and I/O modules; 1 x LIN (Local Interconnect Network) for additional module<br />

monitoring and configuration functions;1 x CAN for external integration;<br />

– 2 x RS232/RS485, RS232 can operate with a modem<br />

– Optional: Ethernet; USB plug<br />

– As an optional various <strong>com</strong>munication functions can be implemented (e.g: OPC;<br />

LON; MODBUS; OSPA; BACnet ® ). As a native BACnet ® -Building Controller<br />

(B-BC) the system can integrate every BACnet ® third system with little extra<br />

expense or can integrate itself in such a system.<br />

– In and output modules with an integrated microcontroller and memory for recording<br />

a programme specifically designed for the relevant module. Status indicator<br />

for every input or output. CAN provided via top hat-rail bus plug.<br />

– Comfortable intelligent control terminal for supporting display, control buttons and<br />

data transfer, installed in the door of the switch cabinet<br />

– Alufront panel with front foíl<br />

– Keyboard connection via plug connector<br />

– Front side protection type IP 65<br />

– LCD-Display with 8 lines each with 40 symbols as clear text display, monochrome<br />

– 6 function buttons<br />

– Colour background lighting, adjustable, automatic lighting activation<br />

– Adjustable LCD contrast<br />

– System bus CAN<br />

– Alternative (option): as before, but:<br />

– with <strong>com</strong>fortable touch control terminal<br />

– LCD display with 16 colours<br />

– Graphical resolution 320 x 240 Pixel<br />

46 PR-2008-0327-GB • Subject to modifications • Status 05/2009


Air mixing dehumidifier CAC<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Control and regulation<br />

functions:<br />

Dehumidification Unit with Air Mixing Function<br />

Type CAC<br />

– Status and fault signals in clear text<br />

– Indication of all status and control parameters<br />

– Stepwise access authorization using code<br />

– Integrated clock timer<br />

– Automatic summer / winter time switch-over, activation of weekly programmes,<br />

holiday and special day programmes<br />

– Log for registration of faults with date and time<br />

– Operating hours counter, total operation and maintenance intervals<br />

– Data logging function for most important parameters, can be downloaded<br />

– Separate controls for supply and exhaust air fan motors<br />

– Air volume adjustment and display in m³/h, including monitoring for units with frequency<br />

converters<br />

– Fan motor monitoring using PTC resistor and motor protection relay<br />

– Filter monitoring<br />

– Compressor control (heat pump) with minimum run / standstill time<br />

– Regulation of air mixing dampers with selectable minimum fresh air rate and maximum<br />

limitation, automatic control depending on conditions of fresh air and swimming<br />

pool air<br />

– Control sequence with energy recovery, heater, <strong>com</strong>pressor (heat pump), bypass<br />

damper and air mixing damper system<br />

– Exhaust air temperature cascade control with min./max. limitation of supply air temperature<br />

– Cooling with outside air (night cooling)<br />

– Reheater-heat pump consumption control with blockage protection functions<br />

– Continuous humidity control<br />

– On demand - controls for automatic pool water pump with block up protection<br />

– Automatic switch-over between active/non-active hours operation<br />

– Continuous inactive/idle mode possible<br />

– Different languages can be selected<br />

– Commissioning function for air dampers<br />

– Inputs: external emergency switch off (e.g. fire protection damper or chlorine gas<br />

alarm)<br />

– Motor monitoring for NE pump can be switched, if required motor protection<br />

by others<br />

– Motor monitoring for pool water pump can be switched, if required motor protection<br />

by others<br />

– The necessary sensors and actuators are built into the unit or, if necessary,<br />

supplied loose with subsequent installation by others<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 47


Dehumidification Unit with Air Mixing Function<br />

Type CAC<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Technical data<br />

Unit series CAC...S..<br />

Typ<br />

e Unit dimensions Air volume flow Dehumidification<br />

capacity<br />

Heating capacity<br />

Pressure<br />

drop<br />

Motor rated power/<br />

current<br />

Current<br />

consumption<br />

CAC_S<br />

Total width<br />

Total height<br />

Total length<br />

Minimum<br />

Maximum<br />

Rated (with dehumidification)<br />

Rated (with ventilation)<br />

according to VDI 2089,<br />

at nominal air capacity 1)<br />

Active hours mode (30 % fresh air) /<br />

idle/inactive mode (circulating air)<br />

/VDI 2089<br />

[mm] [m3/h] [kg/h] [kW] [Pa] [kW/A] [A]<br />

015 760 1480 1640 750 1600 1000 743 6 6.5 / 3.7 / 6 5.4 3.3 2.4 3.0 10.0 300 0.6/1.4 0.6/1.4 2.8<br />

025 760 1800 2760 1600 2500 2000 1320 13 11.6 / 5.9 / 13 10.0 7.2 3.2 5.9 16.2 300 1.1/2.4 1.1/2.4 4.8<br />

037 760 1800 2760 2000 3600 3050 2013 19 16.8 / 6.8 / 19 12.1 10.1 3.0 6.9 23.2 300 1.5/3.4 1.1/2.4 5.8<br />

Tab. 1: Technical data <strong>CAIRfricostar</strong> CAC_S<br />

Air condenser, with inactive<br />

pool water condenser<br />

Air condenser, with active<br />

pool water condenser<br />

Pool water condenser<br />

(accessory)<br />

Heat recovery system<br />

Reheater 2)<br />

Ext. fresh/supply air;<br />

exhaust/return air; each<br />

Supply air fan, high speed,<br />

at rated volume flow<br />

Exhaust air fan, high speed,<br />

at rated volume flow<br />

Unit total 3)<br />

1) Swimming pool air condition 30 °C/54 %r.h.; Outdoor air condition 5 °C/85 %r.h.<br />

2) Inlet/outlet temperature 70 °C/50 °C; maximum heating capacity; 2 rows<br />

3) plus controls/regulation/pumps etc.<br />

(All data are approximate values and summarize most important features. Subject to modifications.<br />

Exact data are available in the current Lplus design software)<br />

48 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidification Unit with Air Mixing and Heat Pump Function<br />

Type CWC<br />

Functional description of the unit<br />

The <strong>GEA</strong> <strong>CAIRfricostar</strong> CWC is designed for private and small public swimming pools.<br />

The series is available in 2 sizes. The unit's function is to dehumidify and heat air in<br />

swimming pools in air mixing mode. The unit is delivered with a DDC controls which<br />

regulates all functions of the system on a fully automated basis.<br />

Sample selection of operation modes:<br />

This unit type is additionally equipped with an efficient heat recovery system. When in<br />

idle mode without dehumidification the air is recirculated in the swimming pool. When<br />

the humidity setpoint has been exceeded the unit switches into dehumidification mode.<br />

For this purpose the supply and exhaust air fans are activated to run at high speed with<br />

continuous mixing of outdoor air. The dehumidification stage continues until the actual<br />

humidity value lies below that of the humidity setpoint. After that the fans are deactivated.<br />

Idle mode without dehumidification<br />

demand<br />

Active hours operation mode with<br />

dehumidification demand<br />

Idle mode with dehumidification<br />

demand<br />

Bypass damper mode, exhaust air fan<br />

is deactivated,<br />

Supply air fan runs at low speed.<br />

Air mixing operation according to VDI, exhaust<br />

and supply air fans run at high speed.<br />

The reheater provides the missing residual<br />

heat supply.<br />

Air mixing operation, exhaust and supply air<br />

fans are operating at high speed. The reheater<br />

provides the missing residual heat supply.<br />

Active hours/summer operation mode<br />

Summer mode / inactive operating „free night cooling“<br />

Fresh air mode, exhaust and supply air fans run at high speed. Heat<br />

recovery is not used thanks to a damper system.<br />

If the swimming pool is overheated during the night time or idle period<br />

the unit ventilates only in outdoor/exhaust air mode. The fans run at<br />

high speed and provide cooling of the swimming pool to reach the<br />

setpoint temperature. In case of an optional bypass of the heat recovery<br />

system the heat recovery is not used thanks to a damper system<br />

and at the same time the air volume flow is increased.<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 49<br />

Air mixing dehumidifier CWC


Dehumidification Unit with Air Mixing and Heat Pump Function<br />

Type CWC<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

System and controls scheme<br />

Components<br />

Casing:<br />

Indoor installation<br />

– 50 mm panels, inside and outside skins are painted; (corresponds to RAL 9002),<br />

the series includes casing frame and service door in casing panel thickness together<br />

with a full profile rubber gasket in EPDM quality. All outside and inside surfaces<br />

are <strong>com</strong>pletely smooth.<br />

– Leak tightness class G II according to VDI 3803. Thermal and sound bridges are<br />

minimized.<br />

– Non <strong>com</strong>bustible insulation (fire classification A1 according to DIN 4102; Ö-Norm<br />

B3800; CFC-free)<br />

– Heat transfer coefficient k = 0,57 W/m2 K<br />

– Sound insulation performance Rw = 44 dB according to DIN 52210/T4<br />

– Casing features according to EN1886<br />

– Filter bypass leakage F9<br />

– Leak tightness class according to prEN 1886 (10/2005) L1<br />

– Casing leakage B<br />

– Mechanical stability 1A<br />

– Thermal insulation T2<br />

– Thermal bridging factor TB2 (in risk areas)<br />

– Frame profiles AlMgSi 0,5<br />

– Flexible connector with potential equalisation, temperature resistant<br />

from -30 °C to +120 °C<br />

– Duct connection using 30 mm frame with 4 hole bolt connection<br />

– Interior installation parts for swimming pool mode with special corrosion protection<br />

Droplet eliminator – made of plastic with an aluminium frame at air velocities on supply and exhaust side<br />

exceeding 2,5 m/s is necessary<br />

Fan unit:<br />

<strong>GEA</strong> centrifugal fan „LESS ENERGY SYSTEM“<br />

– Optimized operating point, double side suction, coated surface model<br />

– Three phase motor, protection class IP55 , model type B3, <strong>com</strong>plete belt drive, easy<br />

service thanks to one bolt tensioning sled<br />

– Fan/motor unit mounted on anti-vibration mounts<br />

Air damper system: – Dampers with sealing lips, leakage volume flow 20 m 3 /h m2 (dp=100 Pa), for circulating<br />

air/bypass, for fresh and exhaust air. Circulating and fresh air rate 0-100%<br />

50 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidification Unit with Air Mixing and Heat Pump Function<br />

Type CWC<br />

– Coated Almg3 damper blades with flow efficient profile, operate in opposite directions.<br />

Driven by double sided, anti-static plastic gears PA6 as fiberglass reinforced<br />

model (resistant to chemicals) including special actuator for each damper<br />

– Control of the individual actuators using continuous DDC signals<br />

Filter for fresh and<br />

exhaust air:<br />

– Filter units conform with VDI 6022<br />

– including bag filter as of DIN/EN 779, synthetic fiber filter medium<br />

– All filters are fitted with a differential pressure switch for filter-monitoring via the<br />

DDC<br />

Heat recovery system: <strong>GEA</strong> „ECOPLAT POWER PLATE“:<br />

– symmetric high performance plate heat exchangers, recuperative heat recovery by<br />

using two cross-flow aluminium plate heat exchangers (corrosion protected Al99<br />

with best temperature coefficient). Surface is additionally coated with thermoplastic<br />

material. Largest possible heat exchange surface using entire unit depth with minimum<br />

pressure losses. Optimal selection with consideration of operation conditions.<br />

Best efficiency rates within entire outdoor temperature range, especially resistant to<br />

corrosion and wear. Swimming pool configuration.<br />

– AlMg3 ventilation tray<br />

– technical data checked according to EUROVENT<br />

– conform with VDI 6022<br />

– Non-<strong>com</strong>bustible according to fire protection regulation<br />

Heating section: – L.P.H.W. air heater, heat exchanger with copper pipes and drawn aluminium fins in<br />

aluminium frame AlMg3 (max. temp. 110°C, Pmax 16bar) removable in accordance<br />

with VDI6022;<br />

<strong>GEA</strong> motor -3-way mixing<br />

valve:<br />

Control and<br />

regulation system<br />

The switch cabinet is<br />

supplied with the following<br />

main <strong>com</strong>ponents:<br />

– For air reheater, supplied loose including actuator 0-10 V with an automatic step<br />

measurement system for fine adjustment of water flow rate<br />

– supplied loose, installation by others<br />

– Consists of a separate switch cabinet for mounting on units or separate installation<br />

(depending in unit size), with all necessary <strong>com</strong>ponents for control functions, wired<br />

according to VDE specifications. IP55 electrical connection (via plug or screw terminals)<br />

between control cabinet and unit using factory prepared lines. Electrical<br />

installation for voltage supply, valve mixing control, reheater pump, if necessary<br />

external sensor and possibly other functions like remote control inputs are provided<br />

by others. The cabinet is supplied loose depending on the unit size as a stand alone<br />

cabinet or for mounting on the unit;<br />

– Main isolating switch for all pole shut-down of the electrical unit, lockable<br />

– Group fuses for fans<br />

– Fuses for reheater 230V/N/PE/50Hz (types 015-083) 3 X 400V/NPE/50Hz (types<br />

100-320) (if necessary - motor protection by others)<br />

– Control fuses, control transformer 230 V and control voltage supply unit 24V DC for<br />

the digital control<br />

– Control fuse and control voltage supply unit 24V AC for actuators<br />

– Automatic phase controller (option)<br />

– Indoor installation, frost free<br />

Digital control: – Modular automation station built into switch cabinet with deletion-proof software<br />

modules and digital and analogue inputs and outputs, equipped with all control<br />

functions for swimming pool dehumidifier, consisting of:<br />

– Control unit with 32 bit processor in network based, interdisciplinary, free programmable<br />

automation system<br />

– Watchdog function, data buffering (FLASH-ROM), hardware clock<br />

– Interfaces: 1 x CAN (Controller Area Network) as central bus between control<br />

unit and I/O modules; 1 x LIN (Local Interconnect Network) for auxiliary module<br />

monitoring and configuration functions; 1 x CAN for external connection; 2 x<br />

RS232/RS485, one RS232 has modem function; optional: Ethernet; USB plug;<br />

optionally - various <strong>com</strong>munication functions can be carried out (e. g: OPC;<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 51<br />

Air mixing dehumidifier CWC


Dehumidification Unit with Air Mixing and Heat Pump Function<br />

Type CWC<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

LON; MODBUS; OSPA; BACnet®) As BACnet®-Building Controller (B-BC) the<br />

system can cost efficiently integrate or be integrated in any BACnet® third system.<br />

– In and output modules with an integrated microcontroller and memory for recording<br />

a programme specifically designed for the relevant module, status display for<br />

every input or output with CAN provided via top hat rail bus plug.<br />

– Comfortable intelligent control terminal for supporting display, control buttons and<br />

data transfer, installed in the door of the switch cabinet<br />

– Alufront panel with front foíl<br />

– Keyboard connection via plug connector<br />

– Front side protection type IP 65<br />

– LCD-Display with 8 lines each with 40 symbols as clear text display, monochrome<br />

– 6 function buttons<br />

– Colour background lighting, adjustable, automatic lighting activation<br />

– Adjustable LCD contrast<br />

– System bus CAN<br />

– Alternative (option): as before, but:<br />

– with <strong>com</strong>fortable touch control terminal<br />

– LCD display with 16 colours<br />

– Graphical resolution 320 x 240 Pixel<br />

52 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Control and regulation<br />

functions:<br />

Dehumidification Unit with Air Mixing and Heat Pump Function<br />

Type CWC<br />

– Status and fault signals in clear text<br />

– Indication of all status and control parameters<br />

– Stepwise access authorization using code<br />

– Integrated clock timer<br />

– Automatic summer / winter time switch-over, activation of weekly programmes, holiday<br />

and special day programmes<br />

– Log for registration of faults with date and time<br />

– Operating hours counter, total operation and maintenance intervals<br />

– Data logging function for most important parameters, can be downloaded<br />

– Separate controls for supply and exhaust air fan motors<br />

– Air volume adjustment and display in m³/h, including monitoring for units with frequency<br />

converters<br />

– Fan motor monitoring using PTC resistor and motor protection relay<br />

– Filter monitoring<br />

– Automatic regulation depending on conditions of fresh air and swimming pool air<br />

– Control sequence with energy recovery, heater and bypass damper<br />

– Exhaust air temperature cascade control with min./max. limitation of supply air temperature<br />

– Cooling with outside air (night cooling)<br />

– Reheater-heat pump consumption control with blockage protection functions<br />

– Continuous humidity control<br />

– Automatic switch-over between active/non-active hours operation<br />

– Continuous inactive/idle mode possible<br />

– Different languages can be selected<br />

– Commissioning function for air dampers<br />

– Inputs: external emergency switch off (e.g. fire protection damper or chlorine gas<br />

alarm)<br />

– Motor monitoring for NE pump can be switched, if required motor protection<br />

by others<br />

– The necessary sensors and actuators are built into the unit or, if necessary,<br />

supplied loose with subsequent installation by others<br />

Technical data<br />

Unit series CWC…S..<br />

Dehumidification<br />

capacity drop<br />

Heating capacity Pres-<br />

sure<br />

Type Unit dimensions Air volume flow<br />

Motor rated power/current<br />

Current<br />

consumption<br />

CWC_S<br />

Total width<br />

Total height<br />

Total length<br />

Minimum<br />

Maximum<br />

Rated (with dehumidification)<br />

Rated (with ventilation)<br />

according to VDI 2089,<br />

at nominal air capacity 1)<br />

[mm] [m3/h] [kg/h] [Pa] [kW/A] [A]<br />

015 760 1480 1640 750 2000 1500 1000 9.5 2.8 16.0 300 0.6/1.4 0.6/1.4 1.3/2.5 5.3<br />

037 760 1800 2760 1500 3600 2500 1667 16 4.8 23.0 300 3.0/6.1 2.2/4.6 2.3/4.5 15.2<br />

Tab. 1: Technical data <strong>CAIRfricostar</strong> CWC_S<br />

1) Swimming pool air condition 30 °C/54 %r.h.; Outdoor air condition 5 °C/85 %r.h.<br />

2) Inlet/outlet temperature 70 °C/50 °C; maximum heating capacity; 2 rows<br />

3) plus controls/regulation/pumps etc.<br />

(All data are approximate values and summarize most important features. Subject to modifications. Exact data are available in the current Lplus<br />

design software<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 53<br />

Heat recovery system<br />

Reheater 2)<br />

Ext. fresh/supply air;<br />

exhaust/return air; each<br />

Supply air fan, high speed,<br />

at rated volume flow<br />

Exhaust air fan, high speed,<br />

at rated volume flow<br />

Compressor, without<br />

pool water condenser<br />

Unit total 3)<br />

Air mixing dehumidifier CWC


Electrical Integration<br />

Overview of Cable Connections<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

<strong>GEA</strong> <strong>CAIRfricostar</strong> Air mixing units<br />

NOTE!<br />

Only the unit wiring diagram provides exact information about the unit delivery<br />

state.<br />

The switch cabinet is supplied loose! (special configuration includes intermediate<br />

terminal box) Use the enclosed documentation for detailed information about the<br />

installation of the switch cabinet.<br />

Unit size 015-083 with swing switch cabinet on the unit<br />

Unit size 100-360 with upright switch cabinet near the unit<br />

*<br />

9<br />

Fig. 1:<br />

Swing switch cabinet<br />

1<br />

3<br />

4<br />

( )<br />

5 5<br />

2<br />

8<br />

7<br />

on Fig. 1: Swing unit<br />

6<br />

11 10<br />

Fig. 2:<br />

Upright switch cabinet<br />

Fig. 3: Overview of cable connections of the <strong>GEA</strong> <strong>CAIRfricostar</strong> air mixing units<br />

1: Pool water immersion sensor (option) 2 x 0,75 mm²; screened LIYCY-0B<br />

2: Reheater 3-way valve 6 x 0,75 mm²; screened LIYCY-JZ<br />

3: Outdoor temperature sensor 2 x 0,75 mm²; screened LIYCY-0B<br />

4: On-site BMS connections provided by others (see unit wiring diagram for options)<br />

5: System cable fully assembled in protective hose (press and attach plugs)<br />

6: Power supply 3 x 400 V+N+PE/ 50 Hz<br />

7: Connection for pool water pump (option); 3 x 1,5 to 083 if more 5 x 1,5 mm² (not for<br />

CW_units) + 2 x 0,75 mm² fault contact.<br />

8: Connection for reheater pump; 3 x 1,5 to 083 if more 5 x 1,5 mm² (not for CW_units) + 2 x<br />

0,75 mm² fault contact.<br />

9: External shut-down; smoke and gas alarm; 2 x 0,75 mm²<br />

* Special configuration for Austria:<br />

It is usually not necessary to screen the sensor supply line!<br />

1: Pool immersion temperature sensor 2 x 0,75 mm²<br />

2: Reheater valve 5 x 1,5 mm²<br />

3: Outdoor temperature sensor 2 x 0,75 mm²<br />

4: On-site BMS connections provided by others according to wiring diagram<br />

5: Fully assembled system cable is not necessary (standard in switch cabinet)<br />

6: Power supply 3 x 400 V+N+PE/ 50 Hz<br />

7: Connection for pool water pump (option); 3 x 1,5 to 037 if more 6 x 1,5 mm² (400 V)<br />

8: Connection for reheater pump; 3 x 1,5 mm to 037 if more 6 x 1,5 mm² (400 V)<br />

9: External safety shut-down only on request<br />

10: Inlet temperature sensor, heater 2 x 0,75 mm²<br />

11: Room temperature and humidity sensor 5 x 0,75 mm²<br />

54 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Electrical Integration<br />

Overview of Cable Connections<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong> circulating air units<br />

NOTE!<br />

Only the unit wiring diagram provides exact information about the unit delivery condition.<br />

The switch cabinet is supplied loose!<br />

*<br />

11<br />

10<br />

2<br />

1<br />

4<br />

8<br />

5 5 5<br />

6<br />

9<br />

7<br />

Fig. 4: Overview of cable connections of the <strong>GEA</strong> <strong>CAIRfricostar</strong> circulating air units<br />

1: Pool water thermostat (option); 3 x 1,5 mm²<br />

2: Reheater valve 5 x 1,5 mm²<br />

3: Switch cabinet<br />

4: Power supply; 3~ 400 V+N+PE/ 50 Hz<br />

5: System cable fully assembled (press and attach plugs)<br />

6: Exhaust air fan (option); 5 x 1,5<br />

7: Pool water pump connection (option); 3 x 1,5 mm²<br />

8: Remote control/humidistat; 5 x 0,75 mm²<br />

9: Reheater pump; 3 x 1,5 mm²<br />

*Special model for Austria:<br />

It is usually not necessary to screen the sensor supply line!<br />

1: Pool immersion temperature sensor 2 x 0,75 mm²<br />

2: Reheater valve 5 x 1,5 mm²<br />

3: Switch cabinet<br />

4: On-site BMS connections provided by others according to wiring diagram<br />

5: Fully assembled system cable is not necessary (standard in switch cabinet)<br />

6: Power supply 3 x 400 V+N+PE/ 50 Hz<br />

7: Pool water pump connection (option); 3 x 1,5 mm²<br />

8: Reheater pump; 3 x 1,5 mm²<br />

9: External safety switch off only on request<br />

10: Inlet temperature sensor, heater 2 x 0,75 mm²<br />

11: Room temperature and humidity sensor 5 x 0,75 mm²<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 55


Unit Selection<br />

As Relates to Water Surface<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Unit Model Range as Relates to Water Surface, Unit Type: Standard<br />

<strong>CAIRfricostar</strong> model range<br />

CAM320<br />

950m²<br />

CAM290<br />

850m²<br />

CAM250<br />

745m²<br />

CAM230<br />

680m²<br />

CAM200<br />

590m²<br />

CAM170<br />

510m²<br />

Standard unit types<br />

CAM150<br />

CAM130<br />

CAM110<br />

CAM100<br />

CAM083<br />

CAM055<br />

260m²<br />

195m²<br />

130m²<br />

325m²<br />

380m²<br />

435m²<br />

Water surface max. [m²]<br />

Temp.: 30° C air / 28° C water<br />

CAM045<br />

100m²<br />

CAM037<br />

85m²<br />

CAM030<br />

70m²<br />

CAM025<br />

60m²<br />

CAM015<br />

40m²<br />

0 5.000 10.000 15.000 20.000 25.000 30.000 35.000 40.000 45.000 50.000<br />

Air volume flow [m 3 /h]<br />

Unit Model Range as Relates to Water Surface, Unit Type: Standard<br />

<strong>CAIRfricostar</strong> model range<br />

CAM360<br />

830m²<br />

CAM320<br />

740m²<br />

CAM290<br />

670m²<br />

CAM250<br />

575m²<br />

CAM230<br />

530m²<br />

Performance unit types<br />

CAM200<br />

CAM170<br />

CAM150<br />

CAM130<br />

CAM110<br />

CAM100<br />

CAM083<br />

CAM055<br />

190m²<br />

130m²<br />

230m²<br />

250m²<br />

300m²<br />

340m²<br />

400m²<br />

460m²<br />

Water surface max. [m²]<br />

Temp.: 30° C air / 28° C water<br />

CAM045<br />

100m²<br />

CAM037<br />

85m²<br />

CAM030<br />

70m²<br />

CAM025<br />

60m²<br />

CAM015<br />

35m²<br />

0 5.000 10.000 15.000 20.000 25.000 30.000 35.000 40.000<br />

Air volume flow [m 3 /h]<br />

56 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Configuration Variants and Accessories<br />

Configuration Variants<br />

<strong>GEA</strong> quality class K for<br />

swimming pools<br />

<strong>GEA</strong> quality class H for<br />

swimming pools (option)<br />

<strong>GEA</strong> quality class P for<br />

swimming pools (option)<br />

Standard protection for swimming hall units<br />

– Protective paint for fans<br />

– Aluminium <strong>com</strong>ponents in risk areas<br />

– Corrosion resistant Bumax screw connection<br />

– Protective paint for refrigeration circuit and <strong>com</strong>ponents (section related)<br />

– V4A unit parts with additional coating in risk areas<br />

For tougher requirements (brine pools, ...)<br />

– Additional protective paint for fans<br />

– Aluminium <strong>com</strong>ponents in risk areas<br />

– Corrosion resistant Bumax screw connection<br />

– Multicoat marine paint „ULTRA HIGH SOLID“ for refrigeration circuit, dampers and<br />

various <strong>com</strong>ponents<br />

– V4A unit parts with additional coating in risk areas<br />

– „Alodyne“ coating of heat exchanger fins<br />

– Plastic laminated pipework of the refrigeration circuit (section related)<br />

– „PlasTec“ capillary tube lines<br />

For tough requirements (thermal baths/pools, ...)<br />

– Additional protective paint for fans<br />

– Aluminium <strong>com</strong>ponents in risk areas<br />

– Corrosion resistant Bumax screw connection<br />

– Multicoat marine paint „ULTRA HIGH SOLID“ for refrigeration circuit, dampers and<br />

various <strong>com</strong>ponents<br />

– V4A unit parts with additional coating in risk areas<br />

– V4A dampers<br />

– Plastic laminated pipework of the refrigeration circuit<br />

– „PlasTec“ capillary tube lines<br />

– „S70“- immersion bath coating of heat exchanger<br />

– „SÄKA-TEC“ coating of evaporator<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 57


Configuration Variants and Accessories<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Accessories<br />

(Component version only for DDC-controller; except for CAU)<br />

<strong>GEA</strong> unit<br />

Input extension for control possibilities by others<br />

Potential-free floating contacts for status signals<br />

Output extension, 0-10 V signals, exhaust air humidity and temperature<br />

Input extension for setpoint shift by others, 0-10 V signals, exhaust air humidity,<br />

exhaust air temperature and minimum fresh air rate<br />

Type<br />

DEW<br />

DPK<br />

DAW<br />

DFV<br />

Error message fire protection damper/fire alarm system<br />

Control display in a separate casing as remote control (without cabinet display)<br />

Additional control display in a separate casing as remote control (without cabinet display)<br />

Automatic shift for humidity setpoint<br />

Air flow monitoring for supply and exhaust air fan<br />

Emergency manual control for fans, reheater valve, pump, damper actuator<br />

Automatic adjustment of indoor temperature setpoint, depending on the pool water temperature<br />

BSK<br />

DFB<br />

DFD<br />

DFS<br />

DLW<br />

DNH<br />

DTA<br />

Interface GSM Modem including software<br />

Interface ISDN Modem including software<br />

Interfaces of <strong>GEA</strong> to GFR building management system<br />

Interface OPC-S Bus<br />

Interface BACnet-Bus<br />

Interface LON-Bus<br />

Interface OSPA Blue Control<br />

Interface MOD Bus<br />

Generating data point list for relevant GLT system<br />

Assistance for the network technician during integration of GLT connections on site, requirement<br />

is a <strong>com</strong>plete unit connection by others on site<br />

Interface for modem<br />

Comfortable touch control terminal<br />

Software WEBVISION light<br />

GSM<br />

ISDN<br />

DSG<br />

OPC<br />

BACNET<br />

LON<br />

OSPA<br />

MOD<br />

xxxDP<br />

xxxIB<br />

DSM<br />

TBT<br />

WEV<br />

58 PR-2008-0327-GB • Subject to modifications • Status 05/2009


<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Notes<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 59


Customer proximity, sales structures<br />

Reachable always and everywhere!<br />

AE<br />

AT<br />

BA<br />

BE<br />

BG<br />

BY<br />

CH<br />

CZ<br />

CZ<br />

DE<br />

<strong>GEA</strong> Air Treatment<br />

Middle East<br />

UAE-Dubai<br />

Tel. +971 / 4 / 887 3881<br />

<strong>GEA</strong> Klimatechnik<br />

GmbH & Co KG<br />

A-4673 Gaspoltshofen<br />

Tel. +43 / 7735 / 8000-0<br />

<strong>GEA</strong> Klimatechnik<br />

GmbH & Co KG<br />

RS-11070 Novi Beograd<br />

Tel. +381 / 11 / 3193955<br />

<strong>GEA</strong> Happel Belgium N. V.<br />

B-1130 Brussels<br />

Tel. +32 / 2 / 2406161<br />

EVISS Ltd.<br />

BG-7000 Rousse<br />

Tel . +359 / 82 / 81000<br />

<strong>GEA</strong> Klimatechnik UAB<br />

LT-01141 Vilnius<br />

Tel. +370 / 5 / 2106060<br />

ATC Klimatec Schweiz AG<br />

CH-3065 Bolligen<br />

Tel. +41 / 31 / 9171919<br />

<strong>GEA</strong> LVZ, a.s.<br />

CZ-46312 Liberec<br />

Tel. +420 / 48 / 5225-111<br />

<strong>GEA</strong> Klimatizace spol. s r.o.<br />

CZ-46312 Liberec<br />

Tel. +420 / 48 / 5225-303<br />

<strong>GEA</strong> Happel<br />

Klimatechnik GmbH<br />

D-44625 Herne<br />

Tel. +49 / 2325 / 468-00<br />

The <strong>com</strong>plete addresses are available on the<br />

Internet under: www.gea-air-eco2nomy.<strong>com</strong>.<br />

DE<br />

DE<br />

DE<br />

DE<br />

DK<br />

EE<br />

ES<br />

FI<br />

FR<br />

FR<br />

<strong>GEA</strong> Happel<br />

Wieland GmbH<br />

D-44625 Herne<br />

Tel. +49 / 2325 / 468-754<br />

<strong>GEA</strong> Deichmann<br />

Umwelttechnik GmbH<br />

D-36179 Bebra<br />

Tel. +49 / 6622 / 504-0<br />

<strong>GEA</strong> Delbag<br />

Lufttechnik GmbH<br />

D-44625 Herne<br />

Tel. +49 / 2325 / 468-700<br />

<strong>GEA</strong> Delbag-Luftfilter<br />

Vertriebsgesellschaft mbH<br />

D-10709 Berlin<br />

Tel. +49 / 30 / 43592-3<br />

CS Klimateknik ApS<br />

DK-5450 Otterup<br />

Tel . +45 / 38 / 887070<br />

<strong>GEA</strong> Klimatechnik UAB<br />

LT-01141 Vilnius<br />

Tel. +370 / 5 / 2106060<br />

<strong>GEA</strong> Air Treatment<br />

Marketing Services Int.<br />

GmbH – oficina España<br />

ES-28028 Madrid<br />

Tel. +34 / 91 / 3837701<br />

OY TEKNOCALOR AB<br />

FIN-01300 Vantaa<br />

Tel. +358 / 10 / 8201100<br />

<strong>GEA</strong> Delbag<br />

Filtration de l’air<br />

F-77450 Montry<br />

Tel. +33 / 1 / 60043355<br />

<strong>GEA</strong> Happel France sarl<br />

F-59436 Roncq Cedex<br />

Tel. +33 / 3 / 20689020<br />

GB<br />

HR<br />

HU<br />

IE<br />

IS<br />

LT<br />

LU<br />

LV<br />

ME<br />

NL<br />

NO<br />

<strong>GEA</strong> Denco Ltd.<br />

UK-HR4 8DS Hereford<br />

Tel. +44 / 1432 / 277 277<br />

<strong>GEA</strong> Klima-rashladna<br />

tehnika d.o.o.<br />

HR-10000 Zagreb<br />

Tel. +385 / 1 / 6064900<br />

<strong>GEA</strong> Klimatechnika Kft<br />

H-1037 Budapest<br />

Tel. +36 / 1 / 4393200<br />

Aspect Environmental Ltd.<br />

Ardee, Co. Louth Ireland<br />

Tel. +353 / 41 / 6858983<br />

Rafn Jensson<br />

IS-110 Reykjavik<br />

Tel. +354 / 56 / 780-30<br />

<strong>GEA</strong> Klimatechnik UAB<br />

LT-01141 Vilnius<br />

Tel. +370 / 5 / 2106060<br />

<strong>GEA</strong> Happel Luxembourg<br />

L-4940 Bascharage<br />

Tel. +352 / 26 / 502970<br />

<strong>GEA</strong> Klimatechnik UAB<br />

LT-01141 Vilnius<br />

Tel. +370 / 5 / 2106060<br />

<strong>GEA</strong> Klimatechnik<br />

GmbH & Co KG<br />

RS-110 70 Novi Beograd<br />

Tel. +381 / 11 / 3193955<br />

<strong>GEA</strong> Happel Nederland B.V.<br />

NL-2909 LL<br />

Capelle a/d Ijssel<br />

Tel. +31 / 10 / 2350606<br />

<strong>GEA</strong> Klimaprodukter AS<br />

N-0484 Oslo<br />

Tel. +47 / 220 / 27990<br />

PL<br />

PT<br />

RO<br />

RU<br />

SE<br />

SI<br />

SK<br />

RS<br />

TR<br />

UA<br />

<strong>GEA</strong> Klimatyzacja sp.z.o.o<br />

PL-53-609 Wrocław<br />

Tel. +48 / 71 / 3565866<br />

Nónio, Lda.<br />

P-1269-090 Lisboa<br />

Tel. +351 / 21 / 3826160<br />

<strong>GEA</strong> Klimatechnik s.r.l.<br />

RO-300222 Timisoara<br />

Tel. +40 / 356 / 423703<br />

<strong>GEA</strong> Klimatechnik<br />

GmbH & Co KG<br />

RU-105094 Moskva<br />

Tel. +7 / 495 / 9566674<br />

<strong>GEA</strong> EXOS Ventilation AB<br />

S-74528 Enköping<br />

Tel. +46 / 171 / 85530<br />

<strong>GEA</strong> Klimatizacijska<br />

Tehnika d.o.o.<br />

SI-1000 Ljubljana<br />

Tel. +386 / 1 / 2573850<br />

<strong>GEA</strong> Klimatizácia s.r.o.<br />

SK-83104 Bratislava<br />

Tel. +421 / 7 / 44457917<br />

<strong>GEA</strong> Klimatechnik<br />

GmbH & Co KG<br />

RS-11070 Novi Beograd<br />

Tel. +381 / 11 / 3193955<br />

<strong>GEA</strong> ISISAN<br />

TR-80700<br />

Balmumcu Istanbul<br />

Tel. +90 / 212 / 2757171<br />

<strong>GEA</strong> Ukraina t.o.v.<br />

UA-01135 Kyiv<br />

Tel. +38 / 044 / 4619356<br />

MRLOMMV=Ó=moJOMMVJMPOTJd_<br />

pìÄàÉÅí=íç=ãçÇáÑáÅ~íáçåë=•=`çéóêáÖÜí=db^=^áê=qêÉ~íãÉåí<br />

xx/xxxx – PR-xxxx-xxxx-xxx<br />

<br />

www.gea-air-eco2nomy.<strong>com</strong>