Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CMP<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

– With optimized heat exchanger <strong>com</strong>bination for maximum COP values, mounted on<br />

anti-vibration mounts, circuit includes filter drier, liquid collector, thermostatic<br />

expansion valve with MOP (maximum operating pressure) and external pressure<br />

equalisation, all necessary shut-off valves, monitoring and safety devices<br />

(pressostat, icing sensor, etc.)<br />

Droplet eliminator – Made of plastic with an aluminium frame at air velocities on supply and exhaust side<br />

exceeding 2,5 m/s is necessary<br />

Fan unit:<br />

<strong>GEA</strong> „OPTIVENT“<br />

– High performance fan impellers with coated backward curved blades, one side suction<br />

and blades directly connected to motor shaft; Performance<br />

– Optimized high value three-phase motor, B3 model type, protection type IP55, insulation<br />

class F adjusted for operation with a frequency converter. Fan and motor unit<br />

including coated intake nozzle mounted on buckling resistant and coated base construction,<br />

motor and fan have sound attenuated bearings<br />

– Continuous measurement of pressure effects<br />

– Statically and dynamically balanced according to DIN ISO 1940, part 1, G2,5). Continuous<br />

monitoring of operation using DDC. Frequency converter for each motor<br />

installed in or mounted on the unit, control via <strong>GEA</strong> DDC with a separate analogue<br />

signal for both motors. Frequency converters are adjusted and set for both motors.<br />

Limit values for motor current and fan speed are set by the programme<br />

– Resonance frequency band/fade out set by factory<br />

– Automatic energy optimization for optimal energy use and efficiency rate<br />

– Multiple motor operation is possible<br />

– Voltage intermediate circuit converter without reduction of capacity<br />

– Continuous speed control<br />

– Operating hours counter<br />

– Min. and max. speed limitation, automatic ramp curve function UP/DOWN<br />

– Automatic motor adjustment<br />

– Motor tracing switch<br />

– DC break<br />

– Variable clock frequency<br />

– Motor protection<br />

– Short circuit and short circuit to earth safe<br />

– Under and over current protection<br />

– Phase fault monitoring<br />

– Motor coils for reducing speed of voltage rise du/dt (delta voltage/delta time)<br />

– Numerical display for queries and entering of different indicators on operating status:<br />

control setpoint, motor frequency, actual value and setpoint, motor current,<br />

motor torque and capacity, intermediate circuit voltage, thermal motor load, thermal<br />

frequency converter load, control and programmable display with copy function,<br />

production according to ISO 9001, CE Label, net and main shaft protection<br />

according to VDE 0160, radio interference shielding, codes and regulations on electromagnetic<br />

<strong>com</strong>patibility conform with EN 55011 Kl.B-1; EN 50082-2, electric insulation<br />

of control and power <strong>com</strong>ponents according to VDE 0106/0160 (The use of<br />

earth leakage circuit breaker / fuse with frequency converters NOT possible!), volume<br />

flow measuring device via ring measuring line and pressure measuring point<br />

in fan. Calculation and evaluation of volume flow via the <strong>GEA</strong> DDC. The settings for<br />

entire unit are done at the factory. Continuous safety monitoring via safety chain in<br />

the unit. Display and settings via <strong>GEA</strong> DDC.<br />

24 PR-2008-0327-GB • Subject to modifications • Status 05/2009