<strong>GEA</strong> <strong>CAIRfricostar</strong><br />
Dehumidifier with Air Mixing and Heat Pump Function<br />
Type CMP<br />
Air damper system: – Dampers with sealing lips, leakage volume flow 20 m3/h m2 (dp=100 Pa), for circulating<br />
air/bypass, for fresh and exhaust air. Circulating and fresh air rate 0-100%<br />
– Coated Almg3 damper blades with flow efficient profile, operate in opposite directions.<br />
Driven by double sided, anti-static plastic gears PA6 as fiberglass reinforced<br />
model (resistant to chemicals) including special actuator for each damper<br />
– Control of the individual actuators using continuous DDC signals<br />
Filter for fresh and<br />
exhaust air:<br />
– Filter units conform with VDI 6022<br />
– Including bag filter as of DIN/EN 779, synthetic fiber filter medium<br />
– All filters are fitted with a differential pressure switch for filter monitoring via the DDC<br />
Heat recovery system:<br />
<strong>GEA</strong> „ECOPLAT2 POWER PLATE“<br />
– 2 symmetric high performance plate heat exchangers, recuperative heat recovery<br />
by using two cross flow aluminium plate heat exchangers (corrosion protected Al99<br />
with best temperature coefficient) in row switch. Surface is additionally coated with<br />
thermoplastic material. Largest possible heat exchange surface using entire unit<br />
depth with minimum pressure losses. Optimal selection with consideration of operation<br />
conditions. Best efficiency rates within entire outdoor temperature range,<br />
especially resistant to corrosion and wear. Swimming pool configuration.<br />
– „Upside Down“ installation for smaller internal pressure drops.<br />
– AlMg3 ventilation tray<br />
– Technical data checked according to EUROVENT<br />
– Conform with VDI 6022<br />
– Non-<strong>com</strong>bustible according to fire protection regulation<br />
Heating section: – L.P.H.W. air heater, heat exchanger with copper pipes and drawn aluminium fins in<br />
aluminium frame AlMg3 (max. temp. 110°C, Pmax 16 bar) removable in accordance<br />
with VDI 6022;<br />
<strong>GEA</strong> motor 3-way mixing<br />
valve:<br />
Control and regulation<br />
system<br />
– For air reheater, supplied loose including actuator 0-10 V with an automatic step<br />
measurement system for fine adjustment of water flow rate<br />
– Supplied loose, installation by others<br />
– Consists of a separate switch cabinet for mounting on units or separate installation<br />
(depending in unit size), with all necessary <strong>com</strong>ponents for control functions, wired<br />
according to VDE specifications. IP55 electrical connection (via plug or screw terminals)<br />
between control cabinet and unit using factory prepared and fully<br />
assembled lines. Electrical installation for voltage supply, valve mixing control,<br />
reheater pump, if necessary external sensor of the pool water pump and possibly<br />
other functions like remote control inputs by others. The cabinet is supplied loose<br />
depending on the unit size as a stand alone cabinet or for mounting on the unit<br />
Air mixing dehumidifier CMP<br />
The switch cabinet is<br />
supplied with the following<br />
main <strong>com</strong>ponents:<br />
– Main isolating switch for all pole shut-down of the electrical unit, lockable<br />
– Group fuses for fan and <strong>com</strong>pressor<br />
– Fuses for reheater and PWC pump<br />
230V/N/PE/50Hz (types 015-083)<br />
3 X 400V/NPE/50Hz (types 100-320)<br />
(if necessary - motor protection by others)<br />
– Control fuses, control transformer 230 V and control voltage supply unit 24V DC for<br />
the digital control<br />
– Control fuse and control voltage supply unit 24V AC for actuators<br />
– Automatic phase controller (option)<br />
– Indoor installation, frost free<br />