<strong>GEA</strong> <strong>CAIRfricostar</strong><br />
Alternative fan unit:<br />
Dehumidifier with Air Mixing Function<br />
Type CWR<br />
<strong>GEA</strong> „OPTIVENT“ high performance fan impellers<br />
– Surface coated one side suction with backward curved blades that are directly connected<br />
to motor shaft; performance optimized three-phase motor, B3 model type,<br />
protection type IP55, insulation class F adjusted for operation with a frequency converter.<br />
Fan and motor unit including coated intake nozzle mounted on buckling<br />
resistant and coated base construction, motor and fan have sound attenuated bearings<br />
– Continuous measurement of pressure effects<br />
– Statically and dynamically balanced according to DIN ISO 1940, part 1, G2,5). Continuous<br />
pressure monitoring using DDC. Frequency converter for each motor<br />
installed in or mounted on the unit, control via <strong>GEA</strong> DDC with a separate analogue<br />
signal for each motor. Frequency converters are adjusted and set for both motors.<br />
Limit values for motor current and fan speed are set by the programme<br />
– Resonance frequency band/fade out set by factory<br />
– automatic energy optimization for optimal energy use and efficiency rate<br />
– Multiple motor operation is possible<br />
– Voltage intermediate circuit converter without reduction of capacity<br />
– continuous speed control<br />
– Operating hours counter<br />
– Min. and max. speed limitation, automatic ramp curve function UP/DOWN<br />
– Automatic motor adjustment<br />
– Motor tracing switch<br />
– DC break<br />
– Variable clock frequency<br />
– Motor protection<br />
– Short circuit and short circuit to earth safe<br />
– Under and overcurrent protection<br />
– Phase fault monitoring<br />
– Motor coils for reducing speed of voltage rise du/dt (delta voltage/delta time)<br />
– Numerical display for queries and entering of different indicators on operating status:<br />
control setpoint, motor frequency, actual value and setpoint, motor current,<br />
motor torque and capacity, intermediate circuit voltage, thermal motor load, thermal<br />
frequency converter load, control and programmable display with copy function,<br />
production according to ISO 9001, CE Label, net and main shaft protection according<br />
to VDE 0160, radio interference shielding, codes and regulations on electromagnetic<br />
<strong>com</strong>patibility conform with EN 55011 Kl.B-1; EN 50082-2, electric<br />
insulation of control and power <strong>com</strong>ponents according to VDE 0106/0160 (The use<br />
of earth leakage circuit breaker / fuse with frequency converters NOT possible!),<br />
volume flow measuring device via ring measuring line and pressure measuring<br />
point in fan. Calculation and evaluation of volume flow via the <strong>GEA</strong> DDC. The settings<br />
for entire unit are done at the factory. Continuous safety monitoring via safety<br />
chain in the unit. Display and settings via <strong>GEA</strong> DDC.<br />
Air mixing dehumidifier CWR<br />
Air damper system: – Dampers with sealing lips, leakage volume flow 20 m3/h m2 (dp=100 Pa), for circulating<br />
air/bypass, for fresh and exhaust air. Circulating and fresh air rate 0-100%<br />
– Coated Almg3 damper blades with flow efficient profile, operate in opposite<br />
directions. Driven by double sided, anti-static plastic gears PA6 as fiberglass<br />
reinforced model (resistant to chemicals) including special actuator for<br />
each damper<br />
– Control of the individual actuators using continuous DDC signals<br />
Filter for fresh and<br />
exhaust air:<br />
– Filter units conform with VDI 6022<br />
– Including bag filter as of DIN/EN 779, synthetic fiber filter medium<br />
– All filters are fitted with a differential pressure switch for filter monitoring via the DDC<br />
PR-2008-0327-GB • Subject to modifications • Status 05/2009 31