26.01.2015 Views

GEA CAIRfricostar - Aspectenvironmental.com

GEA CAIRfricostar - Aspectenvironmental.com

GEA CAIRfricostar - Aspectenvironmental.com

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Electrical Integration<br />

Overview of Cable Connections<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong> circulating air units<br />

NOTE!<br />

Only the unit wiring diagram provides exact information about the unit delivery condition.<br />

The switch cabinet is supplied loose!<br />

*<br />

11<br />

10<br />

2<br />

1<br />

4<br />

8<br />

5 5 5<br />

6<br />

9<br />

7<br />

Fig. 4: Overview of cable connections of the <strong>GEA</strong> <strong>CAIRfricostar</strong> circulating air units<br />

1: Pool water thermostat (option); 3 x 1,5 mm²<br />

2: Reheater valve 5 x 1,5 mm²<br />

3: Switch cabinet<br />

4: Power supply; 3~ 400 V+N+PE/ 50 Hz<br />

5: System cable fully assembled (press and attach plugs)<br />

6: Exhaust air fan (option); 5 x 1,5<br />

7: Pool water pump connection (option); 3 x 1,5 mm²<br />

8: Remote control/humidistat; 5 x 0,75 mm²<br />

9: Reheater pump; 3 x 1,5 mm²<br />

*Special model for Austria:<br />

It is usually not necessary to screen the sensor supply line!<br />

1: Pool immersion temperature sensor 2 x 0,75 mm²<br />

2: Reheater valve 5 x 1,5 mm²<br />

3: Switch cabinet<br />

4: On-site BMS connections provided by others according to wiring diagram<br />

5: Fully assembled system cable is not necessary (standard in switch cabinet)<br />

6: Power supply 3 x 400 V+N+PE/ 50 Hz<br />

7: Pool water pump connection (option); 3 x 1,5 mm²<br />

8: Reheater pump; 3 x 1,5 mm²<br />

9: External safety switch off only on request<br />

10: Inlet temperature sensor, heater 2 x 0,75 mm²<br />

11: Room temperature and humidity sensor 5 x 0,75 mm²<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 55