<strong>GEA</strong> <strong>CAIRfricostar</strong><br />
<strong>GEA</strong> motor 3-way mixing<br />
valve:<br />
Control and regulation<br />
system<br />
The switch cabinet is<br />
supplied with the following<br />
main <strong>com</strong>ponents:<br />
Dehumidifier with Air Recirculating and Heat Pump Function<br />
Type CAU<br />
– Supplied loose for air reheating coil including actuator 230 V with an automatic step<br />
measurement system for fine adjustment of water flow rate<br />
– Supplied loose, installation by others<br />
– Consists of a separate switch cabinet for mounting on units with all necessary <strong>com</strong>ponents<br />
for control functions, wired according to VDE specifications.<br />
– Electrical connection (via plug or screw terminals) between control cabinet and unit<br />
using factory prepared and fully assembled lines.<br />
– Mains voltage for control of mixing valve and reheater pump (including controls)<br />
– Possible output for pool water pump<br />
– The switch cabinet is supplied loose, including fixing material for mounting on the<br />
unit<br />
– All electronic control and regulation <strong>com</strong>ponents can be easily replaced<br />
– Main isolating switch for all pole shut-down of the electrical unit<br />
– Group fuses for fan and <strong>com</strong>pressor<br />
Safety fuse for pump reheater circuit 230V<br />
Control fuse and control voltage supply unit 24V (safety extra-low voltage or SELV)<br />
Control of supply air fan using motor full protection device via PTC<br />
temperature sensor and electronic motor tripping device<br />
– Control of <strong>com</strong>pressor motor with thermal motor protection and interlock for safety<br />
chain and control card, control of icing protection, low and high pressure.<br />
– Electronic control card for <strong>com</strong>pressor regulation with minimum run and standstill<br />
time as clock protection, service reset button, status messages for timer control and<br />
light diode for faults of the refrigeration circuit.<br />
– Humidistat with remote control for mounting in the swimming pool, with status and<br />
fault lamp and operation switch.<br />
Operation with safety extra-low voltage.<br />
Setpoint setting 30-90 % r.h.<br />
Colour: white<br />
On-wall mounting<br />
Dimensions: W/H/D 145/80/30 (mm) supplied loose<br />
– Electronic three point PI-controller for exhaust air temperature control with setpoint<br />
setting on the switch cabinet including installed NTC exhaust air temperature sensor.<br />
– Output 230V for modulating 3-way valve motor in reheater circuit<br />
– If necessary <strong>GEA</strong> pool water temperature control for controlling pool water pump<br />
consisting of an integrated immersion thermostat, interlocking with <strong>com</strong>pressor<br />
operation and output for pool water pump 230V (only control output max. 2A) and<br />
time control for registration of actual values (only in <strong>com</strong>bination with pool water<br />
condenser)<br />
– Output for collective error message signal (floating change-over contact)<br />
– Control possibility of an exhaust fan by others, 2-speed, 230 V/max. 150 W<br />
Air recirculating dehumidifier CAU<br />
PR-2008-0327-GB • Subject to modifications • Status 05/2009 5