<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidifier with Air Mixing Function<br />

Type CWR<br />

Functional description of the unit<br />

The <strong>GEA</strong> <strong>CAIRfricostar</strong> CWR is designed for various kinds of private and public swimming<br />

pools. The series can be supplied with air volume capacity between 750 up to<br />

45,000 m³/h. The unit's function is to dehumidify and heat air in swimming pools in air<br />

mixing mode. This unit type is additionally equipped with an efficient heat recovery system.<br />

The unit is delivered with a DDC controls which regulates all functions of the system<br />

on a fully automated basis.<br />

Sample selection of operating modes:<br />

When in idle mode without dehumidification the air is recirculated in the swimming pool.<br />

When the humidity setpoint has been exceeded the unit switches into dehumidification<br />

mode. For this purpose the supply and exhaust air fans are activated to run at high<br />

speed with continuous mixing of outdoor air. The dehumidification stage continues until<br />

the actual humidity value is reduced below that of the humidity setpoint. After that the<br />

fans are deactivated.<br />

Idle mode without dehumidification<br />

demand<br />

Active hours operation mode with<br />

dehumidification demand<br />

Idle mode with dehumidification<br />

request<br />

+<br />

+<br />

+<br />

-<br />

-<br />

-<br />

Bypass damper mode, exhaust air fan is<br />

deactivated,<br />

supply air fan runs at low speed.<br />

Active hours operation mode with high<br />

dehumidification demand<br />

Air mixing operation according to VDI,<br />

exhaust and supply air fans run at high<br />

speed. The reheater provides the missing<br />

residual heat supply.<br />

Air mixing mode with a minimum fresh air rate<br />

Active hours/summer operation mode<br />

Air mixing dehumidifier CWR<br />

+<br />

+<br />

-<br />

-<br />

130<br />

130<br />

Air mixing operation according to VDI, exhaust and supply air fans<br />

run at high speed. The reheater provides the missing residual heat<br />

supply. Outdoor air temperature is increased.<br />

Fresh air mode, exhaust and supply air fans run at high speed.<br />

Heat recovery is not used thanks to a damper system.<br />