130<br />
130<br />
130<br />
<strong>GEA</strong> <strong>CAIRfricostar</strong><br />
Dehumidifier with Air Mixing Function<br />
Type CWR<br />
Functional description of the unit<br />
The <strong>GEA</strong> <strong>CAIRfricostar</strong> CWR is designed for various kinds of private and public swimming<br />
pools. The series can be supplied with air volume capacity between 750 up to<br />
45,000 m³/h. The unit's function is to dehumidify and heat air in swimming pools in air<br />
mixing mode. This unit type is additionally equipped with an efficient heat recovery system.<br />
The unit is delivered with a DDC controls which regulates all functions of the system<br />
on a fully automated basis.<br />
Sample selection of operating modes:<br />
When in idle mode without dehumidification the air is recirculated in the swimming pool.<br />
When the humidity setpoint has been exceeded the unit switches into dehumidification<br />
mode. For this purpose the supply and exhaust air fans are activated to run at high<br />
speed with continuous mixing of outdoor air. The dehumidification stage continues until<br />
the actual humidity value is reduced below that of the humidity setpoint. After that the<br />
fans are deactivated.<br />
Idle mode without dehumidification<br />
demand<br />
Active hours operation mode with<br />
dehumidification demand<br />
Idle mode with dehumidification<br />
request<br />
+<br />
+<br />
+<br />
-<br />
-<br />
-<br />
Bypass damper mode, exhaust air fan is<br />
deactivated,<br />
supply air fan runs at low speed.<br />
Active hours operation mode with high<br />
dehumidification demand<br />
Air mixing operation according to VDI,<br />
exhaust and supply air fans run at high<br />
speed. The reheater provides the missing<br />
residual heat supply.<br />
Air mixing mode with a minimum fresh air rate<br />
Active hours/summer operation mode<br />
Air mixing dehumidifier CWR<br />
+<br />
+<br />
-<br />
-<br />
130<br />
130<br />
Air mixing operation according to VDI, exhaust and supply air fans<br />
run at high speed. The reheater provides the missing residual heat<br />
supply. Outdoor air temperature is increased.<br />
Fresh air mode, exhaust and supply air fans run at high speed.<br />
Heat recovery is not used thanks to a damper system.<br />
PR-2008-0327-GB • Subject to modifications • Status 05/2009 29