<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidification Unit with Air Mixing Function<br />

Type CAC<br />

– Frame profiles AlMgSi 0,5<br />

– Flexible connector with potential equalisation, temperature resistant from -30 °C to<br />

+120 °C<br />

– Duct connection using 30 mm frame with 4 hole bolt connection<br />

– Interior installation parts for swimming pool mode with special corrosion protection<br />

Heat pump for<br />

dehumidification:<br />

– Direct evaporator according to VDI 6022: heat exchanger as Cu/Alu model for R<br />

407c refrigerant, fins made of aluminium, frame elements made of AlMg3, pipes<br />

made of oxygen-free copper.<br />

– Condensate water tray in bottom panel for evaporator and heat recovery system,<br />

with a slope in the direction of condensate drain, made of stainless steel V4A<br />

powder coated, including drain tray, conform with VDI 6022<br />

– Air-cooled condenser according to VDI 6022: heat exchanger as Cu/Alu model for<br />

R 407c refrigerant, fins made of aluminium, frame elements made of AlMg3, pipes<br />

made of oxygen-free copper<br />

– Compressor unit: refrigeration circuit with a fully hermetic scroll <strong>com</strong>pressor<br />

– with optimized heat exchanger <strong>com</strong>bination for maximum COP values, mounted on<br />

anti-vibration mounts, circuit includes filter drier, liquid collector, thermostatic<br />

expansion valve with MOP and external pressure equalisation, all necessary<br />

shut-off valves, monitoring and safety devices (pressostat, icing sensor, etc.)<br />

Droplet eliminator – made of plastic with an aluminium frame at air velocities on supply and exhaust side<br />

exceeding 2,5 m/s is necessary<br />

Fan unit:<br />

<strong>GEA</strong> centrifugal fan „LESS ENERGY SYSTEM“<br />

– Optimized operating point, double side suction, coated surface model<br />

– Three phase motor, protection class IP55 , model type B3, <strong>com</strong>plete belt drive, easy<br />

service thanks to one bolt tensioning sled<br />

– Fan/motor unit mounted on anti-vibration mounts<br />

Air damper system: – Dampers with sealing lips, leakage volume flow 20 m 3 /h m2 (dp=100 Pa), for circulating<br />

air/bypass, for fresh and exhaust air. Circulating and fresh air rate 0-100%<br />

– Coated Almg3 damper blades with flow efficient profile, operate in opposite directions.<br />

Driven by double sided, anti-static plastic gears PA6 as fiberglass reinforced<br />

model (resistant to chemicals) including special actuator for each damper<br />

– Control of the individual actuators using continuous DDC signals<br />

Filter for fresh and<br />

exhaust air:<br />

– Filter units conform with VDI 6022<br />

– including bag filter as of DIN/EN 779, synthetic fiber filter medium<br />

– All filters are fitted with a differential pressure switch for filter monitoring via the DDC<br />

Heat recovery system:<br />

<strong>GEA</strong> „ECOPLAT POWER PLATE“<br />

– symmetric high performance plate heat exchangers, recuperative heat recovery by<br />

using two cross-flow aluminium plate heat exchangers (corrosion protected Al99<br />

with best temperature coefficient). Surface is additionally coated with thermoplastic<br />

material. Largest possible heat exchange surface using entire unit depth with minimum<br />

pressure losses. Optimal selection with consideration of operation conditions.<br />

Best efficiency rates within entire outdoor temperature range, especially resistant to<br />

corrosion and wear. Swimming pool configuration.<br />

– AlMg3 ventilation tray<br />

– technical data checked according to EUROVENT<br />

– conform with VDI 6022<br />

– Non-<strong>com</strong>bustible according to fire protection regulation<br />

Heating section: – L.P.H.W. air heater, heat exchanger with copper pipes and drawn aluminium fins in<br />

aluminium frame AlMg3 (max. temp. 110°C, Pmax 16bar) removable in accordance<br />

with VDI6022;<br />

Air mixing dehumidifier CAC<br />

<strong>GEA</strong> motor -3-way mixing<br />

valve:<br />

– For air reheater, supplied loose including actuator 0-10 V with an automatic step<br />

measurement system for fine adjustment of water flow rate<br />

– supplied loose, installation by others<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 45