<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidifier with Air Mixing and Heat Pump Function<br />

Type CAM<br />

System and controls scheme<br />

M<br />

M<br />

M<br />

M<br />

M5<br />

M1<br />

M<br />

Ecostat<br />

L-Kondensator<br />

NE<br />

B26<br />

B2<br />

M<br />

p<br />

M<br />

Y1<br />

M<br />

MVS<br />

Ecostat<br />

M<br />

M<br />

P<br />

P<br />

M<br />

M<br />

MVS<br />

p<br />

Components<br />

Casing:<br />

DI<br />

AI<br />

DO<br />

AO<br />

Indoor installation<br />

– 50 mm panels, inside and outside skins are painted; (corresponds to RAL 9002),<br />

the series includes casing frame and service door in casing panel thickness together<br />

with a full profile rubber gasket in EPDM quality. All outside and inside surfaces<br />

are <strong>com</strong>pletely smooth.<br />

– Leak tightness class G II according to VDI 3803. Thermal and sound bridges are<br />

minimized.<br />

– Non <strong>com</strong>bustible insulation (fire classification A1 according to DIN 4102; Ö-Norm<br />

B3800; CFC-free)<br />

– Heat transfer coefficient k = 0,57 W/m2 K<br />

– Sound insulation performance Rw = 44 dB according to DIN 52210/T4<br />

– Casing features according to EN1886<br />

– Filter bypass leakage F9<br />

– Leak tightness class according to prEN 1886 (10/2005) L1<br />

– Casing leakage B<br />

– Mechanical stability 1A<br />

– Thermal insulation T2<br />

– Thermal bridging factor TB2 (in risk areas)<br />

– Frame profiles AlMgSi 0,5<br />

– Flexible connector with potential equalisation, temperature resistant from -30 °C to<br />

+120 °C<br />

– Duct connection using 30 mm frame with 4 hole bolt connection<br />

– Interior installation parts for swimming pool mode with special corrosion protection<br />

Air mixing dehumidifier CAM<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 15