Electrical Integration<br />
Overview of Cable Connections<br />
<strong>GEA</strong> <strong>CAIRfricostar</strong><br />
<strong>GEA</strong> <strong>CAIRfricostar</strong> Air mixing units<br />
NOTE!<br />
Only the unit wiring diagram provides exact information about the unit delivery<br />
state.<br />
The switch cabinet is supplied loose! (special configuration includes intermediate<br />
terminal box) Use the enclosed documentation for detailed information about the<br />
installation of the switch cabinet.<br />
Unit size 015-083 with swing switch cabinet on the unit<br />
Unit size 100-360 with upright switch cabinet near the unit<br />
*<br />
9<br />
Fig. 1:<br />
Swing switch cabinet<br />
1<br />
3<br />
4<br />
( )<br />
5 5<br />
2<br />
8<br />
7<br />
on Fig. 1: Swing unit<br />
6<br />
11 10<br />
Fig. 2:<br />
Upright switch cabinet<br />
Fig. 3: Overview of cable connections of the <strong>GEA</strong> <strong>CAIRfricostar</strong> air mixing units<br />
1: Pool water immersion sensor (option) 2 x 0,75 mm²; screened LIYCY-0B<br />
2: Reheater 3-way valve 6 x 0,75 mm²; screened LIYCY-JZ<br />
3: Outdoor temperature sensor 2 x 0,75 mm²; screened LIYCY-0B<br />
4: On-site BMS connections provided by others (see unit wiring diagram for options)<br />
5: System cable fully assembled in protective hose (press and attach plugs)<br />
6: Power supply 3 x 400 V+N+PE/ 50 Hz<br />
7: Connection for pool water pump (option); 3 x 1,5 to 083 if more 5 x 1,5 mm² (not for<br />
CW_units) + 2 x 0,75 mm² fault contact.<br />
8: Connection for reheater pump; 3 x 1,5 to 083 if more 5 x 1,5 mm² (not for CW_units) + 2 x<br />
0,75 mm² fault contact.<br />
9: External shut-down; smoke and gas alarm; 2 x 0,75 mm²<br />
* Special configuration for Austria:<br />
It is usually not necessary to screen the sensor supply line!<br />
1: Pool immersion temperature sensor 2 x 0,75 mm²<br />
2: Reheater valve 5 x 1,5 mm²<br />
3: Outdoor temperature sensor 2 x 0,75 mm²<br />
4: On-site BMS connections provided by others according to wiring diagram<br />
5: Fully assembled system cable is not necessary (standard in switch cabinet)<br />
6: Power supply 3 x 400 V+N+PE/ 50 Hz<br />
7: Connection for pool water pump (option); 3 x 1,5 to 037 if more 6 x 1,5 mm² (400 V)<br />
8: Connection for reheater pump; 3 x 1,5 mm to 037 if more 6 x 1,5 mm² (400 V)<br />
9: External safety shut-down only on request<br />
10: Inlet temperature sensor, heater 2 x 0,75 mm²<br />
11: Room temperature and humidity sensor 5 x 0,75 mm²<br />
54 PR-2008-0327-GB • Subject to modifications • Status 05/2009