26.01.2015 Views

GEA CAIRfricostar - Aspectenvironmental.com

GEA CAIRfricostar - Aspectenvironmental.com

GEA CAIRfricostar - Aspectenvironmental.com

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Heat recovery system:<br />

Heating section:<br />

<strong>GEA</strong> motor 3-way mixing<br />

valve:<br />

Control and regulation<br />

system<br />

The switch cabinet is<br />

supplied with the following<br />

main <strong>com</strong>ponents:<br />

Dehumidifier with Air Mixing Function<br />

Type CWP<br />

<strong>GEA</strong> „ECOPLAT2 POWER PLATE“<br />

– 2 symmetric high performance plate heat exchangers for recuperative heat<br />

recovery<br />

2 cross flow aluminium plate heat exchangers (corrosion protected Al99 with best<br />

temperature coefficient) in row switch. Surface is additionally coated with thermoplastic<br />

material. Largest possible heat exchange surface using entire unit depth<br />

with minimum pressure losses. Optimal selection with consideration of operation<br />

conditions. Best efficiency rates within entire outdoor temperature range, especially<br />

resistant to corrosion and wear. Swimming pool configuration.<br />

– „Upside Down“ installation for smaller internal pressure drops.<br />

– AlMg3 ventilation tray<br />

– Technical data checked according to EUROVENT<br />

– Conform with VDI 6022<br />

– Non-<strong>com</strong>bustible according to fire protection regulation<br />

L.P.H.W. air heater, heat exchanger with copper pipes and drawn aluminium fins in<br />

aluminium frame AlMg3 (max. temp. 110°C, Pmax 16 bar) removable in accordance<br />

with VDI 6022;<br />

– For air reheater, supplied loose including actuator 0-10 V with an automatic step<br />

measurement system for fine adjustment of water flow rate<br />

– Supplied loose, installation by others<br />

– Consists of a separate switch cabinet for mounting on units or separate installation<br />

(depending in unit size), with all necessary <strong>com</strong>ponents for control functions, wired<br />

according to VDE specifications. IP55 electrical connection (via plug or screw terminals)<br />

between control cabinet and unit using factory prepared and fully assembled<br />

lines. Electrical installation for voltage supply, valve mixing control, reheater<br />

pump, if necessary external sensor and possibly other functions like remote control<br />

inputs by others. The cabinet is supplied loose depending on the unit size as a<br />

stand alone cabinet or for mounting on the unit<br />

– Main isolating switch for all pole shut-down of the electrical unit, lockable<br />

– Group fuses for fan and <strong>com</strong>pressor<br />

– Fuses for reheater 230V/N/PE/50Hz (types 015-083)<br />

3 X 400V/NPE/50Hz (types 100-320)<br />

(if necessary - motor protection by others)<br />

– Control fuses, control transformer 230 V and control voltage supply<br />

unit 24V DC for the digital control<br />

– Control fuse and control voltage supply unit 24V AC for actuators<br />

– Automatic phase controller (option)<br />

– Indoor installation, frost free<br />

Air mixing dehumidifier CWP<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 39