Air mixing dehumidifier CAC<br />

<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidification Unit with Air Mixing Function<br />

Type CAC<br />

Functional description of the unit<br />

The <strong>GEA</strong> <strong>CAIRfricostar</strong> CAC is designed for private and small public swimming pools.<br />

The series is available in 2 model and 3 capacity sizes. The unit's function is to dehumidify<br />

and heat air in swimming pools in air mixing mode. The unit is delivered with a<br />

DDC controls which regulates all functions of the system on a fully automated basis.<br />

When in idle mode without dehumidification the air is recirculated in the swimming pool.<br />

When the humidity setpoint has been exceeded the unit switches into dehumidification<br />

mode. At this point the supply air fan is switched into speed 2 with the exhaust air fan<br />

maintaining air circulation at speed 1. The refrigeration unit is activated in order to start<br />

dehumidification. Using the bypass damper a certain part of return air is mixed without<br />

further treatment with dehumidified air that has passed through the refrigeration cycle.<br />

The dehumidification stage continues until the actual humidity value lies below that of<br />

the humidity setpoint. Then fans and refrigeration unit are deactivated.<br />

When in active hours swimming pool mode the fresh and exhaust air dampers are<br />

opened, the bypass damper is closed. The dehumidification takes place via the<br />

activation of the refrigeration cycle with both fans switched into speed 2.<br />

Using an optional pool water condenser a certain amount of excess energy produced<br />

by the refrigeration cycle can be fed back into swimming pool water.<br />

Sample selection of operation modes:<br />

Idle mode without dehumidification<br />

demand<br />

Idle mode with dehumidification<br />

demand<br />

Active hours swimming pool mode<br />

with humidification demand and pool<br />

water condenser<br />

Bypass damper mode, exhaust air fan is deactivated,<br />

supply air fan runs at low speed.<br />

Bypass damper mode, exhaust air fan runs at<br />

low speed, supply air fan runs at high speed.<br />

Compressor is switched on. The reheater<br />

provides the missing residual heat supply.<br />

Air mixing operation according to VDI,<br />

exhaust and supply air fans run at high<br />

speed. Compressor is switched on. The reheater<br />

provides the missing residual heat<br />

supply. Using a pool water condenser a certain<br />

amount of excess energy can be fed<br />

back into swimming pool water.<br />

PR-2008-0327-GB • Subject to modifications • Status 05/2009 43