<strong>GEA</strong> <strong>CAIRfricostar</strong><br />

Dehumidification unit with air mixing and heat pump function<br />

Type CMU<br />

Functional description of the unit<br />

The <strong>GEA</strong> <strong>CAIRfricostar</strong> CMU is designed for private and small public swimming pools.<br />

The series is available in 6 sizes. The unit's function is to dehumidify and heat air in<br />

swimming pools in air mixing mode. The unit is delivered with a DDC controls which<br />

regulates all functions of the system on a fully automated basis.<br />

When in idle mode without dehumidification the air is recirculated in the swimming pool.<br />

When the humidity setpoint has been exceeded the unit switches into dehumidification<br />

mode. At this point the supply air fan is switched into speed 2 and the exhaust air fan<br />

maintains air circulation at speed 1. The refrigeration unit is activated in order to start<br />

dehumidification. Using the bypass damper a certain part of return air is mixed without<br />

further treatment with dehumidified air that has passed through the refrigeration cycle.<br />

The dehumidification stage continues until the actual humidity value lies below that of<br />

the humidity setpoint. After that the fan is switched back into previous speed and the<br />

refrigeration cycle is stopped.<br />

When in active hours swimming pool mode the fresh and exhaust air dampers are<br />

opened, the bypass damper is closed. The dehumidification takes place via the activation<br />

of the refrigeration cycle with both fans switched into speed 2.<br />

Using an optional pool water condenser a certain amount of excess energy produced<br />

by the refrigeration cycle can be fed back into swimming pool water.<br />

Air mixing dehumidifier CMU<br />

Sample selection of operating modes:<br />

Idle mode without dehumidification<br />

demand<br />

Idle mode with dehumidification<br />

demand<br />

Active hours operation mode with<br />

dehumidification demand<br />

28°C<br />

H<br />

Bypass damper mode, exhaust air fan is deactivated,<br />

supply air fan runs at low speed.<br />

Bypass damper mode, exhaust air fan runs at<br />

low speed, supply air fan runs at high speed.<br />

The reheater provides the missing residual<br />

heat supply.<br />

Air mixing operation according to VDI, exhaust<br />

and supply air fans run at high speed.<br />

Compressor is switched on. The reheater<br />

provides the missing residual heat supply.<br />

Using a pool water condenser a certain<br />

amount of excess energy can be fed back<br />

into swimming pool water.<br />

Transition and summer mode with/without<br />

dehumidification demand<br />

Summer mode inactive period „free night cooling“<br />

In case of overheating of the swimming pool and high outdoor temperatures<br />

the heat pump is blocked. The unit operates for ventilation<br />

and dehumidification in air mixing or only outdoor/exhaust air mode.<br />

The fans run at high speed. In case of an optional bypass of the heat<br />

recovery system the latter is not used thanks to a damper system.<br />

If the swimming pool is overheated during the night time or idle period<br />

the unit ventilates only in outdoor/exhaust air mode. The fans run at<br />

high speed and provide cooling of the swimming pool to reach the<br />

setpoint temperature.<br />