<strong>GEA</strong> <strong>CAIRfricostar</strong><br />
Dehumidification Unit with Air Mixing and Heat Pump Function<br />
Type CWC<br />
– Coated Almg3 damper blades with flow efficient profile, operate in opposite directions.<br />
Driven by double sided, anti-static plastic gears PA6 as fiberglass reinforced<br />
model (resistant to chemicals) including special actuator for each damper<br />
– Control of the individual actuators using continuous DDC signals<br />
Filter for fresh and<br />
exhaust air:<br />
– Filter units conform with VDI 6022<br />
– including bag filter as of DIN/EN 779, synthetic fiber filter medium<br />
– All filters are fitted with a differential pressure switch for filter-monitoring via the<br />
DDC<br />
Heat recovery system: <strong>GEA</strong> „ECOPLAT POWER PLATE“:<br />
– symmetric high performance plate heat exchangers, recuperative heat recovery by<br />
using two cross-flow aluminium plate heat exchangers (corrosion protected Al99<br />
with best temperature coefficient). Surface is additionally coated with thermoplastic<br />
material. Largest possible heat exchange surface using entire unit depth with minimum<br />
pressure losses. Optimal selection with consideration of operation conditions.<br />
Best efficiency rates within entire outdoor temperature range, especially resistant to<br />
corrosion and wear. Swimming pool configuration.<br />
– AlMg3 ventilation tray<br />
– technical data checked according to EUROVENT<br />
– conform with VDI 6022<br />
– Non-<strong>com</strong>bustible according to fire protection regulation<br />
Heating section: – L.P.H.W. air heater, heat exchanger with copper pipes and drawn aluminium fins in<br />
aluminium frame AlMg3 (max. temp. 110°C, Pmax 16bar) removable in accordance<br />
with VDI6022;<br />
<strong>GEA</strong> motor -3-way mixing<br />
valve:<br />
Control and<br />
regulation system<br />
The switch cabinet is<br />
supplied with the following<br />
main <strong>com</strong>ponents:<br />
– For air reheater, supplied loose including actuator 0-10 V with an automatic step<br />
measurement system for fine adjustment of water flow rate<br />
– supplied loose, installation by others<br />
– Consists of a separate switch cabinet for mounting on units or separate installation<br />
(depending in unit size), with all necessary <strong>com</strong>ponents for control functions, wired<br />
according to VDE specifications. IP55 electrical connection (via plug or screw terminals)<br />
between control cabinet and unit using factory prepared lines. Electrical<br />
installation for voltage supply, valve mixing control, reheater pump, if necessary<br />
external sensor and possibly other functions like remote control inputs are provided<br />
by others. The cabinet is supplied loose depending on the unit size as a stand alone<br />
cabinet or for mounting on the unit;<br />
– Main isolating switch for all pole shut-down of the electrical unit, lockable<br />
– Group fuses for fans<br />
– Fuses for reheater 230V/N/PE/50Hz (types 015-083) 3 X 400V/NPE/50Hz (types<br />
100-320) (if necessary - motor protection by others)<br />
– Control fuses, control transformer 230 V and control voltage supply unit 24V DC for<br />
the digital control<br />
– Control fuse and control voltage supply unit 24V AC for actuators<br />
– Automatic phase controller (option)<br />
– Indoor installation, frost free<br />
Digital control: – Modular automation station built into switch cabinet with deletion-proof software<br />
modules and digital and analogue inputs and outputs, equipped with all control<br />
functions for swimming pool dehumidifier, consisting of:<br />
– Control unit with 32 bit processor in network based, interdisciplinary, free programmable<br />
automation system<br />
– Watchdog function, data buffering (FLASH-ROM), hardware clock<br />
– Interfaces: 1 x CAN (Controller Area Network) as central bus between control<br />
unit and I/O modules; 1 x LIN (Local Interconnect Network) for auxiliary module<br />
monitoring and configuration functions; 1 x CAN for external connection; 2 x<br />
RS232/RS485, one RS232 has modem function; optional: Ethernet; USB plug;<br />
optionally - various <strong>com</strong>munication functions can be carried out (e. g: OPC;<br />
PR-2008-0327-GB • Subject to modifications • Status 05/2009 51<br />
Air mixing dehumidifier CWC