EC-TYPE EXAMINATION CERTIFICATE<br />

<strong>Co</strong>mponent intended for use onlin equipment or protective system<br />

intended foe use in Potentially Explosive Armospheres<br />

Directive 94/9/EC<br />

[3] EC-Type Examination Certificate Number: DEMKO 03 ATEX 134439 U<br />

[4] <strong>Co</strong>mponents; Printed Circuit Board Terminal Blocks Type TOP 1,S/GSI ..<br />

(for models see Schedule)<br />

[5] Manufacturer: <strong>Weidmüller</strong> <strong>Interface</strong> <strong>GmbH</strong> & <strong>Co</strong>.<br />

[6] Address: Klingenbergsuaße 16,32758 Detmold, Germany<br />

[7J This <strong>Co</strong>mponem aod aoy acceptable variation therero is specified in the schedule to (his certificate<br />

aud the documems (herein referrcd to.<br />

[8] UL International Demko AIS, notified body number 0539 in accordance wirh Artide 9 of the<br />

<strong>Co</strong>uncil Directive 94/9/EC oE 23 March 1994, certifies that this component has been fallod to<br />

comply with the Essential Health and Safety Requirements relating to design and construction of<br />

componems intended for use in potentially explosive atmospheres given in Annex 11 to the<br />

Directive.<br />

The examination and test resuhs are recorded in confidential test report no. 134439.<br />

[9] <strong>Co</strong>mpliance with the Essential Health and Safety Requirements has bccn assuf(~J by compliance<br />

with:<br />

EN 50014, 1997 EincI. Ai+A2 EN 50019, 2002 E EN 50281-1-1,1998 E<br />

[101 The sign "D" placed after the certificate number indicates that this certificate mustnot be misraken<br />

fm a certificate intended far an equipmem or protective system. This partial certification may be<br />

t1sed as a basis for ccrtification of an equipment or protective system.<br />

[11] This EC-Type examination certificate rdates only to the design, examination anJ te.•• ts of the<br />

specified component in accordance with the Directive 94/9/EC. Further requiremenrs of the<br />

Directivc apply to the manufacruring process and supply of this componenr. These are not covered<br />

by this certificate.<br />

[12] The marking of the component shall include the following:<br />

G II 2 GD EEx e II<br />

01~~I,IL Intemational Oemko AIS<br />

~ristiansen<br />

Certification Manager<br />

UL International Demko AlS Cmifi"", 03 ATEX 134439 U ®<br />

Herlev, 2003·06-10<br />

An Affilia" 01 "\<br />

~~-~;;g'~~~~~e;~~rk ------------ VL Underwriters<br />

Telephone: +45 44856565 enrr:;:r~i~~:I:::~~~t~~;~~~~~~~:i~<br />

LaboratoriBS Inc.~<br />

Fax:+45441:J5ö5UlI


[131 Schedule<br />

[14] EC-TYPE EXAMINATION CERTIFICATE No.<br />

DEMKO 03 ATEX 134439 U<br />

[15] Description<br />

Printed Circuit Board Terminal Blocks type TOP L5/GS/ .., for the connection of copper<br />

conductors to electronic circuit on printcd circuit boards which are installed in endosures<br />

in type of explosion proteetion increased safety "e". Thc insulating parts are made of<br />

Wemid.<br />

Thc ambiem temperaturc range is ·20 oe .. +100 oe.<br />

Elecrrical data<br />

Type:<br />

TOP 1.5/GS/1...12/180/5,0<br />

TOP 1,5/GS/1...12/180/5,08<br />

TOP 1,5/GS/1 ... 12/90/5,0<br />

TOP 1.5/GS/1...12/90/5.08<br />

TOP 1.5/GS/1. .12/180/7.5<br />

TOP 1,5/GS/1...12/18017,62<br />

TOP 1,5/GS/1...12/90/7,5<br />

TOP 1,5/GS/J...12/90/7,62<br />

Ratcd voltage<br />

175 V<br />

275 V<br />

Rated conductor cross section for all above mentioned types is 1,5mm (14 AWG).<br />

Rated eurrem:<br />

Mouming insrructions<br />

Primed Circuit Board Terminal Blocks type TOP L5/GSI .., are suitable fot application in endosures in<br />

atmospheres wirh ßammable gases and combusrible dust. For flammable gasc:s these endosures must<br />

satisfy the tequirements according to EN 50014 and EN 50019. Fot combustible dust these enclosures<br />

must satisfy the requirements according to EN 50281-1-1.<br />

If smaller cross sections than the rated cross section are used, the be10nging lower current has (0 be laid<br />

down in the EC-Type Examination Certificate of the compIete apparatus.<br />

Routine tests<br />

According to EN 50019, Clause 7.1.b in combination with Clause 6.1, a routine die1ectric strength test<br />

has to be carried out. This can be done on a statistical basis.<br />

[16] Report No.<br />

Project Report No.: 134439-02 (Hazardous Location Testing)<br />

UL International Demko AIS<br />

Lyskaer8,P.O,Box514<br />

OK-2730Herlev,Del1mark<br />

Telephone: +4544856565<br />

Fax: +4544856500<br />

Cmificate: 03 ATEX 134439 U<br />

Report: 134439·02<br />

IlllscerUllCatemayonlYDereproducCUlnns<br />

entirety and without any change, ~chedu[e indudcd<br />

®<br />

12A<br />

12A<br />

<strong>AnAffillatea</strong>' P 2/3<br />

UL UndBrwriters<br />

• Laboratories Ine.,


[13]<br />

[14]<br />

Drawings:<br />

Number<br />

334211,