12.07.2015 Views

1511 Series - Maintenance Manual

1511 Series - Maintenance Manual

1511 Series - Maintenance Manual

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

XVI. ContinuedASME Boiler andPressure VesselCode Section andSymbolVCODE SYMBOLSTAMPASME Section IUVCODE SYMBOLSTAMPASME Section VIIITable 9Set Pressure Tolerance (The valve must“POP” open within the range indicatedbelow.)If valve set pressure is less than or equal to70 psig (4.83 barg):±2 psig (±0.14 barg)If valve set pressure is 71 psig (4.9 barg) upto and including 300 psig (20.68 barg):±3% of set pressureIf valve set pressure is 301 psig (20.75 barg)up to and including 1000 psig (68.95 barg):±10 psig (±0.69 barg)If valve set pressure is 1001 psig (69.02barg) or greater±1% of set pressureIf valve set pressure is less than or equal to70 psig (4.83 barg):±2 psig (±0.14 barg)If valve set pressure is 71 psig (4.9 barg) orgreater±3% of set pressureBlowdown RequirementsAfter opening, the valve must reclosewithin a range of 98% to 96%, however,if the valve set pressure is 100 psig(6.9 barg) or less the valve must reclosewithin a range of 2 to 4 psig (0.14 to 0.28barg) below set pressure.After opening the valve must reclosebefore the system pressure returns tonormal operating pressure.DRESSER RECOMMENDS THAT THE MAXIMUM OPERATING PRESSURE NEVER EXCEEDS 94% OF THE SETPRESSURE OF <strong>1511</strong> SERIES SAFETY VALVE.5 When presetting is complete, remove the gag andreplace the cap and lifting lever assembly. Attach arope to the lever and stand by to hold the valve openif necessary. Now the valve is ready to test.6. Increase the boiler pressure at a rate not to exceed2 psi (0.14 bar) per second. Note and record thepressure indicated on the pressure guage when thevalve pops open. After the valve pops open, reducethe fire in the boiler and lower the pressure until thevalve closes. Note and record the pressure when thevalve closes.7. Determine if the valve popping point and reseatingpoint comply with the ASME requirements.a. If the valve operation meets the appropriatestandard, raise the pressure in the boiler andconduct two more verification tests.b. If in raising the boiler pressure, the valve doesnot pop open within 3% overpressure (for ASMESection I valves), or 10% overpressure (for ASMESection VIII valves), reduce the fire in theboiler and pull the rope to open the valve.Release the rope and allow the valve to closewhen the boiler pressure returns to operatinglevel. Allow the boiler to reduce to approximately85% of the set pressure. Remove the cap andlifting lever assembly from the valve, and turn thecompression screw lock nut counter-clockwise(as viewed from the top of the valve) until it movesfreely. Reduce the compression in the spring byturning the adjusting screw counter clockwiseone turn (as viewed from the top of the valve).Replace the cap and lifting lever and retest thevalve. Continue repeating this procedure untilthe valve opens at, or below, the set pressurerecorded on the nameplate.c. If the valve opens at a pressure below therecorded set pressure, allow the valve to closeand the boiler pressure to reduce to 85% of setpressure. Increase the compression on the springby turning the compression screw clockwise1/6th of a turn. Tighten the adjusting screw locknut and replace the cap and lifting lever assembly.22 | Dresser Consolidated ®

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!