- Page 1 and 2: INVERTER MULTI-SPLIT SYSTEMROOM AIR
- Page 3 and 4: 5 APPLICATION DATA ................
- Page 5 and 6: 2 SELECTION DATA2.1 Specifications(
- Page 7 and 8: Models SKM60ZG-S, 71ZG-SItemModelSK
- Page 9 and 10: ModelsSRRM25ZF-S, 35ZF-S, 50ZF-S, 6
- Page 11 and 12: ModelsSCM48ZG-SSCM60ZG-SItemCooling
- Page 13 and 14: (3) Operation data¡ The combinatio
- Page 15 and 16: 1room2room3roomModel SCM48ZG-S(a) H
- Page 17: 1room2room3roomModel SCM60ZG-S(a) H
- Page 22 and 23: 3room4roomModel SCM80ZG-S(a) Heatin
- Page 24: 4roomModel SCM80ZG-S(a) HeatingIndo
- Page 28 and 29: 4roomModel SCM80ZG-S(b) CoolingIndo
- Page 30 and 31: 2.3 Exterior dimensions(1) Indoor u
- Page 32 and 33: (2) Outdoor unitModels SCM40ZG-S, 4
- Page 34 and 35: Gas line(ø9.52)Outdoor unitService
- Page 36 and 37: Gas lineSensor(ThI-R2)Indoor Unit(
- Page 38 and 39: 2.5 Selection chartCorrect the cool
- Page 40 and 41: Models SKM60ZG-S, 71ZG-STBHEATEXCHA
- Page 42 and 43: - 39 -Power Source1 Phase220-240V 5
- Page 44 and 45: - 41 -Power Source1 Phase220-240V 5
- Page 46 and 47: 4 OUTLINE OF OPERATION CONTROL BY M
- Page 48 and 49: Unit indlcation sectionS SKM20~50 m
- Page 50 and 51: 4.3 Drain motor forced operation fu
- Page 52 and 53: 4.7 Flap and louver control (SKM, S
- Page 54 and 55: 4.8 3D auto operation (SKM only)Con
- Page 56 and 57: 4.11 Outline of heating operation(1
- Page 58 and 59: (c) SCM80ZG-S◆SKM modelModelFan s
- Page 60 and 61: 4.12 Outline of cooling operation(1
- Page 62 and 63: (c) SCM80ZG-S◆ SKM modelModelFan
- Page 64 and 65: 4.14 Operation permission/prohibiti
- Page 66 and 67: 4.16 Protective control function(1)
- Page 68 and 69:
(5) Freezing cycle system protectiv
- Page 70 and 71:
(10) Heating overload protection co
- Page 72 and 73:
(18) Rotor lockIf the motor for the
- Page 74 and 75:
5.1 Installation of indoor unit(1)
- Page 76 and 77:
4) Installing the support of piping
- Page 78 and 79:
(b)Installation of indoor unit1) In
- Page 80 and 81:
B. When embedded into ceiling1. Det
- Page 82 and 83:
k) Attach two chains to the intake
- Page 84 and 85:
6) Installing the Main Unit7) Secur
- Page 86 and 87:
5.4 Electrical wiringunit A unit B
- Page 88 and 89:
(2) ConnectionIndoorLiquid sideGas
- Page 90 and 91:
Beware of wrong connections in refr
- Page 92 and 93:
(2) Indication of self diagnosisInd
- Page 94 and 95:
(3) Inspection procedures correspon
- Page 96 and 97:
Over heat of compressor[Gas shortag
- Page 98 and 99:
(b)SensorHeat exchangersensorOutdoo
- Page 100 and 101:
(7) Inverter failure diagnosisIf th
- Page 102 and 103:
- 99 -SSCM48ZG-SCAUTION - HIGH VOLT
- Page 104 and 105:
- 101 -SSCM80ZG-SCAUTION - HIGH VOL
- Page 106 and 107:
6.2 Servicing(1) EvacuationThe evac
- Page 108 and 109:
q Wired remote control systemRoom a
- Page 110 and 111:
Connecting the interface and the in
- Page 112 and 113:
Super link adapter connectionSee th
- Page 114 and 115:
7.2 Wired remote controlThe figure
- Page 116 and 117:
(2) Installation of wired remote co
- Page 118 and 119:
(b)Function setting method1) Stop t
- Page 120 and 121:
(c)Changing the remote control set
- Page 122 and 123:
(3) Super link adapter connectionSe
- Page 124 and 125:
7.4 Ducted type (SRRM) optional par
- Page 126 and 127:
◆Air flow and external static pre
- Page 128 and 129:
4) Use hard PVC general purpose pip
- Page 130 and 131:
(3) Lubricating oils for R410AAs th
- Page 132 and 133:
43°~45°d) Flare processingMake ce
- Page 134 and 135:
(2) Identificationa) Piping setA co
- Page 136 and 137:
ReducingvalveNitrogen gasMFlow mete
- Page 138 and 139:
e) Flare tool (clutch type)• A fl
- Page 140 and 141:
f) After charging liquid refrigeran
- Page 142 and 143:
(4) Recovering proceduresa) Accordi
- Page 144: