2.2 Range of usage & limitationsItemIndoor intake air temperature(Upper, lower limits)Outdoor air temperature(Upper, lower limits)Indoor unitsthat can beused incombinationModelsCoolingHeatingCoolingHeatingNumber of connected unitsTotal of indoor Units (class kW)SCM40ZG-S SCM45ZG-S1 to 2 units5.7kW 7.0kWSCM48ZG-S SCM60ZG-S SCM80ZG-S18 to 32°C15 to 30°C-15 to 43°C-15 to 24°C2 to 3 units ※3 to 4 units8.5kW 11.0kW 13.5kWTotal length for all roomsMax. 30mMax. 40mMax. 70mLength for one indoor unitMax. 25mDifference inheight betweenindoor and outdoorunitsWhen indoor unit is aboveoutdoor unit (A)When indoor unit is belowoutdoor unit (B)15m15m20m20mDifference in height between indoor units (C)Max. 25mCompressorstop/startfrequencyPower sourcevoltage1 cycle timeStop timeVoltage fluctuationVoltage drop during startInterval unbalance6 min or more (from stop to stop or from start to start)3 min or moreWithin ±10% of rated voltageWithin ±15% of rated voltageWithin ±3% of rated voltage※ Only combination of SKM60 + SKM60 and SKM60 + SKM71 (2 indoor units) to SCM80ZG-S can be abailable.CAB- 26 -