When All lamps flash ON and OFF every 0.5-second.Indoor unit and outdoor unit do not operate.ECheck of installation of the horizontal vaneTurn OFF thepower supply.Is the stopper of the horizontal vanelocked to the indoor unit correctly?YesNoRelock the stopper of thehorizontal vane to the indoor unit.(Refer to 10-1.5.)Turn ON thepower supply.Are all lamps flashing?YesNoOKTo check the continuity of the interlock switch(Fan), measure the resistance of connector 1 - 2connected to CN1R1 on the indoorelectronic control P.C. board.Turn OFF thepower supply.Is there resistance 0 "?YesNo(∞)Replace theinterlock switch(Fan).Replace theindoor electroniccontrol P.C. board.23