1231415INSTALLATION STEPSThe pipe ends must have a square, even cut.Remove any burrs or shavings from the pipe ends.Clean pipe ends inside and out with authorizedcleaner to remove any dirt or contaminants, andallow to dry.Measure the insertion depth of the fitting. Add 20mmto this and mark this length on the pipe end.Scrape pipe up to measurement mark to remove alloxidation andcontaminants. Usepreferably a <strong>Plasson</strong>Rotational Scraper.One pass (or approx.as shown in table)of pipe surface is tobe removed. Do notuse metal files oremery paper.41617Clean withauthorized cleanerand allow to fullydry beforeproceeding. Donot touch theprepared surfaces.Note: Fittingsspigot ends canbe scraped andmust be cleaned.d Scraping Depth20 - 25 0.2 mm32 - 75 0.25 mm90 0.3 mmRemove fitting from plastic bag. Slide fitting ontopipe until it reaches the center stops of the fitting.Check measurement mark for proper insertion depth.If the fitting cannot be correctly inserted on to thepipe due to ovality, the pipe will need to be reroundedusing rerounding clamps. Use a <strong>Plasson</strong>Rotational Scraper to reduce oversize pipe.Repeat steps 1 through 6 for the opposite end ofthe fitting.