Protection, monitoring and controlTest operation for VIP relaysRange offer descriptionand technical features Primary injection testA primary injection circuit may be permanently installed (option)through the CTs, inside the cubicle, to test the physical integrityof the complete protection system including the CTs- The test is carried out without disconnectingthe CTs and the VIP relay displays the injected current during testing- If necessary, a temporary VIP test mode can be activated to testthe tripping of the circuit breaker by pressing a test pushbutton1 231. VIP2. Pocket Battery3. Injection test caseTest withthe PocketBattery moduleThis accessory can beconnected on the VIPrelay front plate toenergize the relay tocarry out a quick testeven though the relayis not powered.The temporary testmode can be activatedwith the keypad to testthe circuit breakerRange<strong>Schneider</strong> <strong>Electric</strong> – Infrastructure Business – MV <strong>Premset</strong> presentation – January 2012 70