Designer’s Guide / Knight XL BoilerLOCHINVAR CORPORATION300 MADDOX SIMPSON PKWYLEBANON, TN 37090www.lochinvar.com4. DIRECT OUTSIDE AIR, SINGLE OPENINGIf a single combustion air opening is provided to bringcombustion air in directly from the outdoors, the openingmust be sized based on a minimum free area <strong>of</strong> onesquare inch per 3000 Btu/hr (7 cm² per kW). This openingmust be located within 12" (30 cm) <strong>of</strong> the top <strong>of</strong> theenclosure.CautionTHE COMBUSTION AIR MUST BE FREE OF ANY CONTAMINANTS OR CHEMICAL FUMES. SALTS,REFRIGERANTS AND SOLVENTS INTRODUCED INTO THE COMBUSTION PROCESS WILL RESULT INTHE FORMATION OF CORROSIVE ACIDS THAT WILL DAMAGE THE APPLIANCE AND THE VENT.COMBUSTION AIR FILTERThe Knight XL has an optional air filter box. Locatedon the left side over the combustion air inlet, the airfilter is installed to help ensure clean air is used for thecombustion process. The optional air filter box kit ispart number KIT40002.The filter size is 12" x 12" x 1" (40.6 cm x 30.4 cm x 2.5cm). You can find these commercially available filtersat any home center or plumbing supply store.14