10 Powered by Safety ®<strong>Metal</strong>-<strong>Enclosed</strong> <strong>Bus</strong> <strong>IB</strong>-<strong>DU1000</strong>E. Field TestingA one minute AC high potential test can be performed at 75% of the factory test voltage indicated on the test tagshipped attached to each section of bus. This test is in accordance with ANSI C37.23. See Table 1. The test voltageis applied phase-to-phase and phase-to-ground. If an AC test set is not available, a one minute DC test may beused. All internal components of the bus must be CLEAN and DRY before performing the high potential test.Operation of the bus heaters a minimum of 72 hours before performing a high potential test is recommended.Voltage and Insulation Levels<strong>Bus</strong> RatingInsulation Level (kV)Field TestOne Minute WithstandRated MaximumkV (RMS)Power Frequency Withstand(RMS) Dry One MinuteImpulseWithstandACkV-RMSDCkV0.635 2.2 NA 1.65 2.34.76 19.0 60 14.25 20.2515.00 36.0 95 27.00 37.5015.50 50.0 110 37.50 52.5025.80 60.0 125 45.00 63.7538.00 80.0 150 60.00 84.00