GENERALHAZARd-OUSVOLTAGEINSTAL-LATIONWARNINGThis module is designed for connection to hazardous electricvoltages. Ignoring this warning can result in severe personalinjury or mechanical damage. To avoid the risk of electric shockand fire, the safety instructions of this manual must be observedand the guidelines followed. The specifications must not beexceeded, and the module must only be applied as describedin the following. Prior to the commissioning of the module, thismanual must be examined carefully. Only qualified personnel(technicians) should install this module. If the equipment is usedin a manner not specified by the manufacturer, the protectionprovided by the equipment may be impaired.WARNINGUntil the module is fixed, do not connect hazardous voltages tothe module. The following operations should only be carried outon a disconnected module and under ESD safe conditions:Dismantlement of the module for setting of DIP-switchesand jumpers.General mounting, connection and disconnection of wires.Troubleshooting the module.Repair of the module and replacement of circuit breakersmust be done by PR electronics A/S only.WARNINGTo keep the safety distances, the module must neither beconnected to hazardous nor non-hazardous voltages on thesame module’s relay contacts. SYSTEM 5000 must be mountedon DIN rail according to DIN 46277. The communicationconnector of SYSTEM 5000 is connected to the input terminalson which dangerous voltages can occur, and it must only beconnected to the programming unit Loop Link by way of theenclosed cable.Triangle with an exclamation mark: Warning / demand.Potentially lethal situations.The CE mark proves the compliance of the module withthe essential requirements of the directives.The double insulation symbol shows that the moduleis protected by double or reinforced insulation.Ex modules have been approved for use in connectionwith installations in explosive areas.Safety instructionsDefinitions:Hazardous voltages have been defined as the ranges: 75 to 1500 Volt DC, and50 to 1000 Volt AC.Technicians are qualified persons educated or trained to mount, operate, andalso troubleshoot technically correct and in accordance with safety regulations.Operators, being familiar with the contents of this manual, adjust and operate theknobs or potentiometers during normal operation.Receipt and unpacking:Unpack the module without damaging it and make sure that the manual alwaysfollows the module and is always available. The packing should always follow themodule until this has been permanently mounted.Check at the receipt of the module whether the type corresponds to the oneordered.Environment:Avoid direct sunlight, dust, high temperatures, mechanical vibrations and shock,as well as rain and heavy moisture. If necessary, heating in excess of the statedlimits for ambient temperatures should be avoided by way of ventilation.All modules fall under Installation Category II, Pollution Degree 1, and InsulationClass II.Mounting:Only technicians who are familiar with the technical terms, warnings, andinstructions in the manual and who are able to follow these should connect themodule.Should there be any doubt as to the correct handling of the module, pleasecontact your local distributor or, alternatively,PR electronics A/S, Lerbakken 10, DK-8410 Rønde, Denmark,tel: +45 86 37 26 77.Mounting and connection of the module should comply with national legislationfor mounting of electric materials, i.a. wire cross section, protective fuse, andlocation. Descriptions of input / output and supply connections are shown in theblock diagram and side label.18 19


The following apply to fixed hazardous voltages-connected modules:The max. size of the protective fuse is 10 A and, together with a powerswitch, it should be easily accessible and close to the module. Thepower switch should be marked with a label telling it will switch off thevoltage to the module.Year of manufacture can be taken from the first two digits in the serial number.Calibration and Adjustment:During calibration and adjustment, the measuring and connection of externalvoltages must be carried out according to the specifications of this manual.The technician must use tools and instruments that are safe to use.Normal operation:Operators are only allowed to adjust and operate modules that are safely fixed inpanels, etc., thus avoiding the danger of personal injury and damage. This meansthere is no electrical shock hazard, and the module is easily accessible.Cleaning:When disconnected, the module may be cleaned with a cloth moistened withdistilled water.Liability:To the extent the instructions in this manual are not strictly observed, thecustomer cannot advance a demand against PR electronics A/S that wouldotherwise exist according to the concluded sales agreement.As manufacturerEC declaration of conformityPR electronics A/SLerbakken 10DK-8410 Røndehereby declares that the following product:Type: 5223Name: Programmable f/I - f/f converteris in conformity with the following directives and standards:The EMC Directive 2004/108/EC and later amendmentsEN 61326-1 : 2006For specification of the acceptable EMC performance level, refer to theelectrical specifications for the module.The Low Voltage Directive 2006/95/EC and later amendmentsEN 61010-1 : 2001The ATEX Directive 94/9/EC and later amendmentsEN 50014 : 1997, EN 50020 : 2002 and EN 50284 : 1999ATEX certificate: KEMA 04ATEX1001 (5223B)No changes are required to enable compliance with the replacement standards:EN 60079-0 : 2006 and EN 60079-11 : 2007Notified bodyKEMA Quality B.V. (0344)Utrechtseweg 310, 6812 AR ArnhemP.O. Box 5185, 6802 ED ArnhemThe NetherlandsRønde, 11 January 2010Kim RasmussenManufacturer’s signature20 21


How to dismantle system 5000First, remember to demount the connectors with hazardous voltages. By liftingthe bottom lock, the module is detached from the DIN rail as shown in picture 1.Then, by lifting the upper lock and pulling the front plate simultaneously, the PCBis removed as shown in picture 2.Switches and jumpers can now be adjusted. By opening the front, theprogramming connector is accessible as shown in picture 3.PROGRAMMABLE f/I - f/f <strong>CONVERTER</strong>5223• Pulse calculator• Frequency generator• Galvanic isolation, optional ATEX Ex• Analogue current and voltage output• PNP / NPN output, optional relays• Universal supplyPicture 1: Separation from DIN rail.Picture 3: Access to programmingconnector.---------------------------------------------------------------------------------------Supply voltage:24...250 VDC24...230 VAC---------------------------------------------------------------------------------------INPUT RANGE:Frequency:Sensor types:0...20000 HzNamur, tacho,NPN, PNP, TTL, S0---------------------------------------------------------------------------------------OUTPUT RANGE:Current and voltage output:0...20 mA / 0...10 VRelay outputs:0...20 HzNPN and PNP output as f/f:0...1000 HzNPN and PNP output as generator: 0...20000 Hz---------------------------------------------------------------------------------------In generalBy way of a standard PC and the Loop Link programming kit, the <strong>PRecon</strong> 5223f/I - f/f converter is configured acc. to the requested function.Alternatively, the 5223 may be delivered fully-configured acc. to your specifications,see the options index in the data sheet.Typical pulse sources are flow meters, tacho generators, mechanical switches, orinductive proximity sensors.Picture 2: Removal of PCB.22 23


ApplicationsThe f/I function performs frequency to current and voltage conversion.The output can be programmed to show period, meaning that the inputfrequency can be converted to a linear time signal.The digital outputs are used as e.g. a frequency watch for speed control or as awindow comparator having one status between 2 limits and the opposite statusoutside these limits.The f/f function can be used for pulse division or multiplication and as a buffercollecting fast pulse trains. The input pulses are calculated, counted in a buffer,and sent to the output as a pulse train with the programmed pulse width.A scale factor may be entered in all functions. Using both digital inputs, pulseaddition or subtraction are possible. This function permits readout of the actualconsumption at measurement of e.g. liquid flows forward and backward.The frequency generator function is used as e.g. a time base orclockgenerator.The 2-phase encoder, or directional f/I conversion, converts 2 90°-phased digitalinputs to an analogue speed signal with digital output for directional indica tion.ATEX Ex units have input for mechanical contact and NAMUR inductiveproximity sensor.Technical characteristicsInputs2 programmable inputs for standard pulse generator connection.Normally, the auxiliary supply and trigger level follow the sensor type, but thesecan be programmed to other values.At contact input, the 50 Hz filter should be applied.The <strong>PRecon</strong> 5223 is protected against polarity reversal on input and supply.Standard voltage output (pin 12) is obtained by leading the current signal (pin13) through an internal shunt resistor (pin 12). At voltage signals in the ranges0...1 VDC, a 50 Ω shunt (JP1) is applied; in the ranges 0...10 VDC, a 500 Ω shunt(JP2) is applied.Digital output(s)The action on the outputs can be inverted, and the hysteresis can be set acc. toyour specifications.At power up, shifts on the outputs can be delayed for up to 999 s.NPN and PNP outputs for external relay, electromechanical counter, PLC input,or equivalent load.The outputs are current-limited by way of PTC resistors.Relay outputsThe <strong>PRecon</strong> 5223 can be delivered with 2 relay outputs that are programmedindividual ly.Status indicationThe 5223 is equipped with 5 front LEDs.f1 and f2 in:Dig. out. 1 and 2:Error:Indicates an active input (non-active at NPN input).Indicates active output.Programmable by use of PReset to indicate sensorerrors.Analogue outputThe current and voltage signals are galvanically separated from the supply andthe inputs.The analogue current and voltage output can be scaled acc. to your choice inrelation to the digital input. Max. zero offset is 50% of selected measurementrange. Programmable response time.Short-circuit-protected output.When both current and voltage signals are used simultaneously, the mA loop toground must pass through the internal shunt.24 25


Electrical specificationsSpecifications range:-20°C to +60°CCommon specifications:Supply voltage............................................ 19.2...300 VDC21.6...253 VACFrequency................................................... 50...60 HzFuse............................................................ 400 mA T / 250 VACInternal consumption.................................. 3 WMax. consumption...................................... 3.5 WIsolation, test / operation............................ 3.75 kVAC / 250 VACPower up delay........................................... 0...999 sWarm-up time............................................. 1 min.Communications interface.......................... Loop LinkSignal / noise ratio...................................... Min. 60 dBResponse time, analogue........................... < 60 ms + periodResponse time, digital output..................... < 50 ms + periodSignal dynamics, output............................. 16 bitCalibration temperature.............................. 20...28°CTemperature coeffici ent.............................. < ± 0.01% of span / °CLinearity error.............................................. < ± 0.1% of spanEffect of supply voltage change................. < 0.005% of span / VDCAuxiliary voltages:NAMUR supply........................................... 8.3 VDC ± 0.5 VDC / 8 mANAMUR supply EEx.................................... 8.5 VDC ± 0.5 VDC / 8 mAS0 supply.................................................... 17 VDC / 20 mANPN / PNP supply...................................... 17 VDC / 20 mASpecial supply (programmable).................. 5...17 VDC / 20 mAEMC immunity influence............................. < ± 0.5%Max. wire size.............................................. 1 x 2,5 mm 2 stranded wireScrew terminal torque................................. 0.5 NmAir humidity.................................................


TTL input:Trig-level LOW............................................ ≤ 0.8 VDCTrig-level HIGH................................................. ≥ 2.0 VDCInput impedance......................................... ≥ 100 kΩS0 input acc. to DIN 43 864:Trig-level LOW............................................ ≤ 2.2 mATrig-level HIGH ................................................ ≥ 9.0 mAInput impedance......................................... 800 ΩAnalogue output:Current output:Signal range................................................ 0...20 mAMin. signal range........................................ 5 mAMax. offset.................................................. 50% of selected max. valueUpdating time............................................. 20 msLoad (max.)................................................. 20 mA / 600 Ω / 12 VDCLoad stability............................................... < ± 0.01% of span / 100 ΩCurrent limit................................................ ≤ 23 mAVoltage output through internal shunt:Signal range................................................ 0...10 VDCMin. signal span.......................................... 250 mVMax. offset.................................................. 50% of selected max. valueLoad (min.).................................................. 500 kΩActive outputs (NPN / PNP):Imax. source............................................... 10 mAImax. sink.................................................... 130 mAVmax........................................................... 28 VDCf/f converter output:Signal range................................................ 0...1000 HzMin. pulse width.......................................... 500 µsMax. pulse width......................................... 999 msMax. duty cycle........................................... 50%Relay output:Frequency max........................................... 20 HzVmax........................................................... 250 VRMSImax............................................................ 2 A / ACMax. AC power........................................... 500 VAMax. AC power Ex version 5223B.............. 100 VAMax. load at 24 VDC.................................. 1 A.EEx / I.S. approval -5223B:KEMA 04ATEX1001..................................... II (1) GD[EEx ia] IICApplicable in zone...................................... 0, 1, 2, 20, 21 or 22Ex / I.S. data:Terminal 31, 33Um.............................................................. : 250 VTerminal 42, 43 and 52, 53Uo............................................................... : 10.6 VDCIo................................................................. : 13.8 mAPo................................................................ : 38 mWLo................................................................ : 160 mHCo............................................................... : 1.9 µFGOST R approval:VNIIM & VNIIFTRI, Cert. no.......................... See www.prelectronics.comObserved authority requirements: Standard:EMC 2004/108/EC...................................... EN 61326-1LVD 2006/95/EC......................................... EN 61010-1PELV/SELV.................................................. IEC 364-4-41 and EN 60742ATEX 94/9/EC............................................. EN 50014, EN 50020 andEN 50284Of span = Of the presently selected rangeFrequency generator:Min. period ................................................. 50 µsMax. frequency........................................... 20 kHzDuty cycle................................................... 50%28 29


OrderBlock diagram 5223AType Version Output5223 Standard : A Analogue + NPN / PNPATEX Ex : B Analogue + relay output: 1: 233Supply312122Relay N.O. or NPN/PNP23Dig. out 22413 I +A12 V +AV VGnd.115223 connection to Loop LinkJP 25005223Comm.SupplyFile Product Input Output Communication Language Option 08:30:00PRetop 5331Date: 1994-8-10Serial no: 943201594Tag no: PRelectronicsAnalog input Analog outputInput type: Pt100 DIN/IEC Output type: 4 - 20mAInput range: 0.00 - 50.00 C Sensor error: UpscaleConnection: 3-wireCold junction comp: ----Response time: 1.00 secCOMLoop Link41V15 … 17 VDC43Vreg.V2ErrorVreg. Dig. out V12 x relayf in 1or2 x NPN / PNPDig.out 142 f in 1V1Sup.+Sup.+Sup.+PNP NPN5...17V+51V1S053JP 1f in 250525223A5...17V+S0f in 2Sup.+PNP NPNContactContactTachoRelay N.O. / Dig. gnd.IOutVOutI + VOut0 ... 20mAInput gnd.NamurInput +Front comm.Dig.out 2TachoInput gnd.NamurInput +Supply24V … 230VAC24V … 250VDCRelay N.O. or PNP/NPNDig. out 1Relay N.O. / Dig. gnd.30 31


Block diagram 5223BContact NamurInput +5223B52f in 2Ex Barrier8 V+53f in 2Dig.out 2Contact NamurInput +42 f in 1f in 1Ex Barrier8 V+ 438 VDCVreg.V1V2ErrorDig.out 1Front comm.Displays Programmable displays with a wide selectionof inputs and outputs for display of temperature,volume and weight, etc. Feature linearisation, scaling,and difference measurement functions for programmingvia PReset software.Ex interfaces Interfaces for analogue and digitalsignals as well as HART ® signals between sensors / I/Pconverters / frequency signals and control systems in Exzone 0, 1 & 2 and for some modules in zone 20, 21 & 22.Isolation Galvanic isolators for analogue and digitalsignals as well as HART ® signals. A wide product rangewith both loop-powered and universal isolators featuringlinearisation, inversion, and scaling of output signals.Temperature A wide selection of transmitters for DINform B mounting and DIN rail modules with analogueand digital bus communication ranging from applicationspecificto universal transmitters.50JP 1V10 ... 20mAV1Dig. out2 x relayor2 x NPN / PNPUniversal PC or front programmable modules withuniversal options for input, output and supply. This rangeoffers a number of advanced features such as . processcalibration, linearisation and auto-diagnosis.V1JP 25003331Supply24V … 230VACSupply 24V … 250VDC21Relay N.O. or PNP/NPNDig. out 122Relay N.O. / Dig. gnd.23Relay N.O. or NPN/PNPDig. out 224Relay N.O. / Dig. gnd.13 I +I + VOutVOutIOutA12 V +AV11 Gnd.V32