Diagnosis 7Blocking boiler-fault code 6L branch 14page 7442Check the plug-and-socketconnection betwe<strong>en</strong> the ionization electrodeand cable loom. See page 95.Is the plug-and-socketconnection okay?YesMeasure the resistance in the wires betwe<strong>en</strong>the ionization electrode plug and the UBA 3mounting base. See page 99.NoCorrectly insert the plug into its socket.Is the wiring okay?YesReplace the ionization electrode.See page 97NoReplace the cable loom or the affected partthereof.41page 77page 73 – page 7741Press the "Reset" button.Has a new fault codeoccurred?NoYesHas a new locking boiler faultcode occurred?6LNoRemedy the fault using the structure diagramthat corresponds with the fault code.YesDid yougo through all structure diagramsthru 14?YesNo44page 2944page 838page 31locking boiler fault code 6L Zijtak 1e 5<strong>Logamax</strong> <strong>plus</strong> <strong>GB142</strong>-24/30/45/60 - We reserve the right to make any changes due to technical modifications! 77