8Actions• Test the ionization cable betwe<strong>en</strong> the plug and socket connectionand the UBA 3 installation base to make sure that it has noshort circuit to earth (see fig. 27 and fig. 110 on page 126) andthat it is not brok<strong>en</strong> anywhere (see fig. 28).• Assemble the plug and socket connection of the ionization electrode.• Re-assemble the UBA 3 in reverse order of disassembly.• Fit the casing.• Switch on the power supply of the heating system on the circuitbreaker.• Set the main switch on the BC10 to "1" (On).fig. 27Testing the earth connection circuit of the ionizationelectrode (1)Pin 12855UBA3Pin 81Pin 1KIM81-pole connector16-pole connectorPin 16fig. 28Testing the earth connection circuit of the ionizationelectrode (2)96<strong>Logamax</strong> <strong>plus</strong> <strong>GB142</strong>-24/30/45/60 - We reserve the right to make any changes due to technical modifications!