LED StatusThis section describes the status of operating conditions based on the LED orcombination of LEDs which are lit on the front cover of each Veri-Flame model.Table 8.1 LED Status & Conditions <strong>for</strong> Veri-Flame No Purge ModelsLED(s) LitINTERLOCKS CLOSEDSYSTEM ERRORFLAME FAILUREPossible Causes1) The interlocks are closed (normal operation), power on terminal 7.1) The flame detected is out of sequence, flame signal light is on.2) The sensor is “runaway,” flame signal light is on.3) Inductance is detected on sensor wires, flame signal light is on.4) Voltage wired into terminals 3, 4, or 5.5) Internal relay contacts welded.6) Internal controller failure.7) Main valve closed switch defective, no power to V.1) Pilot flame is not established in selected TFI.2) Main flame is not established in selected TFI.3) Main flame fails within 35 seconds of TFI.4) Flame failed during operation in non-recycle mode.5) Flame failed 35 seconds after TFI and was not established after try in recycle mode.No Purge Model30Eclipse Veri-Flame Instruction Manual 818-6/06