Table 9.1 Veri-Flame Operating Sequence (continued)BURNER START-UP (continued)Is flame signal present?YES NOERROR MESSAGEMAIN FLAME FAILXX:XX:XX LOCKOUTNORMAL MESSAGEMAIN FLAME ONNORMAL MESSAGEMAIN FLAME ONPILOT OFFPilot will shut off 10 secondsafter main flame is energized.IF Interrupted Pilot is selectedIF Intermittent Pilot Is SelectedNORMAL MESSAGEMAIN FLAME ONMODULATION MODELSNORMAL MESSAGEAUTOMATICMODULATIONModulator sent to automatic 20seconds after main valve isenergized.MODULATION MODELSPURGE & NO PURGE MODELSNORMAL MESSAGEBURNER ON XX.XVTIME = XXXX:XX:XXMain flame of burner is proven.Flame signal = XX.XVolts DC;elapsed time is shown in hours:minutes:seconds.PURGE & NO PURGE MODELSIs flame signal present?NOYESIs air switch signal on?NOYESIs recycle selected?YES NOIs recycle selected?YESNOWas the main flame on morethan 35 seconds?NOYESWas the main flame on morethan 35 seconds?NOYESERROR MESSAGEMAIN FLAME FAILRECYCLINGUnit returns to beginningsequence.ERROR MESSAGEMAIN FLAME FAILXX:XX:XX LOCKOUTERROR MESSAGEAIR FAILURERECYCLINGUnit returns to beginningsequence.ERROR MESSAGEAIR FAILUREXX:XX:XX LOCKOUT36Eclipse Veri-Flame Instruction Manual 818-6/06