MAN0551.P65 Issue 06 - 03/042108M05016. CALIBRATIONTo calibrate the sensor, proceed as follows:(1) Connect the Hand-Held SHC-1, press ↵ to switch onthe power, check the Hand-held is in <strong>Optima</strong> + mode,wait five seconds and the display will show:MainDisplay(2) Press and the display will show:MainCalibrate(3) Press ↵ and the display will show:CalibrateDisplay(4) Press and the display will show:CalibrateCal Sensor(5) Press ↵ and the display will show:Inhibiting 4 - 20Please WaitThis sets the analogue output to the inhibit level(default 2mA) for the duration of the calibrationsequence.(6) Remove weather protection and dust barrier. Check thatthe optics are clean and dry. Clean / dry optics ifnecessary. Refit the dust barrier and weatherprotection.69