Connection to a PC by the Host Link Section 2-4[Setting the rear switches]S I/O port selection (selector switch)Set this to “RS-232C”.I/O portRS-422ARS-232CSynchronizationInternalExternalTerminationresistanceOFFONCTS0VExternalS Unit # (DIP SW1)Set SW1-1 to SW1-5 to “OFF” (“0”).S Synchronization (selector switch)Set this to “Internal”.S Baud rate (DIP SW2-1 to SW2-4)Set these switches to “1010” to select 9600 bps.Set these switches to “0010” to select 19200 bps.S 1-to-1/1-to-N selection (DIP SW2-6)Set SW2-6 to “0” (1-to-N).S Instruction level (DIP SW2-7, SW2-8)Set these switches to “1”.(Levels 1, 2, and 3 are enabled.)S CTS selection (selector switch)Set this always to “0V” (ON).36ηττπ://νιχοντρολσ.χοm