Procedure for <strong>Insulation</strong> <strong>Coord<strong>in</strong>ation</strong> <strong>in</strong> Four Steps<br />

Fachgebiet<br />

Hochspannungstechnik<br />

Determ<strong>in</strong>ation of the coord<strong>in</strong>ation withst<strong>and</strong> voltages U cw<br />

• The coord<strong>in</strong>ation withst<strong>and</strong> voltages are the lowest values of withst<strong>and</strong> voltages of<br />

each overvoltage class, for which the expected low failure rate of the equipment is not<br />

exceeded over its full lifetime.<br />

• Derived from the representative overvoltages U rp by the coord<strong>in</strong>ation factor K c.<br />

<strong>Overvoltage</strong> <strong>Protection</strong> <strong>and</strong> <strong>Insulation</strong> <strong>Coord<strong>in</strong>ation</strong> / Chapter 1 - 32 -<br />

Typical for<br />

Germany:<br />

0.1% per year<br />

� 1 failure <strong>in</strong><br />

1000 years<br />