Procedure for <strong>Insulation</strong> <strong>Coord<strong>in</strong>ation</strong> <strong>in</strong> Four Steps<br />
Fachgebiet<br />
Hochspannungstechnik<br />
Determ<strong>in</strong>ation of the required withst<strong>and</strong> voltages U rw<br />
• The required withst<strong>and</strong> voltages are determ<strong>in</strong>ed by convert<strong>in</strong>g the coord<strong>in</strong>ation withst<strong>and</strong><br />
voltages to appropriate st<strong>and</strong>ard test conditions.<br />
• Usually different from the coord<strong>in</strong>ation withst<strong>and</strong> voltages.<br />
• Derived from the coord<strong>in</strong>ation withst<strong>and</strong> voltages U cw by the safety factor K s <strong>and</strong>/or the<br />
altitude correction factor K a.<br />
<strong>Overvoltage</strong> <strong>Protection</strong> <strong>and</strong> <strong>Insulation</strong> <strong>Coord<strong>in</strong>ation</strong> / Chapter 1 - 36 -<br />
[IEC 60071-1]