Effects of overlapping dimensionThe axial overlap between the inlet nozzle and impeller cover plateinfluences the air performance and efficiency of a centrifugal fan.Curve[Pa]1[%]X123x / D = 0.6 %x / D = 0 %x / D = -0.8 %3312200[m³/h]Effects of installation spaceWhen mounting our product in a rectangular box, air performancemight be reduced.0,960,971,00DCurveB0,990,98d hBH0,5xDDH= Hydraulic diameterFormula: d h = 2 x B x H / (B + H)= Width of box= Height of boxD = Outer diameter of the fanDCorrection factor for air flow0,92 0,93 0,94 0,951,4 1,6 1,8 2,0 2,2 2,4 2,6 2,8Hydraulic diameter d h/D402