M) EC motors (size 150, three-phase mains-powered)KL3 KL2 KL1RS ARS BRS ARS BGND0-10 VPWM4-20 mA+20 V+10 V0-10 VPWMGNDOUTNOCOMNCL1L2L3PEConnector Connection Assignment / function Connector Connection Assignment / functionPEPE Protective earth KL3 OUTKL1 L3 Mains; L3KL2L2L1NCCOMNOMains; L2Mains; L1Alarm relay, break for failureAlarm relay, COMMON (2A, 250 VAC, AC1)Alarm relay, make for failureGND GND0-10 V / PWM Control / Actual value input (Impedance 100 k)+10 V+20 V4-20 mA Control / Actual value input0-10 V / PWM Control / Actual value inputGNDRSBRSARSBRSAMaster output 0-10 V max. 3 mASupply for external potentiometer,10 VDC (+10 %) @ 10 mASupply for external sensor,20 VDC (±20 %) @ 50 mAGNDRS485 interface for ebmBUS; RS BRS485 interface for ebmBUS; RS ARS485 interface for ebmBUS; RS BRS485 interface for ebmBUS; RS A428