Introducing the Douglas<br />
<strong>WSP</strong>-<strong>2718</strong> <strong>Digital</strong><br />
<strong>Satellite</strong> <strong>Relay</strong> <strong>Panels</strong><br />
An ideal lighting control panel for school classrooms,<br />
lecture theaters and office tenant spaces.<br />
• Eight 20 Amp lighting relays for 120V, 277V or<br />
347V circuits.<br />
• Reduced contractor branch circuit wiring.<br />
• Designed to accept inputs from a variety of sources<br />
including switches, photo sensors and occupancy<br />
detectors with lockout logic provided.<br />
• Optional emergency transfer devices (UL-924 type)<br />
available.<br />
• <strong>Satellite</strong> <strong>Panels</strong> are programmed via any PC that<br />
has Internet browser software installed.<br />
Page 1
W-2000<br />
Lighting Control Networks<br />
with <strong>Satellite</strong> <strong>Relay</strong> <strong>Panels</strong><br />
Master Lighting<br />
Control <strong>Relay</strong><br />
Cabinet c/w<br />
Network Manager<br />
Lighting<br />
Distribution<br />
Panel<br />
to next <strong>Satellite</strong><br />
<strong>Relay</strong> Panel<br />
Classroom A<br />
Classroom B<br />
Remote<br />
<strong>Satellite</strong><br />
<strong>Relay</strong><br />
<strong>Panels</strong><br />
Classroom C<br />
Classroom D<br />
data signal<br />
<strong>WSP</strong>-<strong>2718</strong> <strong>Satellite</strong> Panel Features<br />
• Eight 20A 120/277/347VAC<br />
latching relays that are rated<br />
for lighting loads.<br />
• Each relay has a built-in<br />
manual ON/OFF lever for<br />
easy control at the panel.<br />
• Ten switch inputs. Each can<br />
be set to control any relay<br />
or group of relays in the<br />
panel.<br />
• Two digital photo sensor<br />
inputs for Douglas sensors.<br />
• Two 24VDC inputs and a<br />
24VDC power supply to<br />
accommodate any type of<br />
24VDC occupancy detector.<br />
• Each panel is equipped with a<br />
buzzer that can be pinged to<br />
establish location.<br />
• Switch inputs can also be<br />
programmed to control relays<br />
in other panels.<br />
• A photo sensor can be set so that<br />
each lighting group can switch<br />
ON/OFF at unique light levels.<br />
• Photo sensor control can be<br />
interlocked so that lights stay<br />
OFF regardless of any other<br />
control if the natural light level<br />
is sufficient.<br />
• Occupancy detector controls<br />
can be disabled for “Quiet<br />
Time” applications common<br />
in schools.<br />
• The <strong>Satellite</strong> Panel is part of<br />
the W-2000 System. <strong>Panels</strong><br />
are programmed and set via<br />
any PC that has an Internet<br />
browser installed.<br />
Constant Light Controller<br />
Photo<br />
Cell<br />
Photo<br />
Cell<br />
Photo<br />
Cell<br />
Photo<br />
Cell<br />
Photo<br />
Cell<br />
Photo<br />
Cell<br />
Occ.<br />
OFF<br />
only<br />
Sw.<br />
Early Morning: 2 lamps ON<br />
Morning: 1 lamp ON<br />
Mid Day: No lamps ON<br />
Afternoon: 1 lamp ON<br />
Evening: 2 lamps ON<br />
Night: 3 lamps ON<br />
Unoccupied: No lamps ON<br />
Page 2<br />
www.DouglasLightingControls.com
<strong>WSP</strong>-<strong>2718</strong> <strong>Satellite</strong> Panel Network<br />
W-2000 Network<br />
The panels are connected to<br />
each other with a 2-conductor<br />
data line. This forms the<br />
backbone of the W-2000<br />
system by providing an<br />
address point for each relay.<br />
The W-2000 family of<br />
®<br />
products uses the LonWorks<br />
technology platform to provide<br />
an open standard, nonproprietary<br />
option for your<br />
lighting control system.<br />
Other building automation<br />
systems that support lighting<br />
controls using the LonMark<br />
standards can integrate the<br />
Douglas W-2000 panel<br />
network as part of their<br />
system.<br />
Lighting<br />
Distribution<br />
Panel<br />
Full-Sized Douglas <strong>Panels</strong><br />
• Capacity from 6 to 72 loads.<br />
• Install by breaker panels.<br />
LCP1 LCP2 LCP3<br />
<strong>Satellite</strong> <strong>Panels</strong><br />
• Capacity for eight relays.<br />
• Install each near loads being controlled.<br />
Optional Data Line Switches<br />
• System-wide programmable control.<br />
Local<br />
Hardwired<br />
Switches<br />
and<br />
Devices<br />
Configured by<br />
a WNP-2150<br />
Network<br />
Manager<br />
data signal<br />
Telephone<br />
Connection<br />
Ethernet<br />
Connection<br />
Internet Browser Access<br />
for Lighting Control<br />
System View/Edit<br />
Functions<br />
Internet Access<br />
WNP-2150 Network Manager settings are<br />
viewed and edited with a standard Internet<br />
browser. No proprietary software required.<br />
User connection to the WNP-2150 can be<br />
direct with an ethernet connection or<br />
remote from a computer that is connected<br />
to the Internet. Telephone access is<br />
available for remote programming.<br />
www.DouglasLightingControls.com<br />
Page 3
<strong>WSP</strong>-<strong>2718</strong> <strong>Satellite</strong> Panel<br />
Lighting Control Products<br />
WNP-2150 Network Manager<br />
The WNP-2150 Network Manager connects to the Lighting Control panels via<br />
the LonWorks data signal.<br />
Connection to the WNP-2150 from a PC or LAN is via an ethernet connection.<br />
The WNP-2150 can also be accessed via the optional telephone modem.<br />
Network Lighting Control Scheduler<br />
The WNP-2150 provides the link for control and programming by a PC.<br />
Scheduler features include view & edit relay groups in a PC via any standard<br />
Internet browser. Access is provided by a direct connection or via the Internet. Full<br />
scheduling capability is available for weekly, holiday and special event formats.<br />
Schedules support Flick Warn, Time Out, Delay OFF, Cleaning Mode and Disable<br />
features. The system logs the last 255 events and permits diagnostics.<br />
Douglas Low Voltage Switches<br />
Douglas 2-Wire Switches<br />
-LED or non-LED versions.<br />
-Keyed switches.<br />
-Push button switches with label.<br />
Douglas <strong>Digital</strong> Switches<br />
-LED indication.<br />
-Push button style with label.<br />
-Three switches per gang.<br />
Photo Sensors<br />
WPS-5533/WPS-5527<br />
Photo sensors connect directly to the<br />
<strong>Satellite</strong> Panel and vary output light<br />
levels in response to changing<br />
ambient light during the day.<br />
WPS-5941/WPS-5951<br />
Photo sensors connect into the W-2000<br />
network, for system-wide switching<br />
utilizing photocell control.<br />
Occupancy Sensors<br />
The Douglas WRM-5104 Ceiling-Mounted PIR Occupancy Sensor monitors a<br />
360 O detection zone within a room with eight- to twelve-foot ceilings.<br />
The sensor’s fresnel lens rotates and swivels to allow fine tuning of PIR detection<br />
zones. The control switch under the front cover allows for ON/OFF or OFF-only mode.<br />
Dimming Ballast Controls<br />
The Douglas WPC-5700 Indoor Ambient Light Sensor dims up to 50 Industry-Standard<br />
0-10V dimming ballasts in response to measured ambient light levels. The sensor can be<br />
configured as a stand-alone device or as part of a time-controlled network.<br />
The Douglas WPN-5721 Manual Dimming Ballast Controller is available as a convenient<br />
local room override.<br />
www.DouglasLightingControls.com<br />
Page 4