BACnet Node for Douglas Scanner WBI-2671 Technical Data nonvibrating
WBI-2671 - cut sheet - 1 of 2 - Douglas Lighting Control
WBI-2671 - cut sheet - 1 of 2 - Douglas Lighting Control
- No tags were found...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
OPTIONS PROGRAM<br />
MODE<br />
NORMAL<br />
MODE<br />
SELECT<br />
MASTER<br />
SWITCH<br />
ON<br />
OVERRIDE<br />
OFF<br />
OVERRIDE<br />
<strong>BACnet</strong> ® <strong>Node</strong> <strong>for</strong> <strong>Douglas</strong> <strong>Scanner</strong><br />
<strong>WBI</strong>-<strong>2671</strong><br />
<strong>Technical</strong> <strong>Data</strong><br />
PART No.<br />
<strong>WBI</strong>-<strong>2671</strong><br />
DESCRIPTION<br />
The <strong>WBI</strong>-<strong>2671</strong> is a <strong>BACnet</strong> MSTP device<br />
that allows <strong>Douglas</strong> WRS-2224 Relay<br />
<strong>Scanner</strong>s to send and receive <strong>BACnet</strong><br />
commands to or from a BAS.<br />
The <strong>WBI</strong>-<strong>2671</strong> <strong>Node</strong> uses RS-485<br />
networking technology that uses native<br />
<strong>BACnet</strong> MSTP protocol.<br />
Building Management Systems can<br />
configure and program from their database<br />
all of the functions inherent in the <strong>WBI</strong>-<strong>2671</strong><br />
and the WRS-2224.<br />
The <strong>WBI</strong>-<strong>2671</strong> con<strong>for</strong>ms to the open<br />
native <strong>BACnet</strong> variables <strong>for</strong> lighting.<br />
The <strong>WBI</strong>-<strong>2671</strong> allows programming,<br />
control and monitoring of 5 groups.<br />
The <strong>WBI</strong>-<strong>2671</strong> allows control and<br />
monitoring of 24 relays individually.<br />
The <strong>WBI</strong>-<strong>2671</strong> allows control and<br />
monitoring of 5 switch inputs.<br />
The <strong>WBI</strong>-<strong>2671</strong> allows programming, either<br />
from the WRS-2224 or the Network, of a 2-<br />
hour Time Out or a 5-minute Flick Warn.<br />
SPECIFICATION<br />
Power<br />
The <strong>WBI</strong>-<strong>2671</strong> <strong>Node</strong> obtains power from<br />
the host WRS-2224 Relay <strong>Scanner</strong>.<br />
CAUTION: Always disconnect 24VAC<br />
from the WRS-2224 <strong>Scanner</strong> prior to<br />
plugging/unplugging the <strong>WBI</strong>-<strong>2671</strong> unit.<br />
Wire Type & Method<br />
<strong>WBI</strong>-<strong>2671</strong> <strong>Node</strong>s are connected together<br />
using a shielded single twisted pair cable<br />
in a serial loop.<br />
Con<strong>for</strong>m to wiring specifications issued by<br />
the host Building Management System.<br />
Networking Technology Specification<br />
Network signal:<br />
RS-485 Transceiver.<br />
MSTP Protocol.<br />
100K Ohm bias (120 Ohm termination<br />
recommended).<br />
<strong>BACnet</strong> Spec 9.2.2 compliant.<br />
.Up to 32 devices per segment.<br />
Baud Rates (selectable)<br />
Relay Outputs<br />
24 output terminals<br />
(12 per side) are<br />
provided <strong>for</strong> relay control.<br />
<strong>Douglas</strong> 2-wire switches<br />
can be connected in<br />
parallel to permit<br />
individual control of a<br />
relay by a switch.<br />
Individual Output<br />
Buttons<br />
In operating mode, use<br />
buttons to switch the<br />
connected relay ON or OFF.<br />
In programming mode, use<br />
buttons to enter or remove<br />
the relay from the switch<br />
input being programmed.<br />
9,600 Baud.<br />
19,200 Baud.<br />
38,400 Baud.<br />
76,800 Baud.<br />
Environment<br />
Environment: Indoors, stationary, <strong>nonvibrating</strong>,<br />
non-corrosive atmosphere and<br />
non-condensing humidity.<br />
Ambient temp: -0° to +120°F (-15° to +50°C).<br />
Select Buttons<br />
& LED's <strong>for</strong>:<br />
1) Operating mode.<br />
2) Program mode.<br />
3) Flick Warn, Time Out<br />
and Flick Warn with<br />
Time Out options.<br />
Directions<br />
Programming<br />
directions are printed<br />
on keypad <strong>for</strong> handy<br />
user reference.<br />
Baud Rate Select<br />
Use the binary DIP switch<br />
to set the Baud Rate:<br />
-9,600 (both up)<br />
-19,200 (#1 up)<br />
-38,400 (#2 up)<br />
-76,800 (both down)<br />
CAUTION:<br />
<strong>WBI</strong>-<strong>2671</strong><br />
Disconnect 24V of WRS-2224<br />
BEFORE plug/unpluging this unit<br />
<strong>BACnet</strong> <strong>Node</strong> <strong>for</strong> WRS-2224 <strong>Scanner</strong><br />
Interface type: MSTP over RS-485<br />
- This node does not have a built-in end of the line termination resistor.<br />
Installer's responsibility to correctly terminate the RS-485 data bus.<br />
- Transmission Baud Rate is selectable, select appropriate baud rate<br />
<strong>for</strong> the system this node is installed to.<br />
- For in<strong>for</strong>mation regarding <strong>BACnet</strong> object types supported, refer to<br />
product cutsheet available at <strong>Douglas</strong> web site.<br />
V#<br />
Status LED<br />
Start-up: 2 blinks then solid <strong>for</strong> 2sec<br />
Run time: blinking = OK, solid = problem<br />
Baud Rate Setting<br />
9,600<br />
19,200<br />
38,400<br />
www.<strong>Douglas</strong>LightingControls.com<br />
76,800<br />
1 2<br />
lighting controls<br />
Transmit<br />
ON<br />
OFF<br />
32<br />
64<br />
128<br />
RS-485 Address Select<br />
Sum of switches set ON<br />
equals the unit's address<br />
RS-485-VCC Connection<br />
Receive<br />
VCC<br />
485 -<br />
1<br />
24816<br />
485 +<br />
GND<br />
Override Buttons<br />
Use ON and OFF<br />
override buttons to<br />
switch relay groups.<br />
Relay Group Select<br />
Use the Input Select button<br />
to choose the relay group<br />
input 1, 2, 3, 4 or 5.<br />
The selected input will have<br />
its indicator LED ON.<br />
Inputs are momentary or<br />
maintained <strong>Douglas</strong> switches<br />
MAC Address Select<br />
Use the binary DIP switch to<br />
set the MAC Address (0-255).<br />
<strong>Data</strong> Signal<br />
RS-485 Transceiver<br />
DIMENSIONS & MOUNTING<br />
Be sure to disconnect 24VAC from<br />
relay scanner be<strong>for</strong>e plugging or<br />
unplugging network node to scanner.<br />
Mount node to 35mm DIN rail<br />
installed in <strong>Douglas</strong> relay panel.<br />
Plan View<br />
6.5"<br />
(165)<br />
2.5"<br />
(64)<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9<br />
10<br />
11<br />
12<br />
1<br />
3<br />
5<br />
7<br />
9<br />
11<br />
2<br />
4<br />
6<br />
8<br />
10<br />
12<br />
14<br />
16<br />
18<br />
20<br />
22<br />
24<br />
WRS-2224<br />
Relay<br />
<strong>Scanner</strong><br />
<strong>WBI</strong>-<strong>2671</strong><br />
<strong>Node</strong><br />
13<br />
15<br />
17<br />
19<br />
21<br />
23<br />
Sw<br />
Inputs<br />
4.0"<br />
(103)<br />
13<br />
14<br />
15<br />
16<br />
17<br />
18<br />
19<br />
20<br />
21<br />
22<br />
23<br />
24<br />
W B<br />
1<br />
2<br />
3<br />
B 45<br />
B<br />
Side<br />
View<br />
1.75"<br />
(45)<br />
Interfaces 4.3<br />
C-4-3,4,5,6 -System Integration, <strong>BACnet</strong><br />
www.<strong>Douglas</strong>LightingControls.com
<strong>BACnet</strong> ® <strong>Node</strong> <strong>for</strong> <strong>Douglas</strong> <strong>Scanner</strong><br />
<strong>WBI</strong>-<strong>2671</strong><br />
<strong>Technical</strong> <strong>Data</strong><br />
EXTERNALLY CONFIGURED NETWORKS<br />
Integrated Systems<br />
<strong>Douglas</strong> Relay Panels can be incorporated into Building<br />
Management Control Systems that use <strong>BACnet</strong> technology.<br />
It is assumed that the BMS supports standard <strong>BACnet</strong> objects<br />
that can be used <strong>for</strong> lighting control.<br />
The <strong>WBI</strong>-<strong>2671</strong> <strong>Node</strong> plugs into the WRS-2224 Relay <strong>Scanner</strong><br />
and is connected to the <strong>BACnet</strong> network.<br />
Individual relay and groups status indicators are available on the<br />
keypad on the attached relay scanner.<br />
Individual relay and group momentary overrides are available on<br />
the keypad on the attached relay scanner.<br />
MAC Address and Configuration<br />
The MAC Address (0-255 address range) <strong>for</strong> each <strong>WBI</strong>-<strong>2671</strong> is set<br />
using the binary DIP switch on the <strong>WBI</strong>-<strong>2671</strong> unit.<br />
The Device ID <strong>for</strong> each <strong>WBI</strong>-<strong>2671</strong> is set using a variable accessible<br />
via the <strong>BACnet</strong> MSTP port.<br />
<strong>WBI</strong>-<strong>2671</strong> FUNCTIONS & FEATURES<br />
Activates a group (one command per group).<br />
Reads the group status (one command per group).<br />
Activates relays (one command per relay).<br />
Reads 'enhanced' group status (one command per<br />
relay: 0 = Absent, 1 = ON, 2 = OFF, 3 = Defective).<br />
Activates a group switch (changes the state, one<br />
command per switch).<br />
Reads a group switch (monitors the state, one<br />
command per switch).<br />
Reads the module status (version numbers and address).<br />
Provides remote programming of the five scanner<br />
resident groups (including Flick Warn, Time Out and<br />
Flick Warn with Timeout options).<br />
Querys programming of the five scanner resident<br />
groups (including Flick Warn, Time Out and Flick Warn<br />
with Time Out options).<br />
Provides local programming of the five scanner resident<br />
groups (by the keypad on the attached scanner).<br />
CONNECTIONS<br />
Relays<br />
<strong>Data</strong> Signal<br />
RS-485 Transceiver<br />
<strong>Node</strong>/<strong>Scanner</strong> Combo<br />
OPTIONS<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9<br />
10<br />
11<br />
12<br />
PROGRAM<br />
MODE<br />
1<br />
3<br />
5<br />
7<br />
9<br />
11<br />
2<br />
4<br />
6<br />
8<br />
10<br />
12<br />
NORMAL<br />
MODE<br />
WRS-2224<br />
Relay<br />
<strong>Scanner</strong><br />
<strong>WBI</strong>-<strong>2671</strong><br />
<strong>Node</strong><br />
14<br />
16<br />
18<br />
20<br />
22<br />
24<br />
13<br />
15<br />
17<br />
19<br />
21<br />
23<br />
INPUT<br />
SELECT<br />
Master<br />
Inputs<br />
13<br />
14<br />
15<br />
16<br />
17<br />
18<br />
19<br />
20<br />
21<br />
22<br />
23<br />
24<br />
W B<br />
1 23B45B<br />
ON<br />
OVERRIDE<br />
OFF<br />
OVERRIDE<br />
Trans<strong>for</strong>mer<br />
W 24VAC<br />
B<br />
Local<br />
Switches<br />
Connect directly<br />
to relays<br />
Relays<br />
Group<br />
Switch<br />
Inputs<br />
Standard<br />
<strong>Douglas</strong><br />
Switches<br />
Motion<br />
Control<br />
OBJECT TYPES<br />
This in<strong>for</strong>mation is provided <strong>for</strong> System Integrators who<br />
areconfiguring this device into an HVAC system.<br />
Object Type<br />
Multi-state input to check relay status<br />
(0 = absent, 1 = ON, 2 = OFF, 3 = defective)<br />
Multi-state input to check device status<br />
Multi-state input to check group programs<br />
Multi-state input to check input configurations<br />
Multi-state input to check to check Flick and<br />
Time Out status<br />
Binary input to monitor group status (ON or OFF)<br />
Binary input to monitor switch status (ON or OFF)<br />
Binary input to monitor Flick status<br />
(Flick ON or OFF)<br />
Multi-state output <strong>for</strong> <strong>for</strong> programming groups,<br />
switches and Flick<br />
Binary output (read/write) <strong>for</strong> individual relay<br />
control (ON or OFF)<br />
Binary output (read/write) <strong>for</strong> group control<br />
(ON or OFF)<br />
Binary output (read/write) <strong>for</strong> group status<br />
control (ON or OFF)<br />
Binary output (read/write) <strong>for</strong> Flick control<br />
(ON or OFF)<br />
Objects<br />
MI0 - MI23<br />
MI24<br />
MI25 - MI29<br />
MI30 - MI34<br />
MI35 - MI39<br />
BI0 - BI4<br />
BI5 - BI9<br />
BI10 - BI14<br />
MV0 - MV4<br />
BV0 - BV23<br />
BV24 - BV28<br />
BV29 - BV33<br />
BV34 - BV38<br />
Quantity<br />
24<br />
1<br />
5<br />
5<br />
5<br />
5<br />
5<br />
5<br />
5<br />
24<br />
5<br />
5<br />
5<br />
Interfaces 4.4<br />
C-4-3,4,5,6 -System Integration, <strong>BACnet</strong><br />
www.<strong>Douglas</strong>LightingControls.com