Fault finding cont’d<br />

Fan will<br />

not run<br />

heater<br />

goes off<br />

on limit<br />

Yes<br />

Bad<br />

electrical<br />

connection<br />

No<br />

Yes<br />

Check<br />

wiring<br />

connection<br />

Fan control<br />

settings<br />

incorrect<br />

Yes<br />

Reset fan<br />

control<br />

settings<br />

No<br />

Fan runs in<br />

manual<br />

mode<br />

Yes<br />

Faulty fan<br />

control<br />

Yes<br />

Change fan<br />

control<br />

No<br />

Faulty fan<br />

motor or<br />

capacitor<br />

Yes<br />

Change fan<br />

motor or<br />

capacitor<br />

Check air<br />

inlet /<br />

discharge not<br />

restricted<br />

Yes<br />

Remove<br />

obstruction<br />

clean filters<br />

Yes<br />

Burner<br />

starts but<br />

heater<br />

goes to<br />

overheat<br />

Yes<br />

Insufficient<br />

airflow over<br />

heat<br />

exchanger<br />

Yes<br />

Fan belts<br />

slipping<br />

/impellor<br />

loose on<br />

shaft<br />

No<br />

Adjust /replace<br />

belts tighten<br />

impellor<br />

or<br />

Faulty fan /<br />

limit stat<br />

Yes<br />

Change fan /<br />

limit stat<br />

or<br />

High return<br />

air<br />

temperature<br />

Yes<br />

Check for warm air<br />

short circuit wiring to<br />

air inlet<br />