9 280<br />

DESIGO PX<br />

<strong>Extension</strong> <strong>module</strong><br />

<strong>for</strong> <strong>KNX</strong> / <strong>EIB</strong><br />

<strong>for</strong> <strong>KNX</strong> / <strong>EIB</strong> integration<br />

<strong>PXA30</strong>-<strong>K11</strong><br />

• Integration of <strong>KNX</strong> / <strong>EIB</strong> subsystems at the automation level of the DESIGO<br />

building automation and control system<br />

• Plugs into the modular automation station type PXC...-U<br />

Functions<br />

• Integration of max. 45 RXB… room controllers (S-mode or polling)<br />

• Integration of max. 2000 data points from <strong>KNX</strong> / <strong>EIB</strong> 3rd party systems (S-mode)<br />

Types<br />

<strong>PXA30</strong>-<strong>K11</strong><br />

<strong>Extension</strong> <strong>module</strong><br />

Compatibility<br />

The <strong>module</strong> is plugged into a PXC64-U or PXC128-U automation station.<br />

CM1N9280en_02<br />

18 May 2009 Building Technologies


Ordering<br />

When ordering, please specify the quantity, product name and type code.<br />

Example:<br />

30 <strong>Extension</strong> <strong>module</strong>s <strong>PXA30</strong>-<strong>K11</strong><br />

Design<br />

• Two-part snap-together housing (plastic)<br />

• Cover <strong>for</strong> contact protection<br />

• PCB with electronic components<br />

• Two-pole <strong>EIB</strong>/<strong>KNX</strong> connection terminals<br />

• RJ45 service socket<br />

• Service pin<br />

9280Z01<br />

Mounting<br />

The extension <strong>module</strong> is plugged into the PXC..-U modular automation station.<br />

It is important to follow the instructions supplied with the device, in particular:<br />

• Avoid touching the connector pins (ESD precautions)<br />

• Push the <strong>module</strong> firmly into position (1.5 mm) and check that it is securely in place<br />

so that the fine contact pins interlock properly.<br />

2<br />

1<br />

3<br />

3<br />

1 Plug-in unit<br />

2 Device base<br />

3 <strong>Extension</strong> <strong>module</strong><br />

9280Z02<br />

2/4<br />

<strong>Siemens</strong> <strong>PXA30</strong>-<strong>K11</strong> – <strong>Extension</strong> <strong>module</strong> <strong>for</strong> <strong>KNX</strong> / <strong>EIB</strong> CM1N9280en_02<br />

Building Technologies 18 May 2009


Commissioning<br />

For integration operation the corresponding firmware must be loaded into the PXC...-U<br />

automation station.<br />

Disposal<br />

The device includes electrical and electronic components and must not be disposed of<br />

as domestic waste.<br />

Current local legislation must be observed.<br />

Technical data<br />

Elements of the user interface Service pin<br />

Programming mode<br />

<strong>KNX</strong> / <strong>EIB</strong> interface<br />

Stranded or solid conductors,<br />

2 x 1.0 mm 2<br />

<strong>KNX</strong> / <strong>EIB</strong> bus Interface type <strong>KNX</strong> / <strong>EIB</strong> (electrically isolated)<br />

Transceiver<br />

TP-UART<br />

Bus current<br />

5 mA<br />

Baud rate<br />

9.6 kbit/s<br />

Bus topology, bus termination<br />

Refer to <strong>KNX</strong> / <strong>EIB</strong> manual<br />

Service interface<br />

RJ45<br />

Housing<br />

Protection standard to EN 60529 IP 30<br />

protection standard<br />

Protection class Insulation protection class II<br />

Ambient conditions Normal operation Class 3K5 to IEC 721<br />

Temperature 0 ... 50 °C<br />

Humidity<br />

< 85 % rh<br />

Transport Class 2K3 to IEC 721<br />

Temperature – 25 ... 65 °C<br />

Humidity<br />

< 95 % rh<br />

Industry standards<br />

Product safety<br />

Automatic electronic controls <strong>for</strong><br />

household and similar use EN 60730-1<br />

Special requirements <strong>for</strong> energy controllers EN 60730-2-11<br />

Electromagnetic compatibility<br />

Interference immunity<br />

EN 61000-6-2 (Industry)<br />

Emitted interference<br />

EN 61000-6-3 (Residential)<br />

Meets the requirements <strong>for</strong> CE marking:<br />

EMC Directive<br />

2004/108/EG<br />

Dimensions<br />

See “Dimensions”<br />

Weight Excluding packaging 75 g<br />

With packaging<br />

95 g<br />

<strong>Siemens</strong> <strong>PXA30</strong>-<strong>K11</strong> – <strong>Extension</strong> <strong>module</strong> <strong>for</strong> <strong>KNX</strong> / <strong>EIB</strong> CM1N9280en_02<br />

Building Technologies 18 May 2009<br />

3/4


Connections<br />

Standard RJ45 socket<br />

<strong>for</strong> service<br />

87654321<br />

9280Z03<br />

1 <strong>KNX</strong> data cable (CE+)<br />

2 <strong>KNX</strong> data cable (CE–)<br />

3 Not used<br />

4 Not used<br />

5 Not used<br />

6 Not used<br />

7 Not used<br />

8 Not used<br />

<strong>KNX</strong> / <strong>EIB</strong>-interface<br />

9280Z05<br />

+ <strong>KNX</strong> data cable (CE+)<br />

– <strong>KNX</strong> data cable (CE–)<br />

Dimensions<br />

Dimensions in mm<br />

9280M01<br />

111<br />

62 33<br />

28<br />

4/4<br />

© 2004 – 2009 <strong>Siemens</strong> Switzerland Ltd. Subject to alteration<br />

<strong>Siemens</strong> <strong>PXA30</strong>-<strong>K11</strong> – <strong>Extension</strong> <strong>module</strong> <strong>for</strong> <strong>KNX</strong> / <strong>EIB</strong> CM1N9280en_02<br />

Building Technologies 18 May 2009

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!