Ventilation Sizing Summary for RECUPERADOR RC01<br />

Project Name: B03309-AJUNTAMENT PALAFRUGELL V1 11/13/2009<br />

Prepared by: GRUPO JG 12:08<br />

Hourly Analysis Program v.4,4 Page 1 of 1<br />

1. Summary<br />

Ventilation Sizing Method Sum of Space OA Airflows<br />

Design Ventilation Airflow Rate 662 L/s<br />

2. Space Ventilation Analysis Table<br />

Floor Maximum Required Required Required Required Uncorrected<br />

Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air<br />

Zone Name / Space Name Mult. (m²) Occupants (L/s) (L/s/person) (L/(s-m²)) (L/s) (% of supply) (L/s)<br />

Zone 1<br />

SALA POLIVALENT PB 1 105,3 24,0 300,0 12,50 0,00 0,0 0,0 300,0<br />

SALA RECAPTACIÓ P1 1 97,1 12,0 150,0 12,50 0,00 0,0 0,0 150,0<br />

JUNTA GOVERN P2 1 50,6 14,0 175,0 12,50 0,00 0,0 0,0 175,0<br />

DESPATX P2 1 23,8 3,0 37,5 12,50 0,00 0,0 0,0 37,5<br />

Totals (incl. Space Multipliers) 662,5 662,5<br />