Air System Design Load Summary for DESPATX P2<br />

Project Name: B03309-AJUNTAMENT PALAFRUGELL V1 11/13/2009<br />

Prepared by: GRUPO JG 12:11<br />

DESIGN COOLING<br />

DESIGN HEATING<br />

COOLING DATA AT Aug 1600<br />

HEATING DATA AT DES HTG<br />

COOLING OA DB / WB 32,5 °C / 26,0 °C HEATING OA DB / WB -1,8 °C / -4,2 °C<br />

Sensible Latent Sensible Latent<br />

ZONE LOADS Details (W) (W) Details (W) (W)<br />

Window & Skylight Solar Loads 13 m² 405 - 13 m² - -<br />

Wall Transmission 21 m² 318 - 21 m² 365 -<br />

Roof Transmission 24 m² 125 - 24 m² 232 -<br />

Window Transmission 13 m² 327 - 13 m² 982 -<br />

Skylight Transmission 0 m² 0 - 0 m² 0 -<br />

Door Loads 0 m² 0 - 0 m² 0 -<br />

Floor Transmission 0 m² 0 - 0 m² 0 -<br />

Partitions 14 m² 53 - 14 m² 162 -<br />

Ceiling 0 m² 0 - 0 m² 0 -<br />

Overhead Lighting 347 W 264 - 0 0 -<br />

Task Lighting 0 W 0 - 0 0 -<br />

Electric Equipment 643 W 574 - 0 0 -<br />

People 3 136 162 0 0 0<br />

Infiltration - 0 0 - 0 0<br />

Miscellaneous - 0 0 - 0 0<br />

Safety Factor 10% / 10% 220 16 20% 348 0<br />

>> Total Zone Loads - 2421 178 - 2089 0<br />

Zone Conditioning - 2496 178 - 2072 0<br />

Plenum Wall Load 0% 0 - 0 0 -<br />

Plenum Roof Load 0% 0 - 0 0 -<br />

Plenum Lighting Load 0% 0 - 0 0 -<br />

Return Fan Load 218 L/s 0 - 218 L/s 0 -<br />

Ventilation Load 38 L/s 389 1002 38 L/s 1038 0<br />

Supply Fan Load 218 L/s 101 - 218 L/s -101 -<br />

Space Fan Coil Fans - 0 - - 0 -<br />

Duct Heat Gain / Loss 0% 0 - 0% 0 -<br />

>> Total System Loads - 2986 1180 - 3009 0<br />

Central Cooling Coil - 2986 1180 - 0 0<br />

Central Heating Coil - 0 - - 3009 -<br />

>> Total Conditioning - 2986 1180 - 3009 0<br />

Key: Positive values are clg loads Positive values are htg loads<br />

Negative values are htg loads<br />

Negative values are clg loads<br />

41<br />

Hourly Analysis Program v.4,4 Page 1 of 1