Air System Design Load Summary for SALA RECAPTACIO P1<br />

Project Name: B03309-AJUNTAMENT PALAFRUGELL V1 11/13/2009<br />

Prepared by: GRUPO JG 12:13<br />

DESIGN COOLING<br />

DESIGN HEATING<br />

COOLING DATA AT Sep 1600<br />

HEATING DATA AT DES HTG<br />

COOLING OA DB / WB 31,4 °C / 25,5 °C HEATING OA DB / WB -1,8 °C / -4,2 °C<br />

Sensible Latent Sensible Latent<br />

ZONE LOADS Details (W) (W) Details (W) (W)<br />

Window & Skylight Solar Loads 47 m² 5266 - 47 m² - -<br />

Wall Transmission 78 m² 756 - 78 m² 1348 -<br />

Roof Transmission 0 m² 0 - 0 m² 0 -<br />

Window Transmission 47 m² 1059 - 47 m² 3699 -<br />

Skylight Transmission 0 m² 0 - 0 m² 0 -<br />

Door Loads 0 m² 0 - 0 m² 0 -<br />

Floor Transmission 0 m² 0 - 0 m² 0 -<br />

Partitions 59 m² 187 - 59 m² 664 -<br />

Ceiling 97 m² 212 - 97 m² 751 -<br />

Overhead Lighting 1416 W 1076 - 0 0 -<br />

Task Lighting 0 W 0 - 0 0 -<br />

Electric Equipment 2622 W 2341 - 0 0 -<br />

People 11 543 649 0 0 0<br />

Infiltration - 0 0 - 0 0<br />

Miscellaneous - 0 0 - 0 0<br />

Safety Factor 10% / 10% 1144 65 20% 1292 0<br />

>> Total Zone Loads - 12584 714 - 7754 0<br />

Zone Conditioning - 12961 714 - 7291 0<br />

Plenum Wall Load 0% 0 - 0 0 -<br />

Plenum Roof Load 0% 0 - 0 0 -<br />

Plenum Lighting Load 0% 0 - 0 0 -<br />

Return Fan Load 1050 L/s 0 - 1050 L/s 0 -<br />

Ventilation Load 150 L/s 1343 4014 150 L/s 4135 0<br />

Supply Fan Load 1050 L/s 486 - 1050 L/s -486 -<br />

Space Fan Coil Fans - 0 - - 0 -<br />

Duct Heat Gain / Loss 0% 0 - 0% 0 -<br />

>> Total System Loads - 14790 4728 - 10940 0<br />

Central Cooling Coil - 14790 4729 - 0 0<br />

Central Heating Coil - 0 - - 10940 -<br />

>> Total Conditioning - 14790 4729 - 10940 0<br />

Key: Positive values are clg loads Positive values are htg loads<br />

Negative values are htg loads<br />

Negative values are clg loads<br />

39<br />

Hourly Analysis Program v.4,4 Page 1 of 1