Type MOR Modular Overload Relay<br />

The Westinghouse Modular Overload Relay<br />

(MOR) is a three-pole overload relay with<br />

discrete solid state components. The MOR<br />

consists of three small current transformers,<br />

an output circuit and overload logic. The<br />

CT's monitor all three phases and provide<br />

basic input to the ove rload. This same input<br />

is used to communicate to the special function<br />

modules. The overload and/or special function<br />

modules then send a trip signal to the<br />

isolated NC contact. A plug-in heater module<br />

protects all three phases and aLE D provides<br />

positive trip indication. The MOR will operate<br />

in ambient temperatures ranging from -30'C<br />

to +80'C.<br />

Plug-in modules are available for such<br />

special functions as Phase Unbalance, Long<br />

Acceleration, Underload and Jam.<br />

List Prices, Panel Mounted (Dis. C1 0-S1 9)<br />

Full load Max Hp, Catalog List<br />

4BO Volts Number Price<br />

3.B·25 10 MOR·l $100<br />

6.5-43 15 MOR·2 100<br />

20.5·135 100 MOR·4 100<br />

HTM Heater Modules<br />

HTM plug-in heater modules maintain a<br />

closer tri p tolerance than do thermal overload<br />

relays. Only one module is needed to<br />

protect all three phases of the motor in ambients<br />

ranging from -30'C to +80'C.<br />

Heater list Price: $9 each. Discount Cl 0-S1 9<br />

Heater Selection<br />

Each heater module is identified by a catalog<br />

number. The application table at right indicates<br />

the range of full load motor current to<br />

which a given heater may be applied. Heaters<br />

should be selected on the basis of the actual<br />

full load current and service factor as shown<br />

on the motor nameplate or in the manufacturers<br />

published literature.<br />

Heater Module Application Table<br />

Heater<br />

Cat.<br />

No.<br />

HTM03<br />

HTM04<br />

HTM05<br />

HTM06<br />

HTM07<br />

HTMOB<br />

HTM09<br />

HTM10<br />

HTMl l<br />

HTM12<br />

HTM13<br />

HTM14<br />

HTM15<br />

HTM16<br />

HTM 17<br />

HTM1 8<br />

HTM1 9<br />

HTM20<br />

HTM21<br />

HTM22<br />

HTM23<br />

HTM24<br />

HTM25<br />

HTM26<br />

HTM27<br />

HTM28<br />

HTM29<br />

HTM30<br />

HTM31<br />

HTM32<br />

Motor Full Load Amperes<br />

'r;XoRT--�2 ��'M0R-4 -<br />

2.6 2.B 4.4 - 4.7 14.4 15.2<br />

2.8 3.05 4.7 · 5.1 15.2 16.7<br />

3.05 · 3.3 5.1 5.6 16.7 - 18.2<br />

3.3 - 3.5 5.6 59 lB.2 . 19.1<br />

3.5 · 3.7 5.9 · 6.2 19.1 20.0<br />

3.7 3.9 6.5 20.0 21 .1<br />

3.9 - 4.1 6.8 21 .1 22.1<br />

4.1 . 4.3 6.8 7.2 22.1 - 23.5<br />

4.3 · 4.6 7.2 7.7 23.5 - 24.6<br />

4.6 . 4.9 7.7 8.2 24.6 26.5<br />

4.9 · 5.3 8.2 - 8.9 26.5 28.2<br />

5.3 5.7 8.9 . 9.4 28.2 29.9<br />

5.7 - 6.2 9.4 10.1 29.9 · 32.2<br />

6.2 - 6.6 10.1 11.1 32.2 · 34.5<br />

6.6 · 7.2 11.1 12.0 34.5 · 37.5<br />

7.2 · 7.7 12.0 - 1 3.1 37.5 · 40.8<br />

7.7 8.2 13.1 . 13.8 40.B - 42.6<br />

8.2 - 8.7 13.B · 14.4 42.6 44.6<br />

8.7 - 9.0 14.4 • 15.0 44.6 · 45.1<br />

9.0 · 9.5 15.0 15.8 45.1 - 48.2<br />

9.5 · 10.2 15.8 · 17.0 48.2 - 51 .2<br />

10.2 11.0 17.0 - 1 8.1 51.2 • 55.0<br />

11.0 - 11.7 1 B.l - 19.5 55.0 - 59.0<br />

11.7 - 12.6 19.5 21 .2 59.0 - 63.3<br />

12.6 · 13.B 21 .2 . 23.2 63.3 · 68.9<br />

13.8 • 15.1 23.2 - 25.0 68.9 75.7<br />

15.1 16.7 25.0 . 28.2 75.7 84.0<br />

16.7 - 1 8.6 2B.2 31 .8 84 95<br />

18.6 . 21 .5 31.8 37.1 95 - 107.5<br />

21 .5 . 25.4 37.1 . 42.5 107.5 - 130<br />

8220 CWE A<br />

Catalog Section<br />

Page 17<br />

Overload Relay Curve<br />

'"<br />

'0<br />

c:<br />

0<br />

u<br />

Q)<br />

if)<br />

'"<br />

E<br />

f=<br />

300<br />

200<br />

175<br />

150<br />

125<br />

100<br />

75<br />

50<br />

25<br />

°c<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I<br />

I Q,<br />

� I<br />

I<br />

2!<br />

c I<br />

E I<br />

E<br />

::> I<br />

'* I<br />

)2 I<br />

I<br />

II<br />

100<br />

Overload<br />

Tr ip Zone<br />

�permi SSive Operati:og Zone<br />

I<br />

\<br />

\<br />

L , (7<br />

\<br />

No Trip<br />

" Cold " Start<br />

Secondsa! 600%)<br />

llHotllStart<br />

\ (4Secondsat600%)<br />

"<br />

",<br />

.... .<br />

LL...--::c.L' =---=",' :--�I_. ____ M:'--t-- -x-<br />

200 300 400 500 600 700<br />

Current, % of Heater Ra!ing<br />