Download - Daman and Diu Electricity Department, Government of ...
Download - Daman and Diu Electricity Department, Government of ...
Download - Daman and Diu Electricity Department, Government of ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
SECTION - I<br />
1-A GENERAL TERMS AND CONDITIOINS<br />
1.1 <strong>Electricity</strong> <strong>Department</strong>, UT <strong>of</strong> <strong>Daman</strong> & <strong>Diu</strong> is setting up 66/11 KV, 2 x 15 MVA, 66KV<br />
Sub along with 66 KV D/C line, as shown in single line diagram at Bhimpore <strong>Daman</strong>. The<br />
location at 15Kms away from Vapi Railway Station on Western Railway.<br />
1.2 This tender covers the design, engineering, manufacture, inspection, supply, storage at site<br />
assembly, erection, testing <strong>and</strong> commissioning <strong>of</strong> 66/11kv, 2x15 MVA Sub-station at<br />
Bhimpore & 66 KV D/C line for feeding the S/S. The details <strong>of</strong> works & as given in Section<br />
IV <strong>of</strong> this document.<br />
1.3 All the equipments designs should be confirm to relevant IS/IEC Specification ended up to<br />
date as per latest IS/IEC .The Equipments covered in this specification shall be complete in<br />
all respect & any device not included in specification but essential for proper design,<br />
operation & maintenance <strong>of</strong> the equipment <strong>and</strong> completion <strong>of</strong> this project as a whole shall be<br />
included in the <strong>of</strong>fer by indicating the reason for same.<br />
1.4 The Tenderer shall study the entire specification & satisfy himself thoroughly regarding the<br />
workability <strong>of</strong> the equipment as a whole & shall take full responsibility for the guaranteed<br />
operation <strong>of</strong> the equipment as regards output, performance, safe, smooth & reliable working.<br />
1.5 Deviation form specification, if any, shall be brought out clearly in the <strong>of</strong>fer separately. If the<br />
deviation are not brought out clearly & agreed prior to order placement, the purchaser will<br />
not consider the same at a later date.<br />
1.6 The Tenderer if he so desires, may visit the site & ascertain local condition, traffic<br />
restriction, labour condition, accommodation etc. he may require for his staff, site condition<br />
& other observation in the area, if any, & allow for any extras likely to be incurred due to any<br />
or all the above in his quoted rates. No additional claim whatsoever will be admissible later,<br />
on these grounds.<br />
1.7 All equipment as well as accessories & fitting shall be st<strong>and</strong>ardized so as to reduce inventory<br />
as well to facilitate maintenance.<br />
1.8 The purchaser reserves the right to selecting a particular manufacturer <strong>of</strong> electrical equipment<br />
in the interest <strong>of</strong> st<strong>and</strong>ardization & the contractor shall supply equipment <strong>of</strong> the particular<br />
make if so required.<br />
1.9 SYSTEM DATA<br />
System Voltage <strong>and</strong> : 66 KV Solidly earthed<br />
System <strong>of</strong> Earthing : 11 KV Solidly earthed<br />
415 V Solidly earthed<br />
Rated frequency : 50 Hz<br />
Voltage variation : 66 KV + 10 %<br />
11 KV + 10%<br />
415 V + 10 % - 15 %<br />
Frequency variation : + 5 %<br />
Three phase symmetrical : 66 KV: 3000 MVA<br />
Short circuit level for 11 KV: 500 MVA<br />
Selection <strong>of</strong> equipment 415 V: 40 MVA<br />
12